background image

2

ATICS-BP-SET_D00162_00_M_DEEN/04.2017

ATICS-BP-2-…-SET, ATICS-

The ATICS® transfer switching device has to be connected to
Line 1. The auxiliary contact installed on the ATICS® recognises
the switching position of the transfer switching device with the
effect that the green LED signals "Bypass enabled".

A

In normal operating condition, the rotary handle of the 
ATICS-BP-… bypass switch is in switch position "I" (Nor-
mal) position. Then the rotary handle may be activated. As 
soon as this switch position is left, the auxiliary contact 
installed in the bypass switch sends the alarm message 
"Manual mode" to the digital input IN1of the ATICS®. This 
alarm message appears on the ATICS's display und will 
simultaneously be signalled via the BMS bus (e.g. to 
SCADA systems). 

B

In switch position "I+II", the power to the output is redun-
dantly supplied from the ATICS® and the bypass switch. 
This switch position is only to be used to switch immedi-
ately to the next switch position.

C

In switch position "II" (Bypass), the power to the output is 
supplied from the bypass switch only. Now it is possible to 
test or replace the ATICS® transfer switching device with-
out interruption of the power supply on Line 3. 

Front view ATICS-BP-2-…

Legend to the front view ATICS-BP-2-…

1

Locking device for the rotary handle (see page 9)

2

Rotary handle (here in switch position "I" resp. in "Nor-
mal" position)

3

Terminal cover

4

Connection to the ATICS® output

5

Connection to the preferred line

6

Auxiliary contact for alarm message "Manual mode"

7

Bridge

8

Outgoing line to the distribution board

9

Indicator light green/red (green = Bypass enabled)

10

Auxiliary contact for ATICS

11

Connection to auxiliary contact (contacts 1 and 2)

Das Umschaltgerät ATICS® muss auf Leitung 1 geschaltet sein.
Der am Umschaltgerät ATICS® montierte Hilfskontakt erkennt die
Schaltposition des Umschaltgerätes und bewirkt, dass die grüne
Leuchte „Freigabe Bypass“ signalisiert.

A

Im Normalbetrieb steht der Drehgriff des Bypass-Schalters 
ATICS-BP-2-… in Schaltposition „I“ (Normal). Der Drehgriff 
darf nun betätigt werden. Sobald diese Schaltposition ver-
lassen wird, wird durch den am Bypass-Schalter mon-
tierten Hilfskontakt eine Alarmmeldung „Handbetrieb“ an 
den digitalen Eingang IN1 des ATICS® gegeben. Diese 
Alarmmeldung erscheint im Display des ATICS® und wird 
gleichzeitig über den BMS-Bus gemeldet (z.B. an die 
Gebäudeleittechnik (GLT)). 

B

In Schaltposition „I+II“ erfolgt die Speisung des Ausgangs 
redundant über ATICS® und den Bypass-Schalter. Diese 
Schaltposition darf nur genutzt werden, um sofort weiter 
auf die nächste Schaltposition zu schalten.

C

In Schaltposition „II“ (Bypass) wird der Ausgang nur noch 
über den Bypass-Schalter gespeist. Die Prüfung oder der 
Austausch des Umschaltgerätes ATICS® ist nun ohne Span-
nungsunterbrechung auf Leitung 3 möglich. 

Frontansicht ATICS-BP-2-…

Legende der Frontansicht ATICS-BP-2-…

1

Abschließvorrichtung für Drehgriff (siehe Seite 9)

2

Drehgriff (hier in Schaltposition „I“ bzw. „Normal“)

3

Klemmenabdeckung

4

Anschluss an Ausgang ATICS®

5

Anschluss an bevorzugte Leitung

6

Hilfskontakt für Alarmmeldung „Handbetrieb“

7

Brücke

8

Abgang  zum  Verteiler

9

Leuchtmelder grün/rot (grün = Freigabe Bypass)

10

Hilfskontakt für ATICS

11

Anschluss Hilfskontakt (Kontakte 1 und 2)

II

I

1

2

4

6

5

7

8

6

10

9

3

11

Summary of Contents for ATICS-BP-2 SET Series

Page 1: ...Bypass Schalter Set f r ATICS Bestimmungsgem e Verwendung Der Bypass Schalter ATICS BP erm glicht die Pr fung und den Austausch des Umschaltger tes ATICS ohne die Stromversor gung der Leitung hinter...

Page 2: ...ne to the distribution board 9 Indicator light green red green Bypass enabled 10 Auxiliary contact for ATICS 11 Connection to auxiliary contact contacts 1 and 2 Das Umschaltger t ATICS muss auf Leitun...

Page 3: ...svoltageatthecontactsofLine1 Plugmustnot be touched unless the part is isolated DANGER Frontansicht ATICS BP 4 Montage und Anschluss Das Geh use eignet sich zum Einbau in Installationsverteiler DIN 43...

Page 4: ...lide lock is properly snapped into position by pulling slightly the lower part of the enclosure 1 2 Ma bild ATICS BP 4 125A Alle Ma e in mm Ma e f r Schraubmontage auf Platte Klemmenabdeckung demontie...

Page 5: ...Check all the screws on a regular basis to make sure they are seated tightly DANGER CAUTION DANGER Schraubmontage auf Platte ATICS mit Befestigungsschrauben M5 auf Montageplatte befes tigen siehe Ma...

Page 6: ...6 ATICS BP SET_D00162_00_M_DEEN 04 2017 ATICS BP 2 SET ATICS Connection example ATICS 2 DIO with ATICS BP 2 Anschlussbeispiel ATICS 2 DIO mit ATICS BP 2...

Page 7: ...7 ATICS BP SET_D00162_00_M_DEEN 04 2017 ATICS BP 2 SET ATICS BP 4 SET Connection example ATICS 4 DIO with ATICS BP 4 Anschlussbeispiel ATICS 4 DIO mit ATICS BP 4...

Page 8: ...a I II to position I Never remain in switch position I II A warning sign with such a reference is to be placed in the vicinity of the bypass switch CAUTION WARNING Inbetriebnahme 1 Bypass Schalter ATI...

Page 9: ...40 C 70 C Operating mode continuous operation Position any position Screw mounting 4 x M5 Drehgriff mit Vorh ngeschloss abschlie en Der Drehgriff kann nur in der Schaltposition I Normal abge schlossen...

Page 10: ...Bypass Schalter ATICS BP entspricht den Vorschriften DIN EN 60947 3 VDE 0660 107 und IEC 60947 3 DIN rail mounting acc to DIN EN 60715 IEC 60715 Weight ATICS BP Single device with auxiliary contact br...

Page 11: ...IN rail mounting AC 80 A B92057260 ATICS BP 4 125A SET Bypass Schalter Set bestehend aus Bypass Schalter 125 A einzeln 4 polig Schaltfolge I I II II mit Hilfs kontakt Br cke Klemmenabdeckung Hilfskont...

Page 12: ...behalten Bender GmbH Co KG All rights reserved Reprinting and duplicating only with permission of the publisher Subject to change Bender GmbH Co KG Fotos Bender Archiv Photos Bender archives Bender Gm...