Technical Documentation
BLR-CM Modbus
Rev. 05
2018-09
14
524
Target cos φ 2 (0...100…200 = i0.00...1.00…c0.00)
1
UINT16
-
525
control sensitivity
1
UINT16
%
526
Tolerance switch cycles balancing
1
UINT16
%
527
Alarm Enable Output Mask 1 (OM1)
1
UINT16
-
528
Alarm action: „Switch Alarm Relay (M)“ (OM1)
1
UINT16
-
529
Alarm action: „Switch DO-Relay (DO)“ (OM1)
1
UINT16
-
530
Alarm action: „Show Display Message (D)“ (OM1)
1
UINT16
-
531
Alarm action: „Target COS-PHI 2 (CP)“ (OM1)
1
UINT16
-
532
Alarm action: „Switch Controll off (O)“ (OM1)
1
UINT16
-
533
Alarm action: „Freeze Control (F)” (OM1)
1
UINT16
-
533
Limit alarm temperature 1 x 10
1
UINT16
°C
534
Limit alarm temperature 2 x 10
1
UINT16
°C
535
Hysteresis temperature x 10
1
UINT16
°C
536
Limit alarm THD U x 10
1
UINT16
%
537
Limit alarm THD I x 10
1
UINT16
%
539
Limit warning step size
1
UINT16
%
540
Limit warning switch cycles
2
UINT32
-
542
Limit alarm active power P
2
UINT32
W
544
Limit alarm reactive power Q
2
UINT32
var
546
pf alarm min (0...100...200 = i0.00...1.00...c0.00)
1
UINT16
-
547
pf alarm max (0...100...200 = i0.00...1.00...c0.00)
1
UINT16
-
548
pf alarm delay time
1
UINT16
s
555
Switching time delay Step exchange x 10
1
UINT16
s
556
Delay time fast control
1
UIN16
per
557
Max. step size (fast control)
1
UINT16
var
559
Mean Q. (fast control)
1
UINT16
Var
560
Datalogger storage interval (0…720)
(Only available with option –DM)
1
UINT16
Min
561
Fast Control Output Mask 1 (OM1)
(Only available with option 1PH: -06T, -12T, -12RT)
Note: Just the THD-U Bit is allowed
1
UINT16
-
562
Alarm frequency: lower limit
(450…(MaxValue-10) = 45,0Hz…(MaxValue-0,1Hz))
1
UINT16
Hz
563
Alarm frequency: upper limit
((M10)…650 = (M0,1Hz)...65,0Hz)
1
UINT16
Hz
564
Alarm Enable Output Mask 2 (OM2)
1
UINT16
-
565
Alarm action: „Switch Alarm Relay (M)“ (OM2)
1
UINT16
-
566
Alarm action: „Switch DO-Relay (DO)“ (OM2)
1
UINT16
-