background image

VAV-Universal Retrofit-Set 

Installation

www.belimo.eu

M4-VAV-Universal Retrofit Set • en • v1.1 • 04.2011 • Subject to changes

9 / 9

VRD3-RE2 setting with VAV adjustment tool ZTH-VAV 

(continued)

Connection

Connection to

Cable type and order designation

VRD3-RE2, RJ «Service» socket

ZK-GEN

Accessories

PP connection (terminal 4), e.g. control 

cabinet terminals

ZK2-GEN

Accessories

white
blue

turquoise

GND

PP

1
2

4

3

~ / +

ZTH-VAV

▲ ▼ – + OK

1

4

2

VRD2

VRD3

Power

Ser

vice

Actuator

min

%

nom

max

%

nom

Too

l

Tool

ZK6-GEN

ZK2-GEN

white

blue

turquoise

For detailed documentation concerning the handling and function of the ZTH-VAV, see ZTH-VAV instruction 

manual at www.belimo.eu

Carry out adaption

An angle of rotation adaption of the damper actuator is recommended at the time of initial 

commissioning. An angle of rotation adaption must however be carried out after the adjustment 

of the angle of rotation limitations.

Procedure:

– Switch on the 24 V supply on the VRD3-RE2

– Press the «Adaption» pressure switch on the damper actuator (actuator travels 

CLOSED … OPEN … setpoint position)

Performance check

A performance check is recommended after the installation of the VAV controller and the 

completion of the adaption.

– Set the VAV controller with the ZTH-VAV to maximum and then afterwards to minimum air 

volume («

max

»/«

min

»).

→ Check whether the required amounts of air have been attained.

Note

Additional optimisation options can be achieved 

together with the single room controllers CR24. 

Information concerning these options can be 

found on the Belimo web site www.belimo.com

Summary of Contents for VRD3-RE2-SET

Page 1: ...thout prior notification For the current edition of the operating instructions see www belimo eu 1 VAV controller VRD3 RE2 2 Damper actuator NM24A V RE2 3 Pick up device ZPD RE2 4 Anti rotation strap...

Page 2: ...B mm 280 220 315 247 355 279 400 314 1 1 4 3 2 4 D 100 250 D 280 400 Dismantling the existing VAV controller Electrical connection 1 In the control cabinet undo supply signal cable to the outgoing ter...

Page 3: ...he VAV unit The auxiliary template is located on the packaging of the set 2 Mount pick up device seal 3 Bore an opening in the duct hole size 36 mm Installation 1 Installation of the pick up device in...

Page 4: ...of the new damper actuator Spindle clamp installation The damper actuator for VAV boxes NM24A V RE2 is equipped with the base plate for form fit mounting The front mounting clip may not be used under...

Page 5: ...orientation aid for placing the end stops 25 1mm Note Incorrect settings can lead to damage to the damper blade and to a diminishment of the quality of the control Installation of the new damper actua...

Page 6: ...s or universal mounting brackets are not required and remain left over after completion of the installation Operation setup connection Setup connections VRD2 VRD3 50 60Hz 24VA C DC 1 5W 3VA IP42 Power...

Page 7: ...m3 h 1134 m3 h min x 100 20 230 m3 h 1134 m3 h max x 100 88 1000 m3 h 1134 m3 h min x 100 20 230 m3 h 1134 m3 h Operation setup connection continued Connecting terminals 1 7 Terminal Designation Funct...

Page 8: ...ffective value 0 100 Tool PP Tool parameterised value Automatic adjustment via potentiometer position w write Tool r w r read Note concerning difference min setting VRD3 VRD2 The adjustment range of t...

Page 9: ...angle of rotation adaption of the damper actuator is recommended at the time of initial commissioning An angle of rotation adaption must however be carried out after the adjustment of the angle of ro...

Reviews: