Setting and first commissioning

Adjusting the volumetric flow

The adaptation of the VAV-Universal Retrofit Set to the nominal width of the VAV/CAV unit is 

accomplished by shortening the pick-up device in accordance with the auxiliary template (see 

page 3). No further calibration of the controller to the system is required.

The adaptation of the volumetric flow to the system is accomplished with the setting of the two 

operating volumetric flow parameters 

min

 and 

max

.

The settings for 

min

 and 

max

 can be readily calculated with the aid of the table below and the 

associated formulas.

Table, formulas

VRD3-RE2

Diameter VAV-

Box

nom

[l/s]

nom

[m

3

/h]

Formulas

100

9

349

112

125

450

125

153

551

140

195

02

10

250

900

180

315

1134

200

403

1451

224

525

1890

250

1

2221

280

95

282

315

1028

301

355

125

4590

400

1

034

max

 in % = 

x 100

x 100

max

 [l/s, m

3

/h]

nom

 [l/s, m

3

/h]

min

 in % = 

min

 [l/s, m

3

/h]

nom

 [l/s, m

3

/h]

Example

Data

Calculation/result

VAV unit diameter

180 mm

nom

 from Table

1134 m

3

/h

max

1000 m

3

/h

min

230 m

3

/h

max

 = 

x 100 = 88 %

1000 m

3

/h

1134 m

3

/h

min

 = 

x 100 = 20 %

230 m

3

/h

1134 m

3

/h

max

 = 

x 100 = 88 %

1000 m

3

/h

1134 m

3

/h

min

 = 

x 100 = 20 %

230 m

3

/h

1134 m

3

/h

Operation, setup, connection 

(continued)

Connecting terminals 1 … 7

Terminal

Designation

Function

1

 / –

Supply 24 VAC/DC

2

~

 / +

3

w

Reference value input w jumper 

VRD3

VRD2

– Mode 0 … 10/2 … 10V switchable with ZTH-VAV

– Function as with new VAV-Compact L/N/SMV-D2-MP:

VAV: 0 … 10/2 … 10V = 

min

 … 

max

CAV: CLOSED/

min

/

max

/OPEN

Reference value input w jumper 

VRD3

VRD2

– Mode 0 … 10/2 … 10V switchable with ZTH-VAV

– Function as with VRD2:

VAV: 0 … 10/2 … 10V = 

min

 … 

max

CAV: not possible  

use Z1 / Z2

4

PP

PP interface for ZTH-VAV (no MP operation)

5

U5

Actual volumetric flow signal U5

– Mode 0 … 10/2 … 10V switchable with ZTH-VAV

– Display range 0 … 100% 

nom

Z1

Override input Z1: Function OPEN

Z2

Forced control input Z2: function CLOSED/

min

/

max

For a detailed description of the VAV controller VRD3, we draw your attention to the separate product 

information, see www.belimo.eu ¦ Documentation ¦ Room and System Solutions.

Notes

– Supply via safety isolation transformer!
– It is recommended that the PP connection 

(terminal 4) and the 24V be wired to readily 

accessible terminals in order to guarantee easy 

access with the VAV adjustment tool ZTH-VAV 

(e.t. at the room temperature controller CR24 or 

in the control cabinet).

The VRD3 does not support any MP operation!

!

min

nom

max

10 V

0 / 2 V

U5 

W

10 V 

0 / 2 V

. . 

. . 

. . 

. . 

. . 

. . 

. . 

. . 

. . 

. . 

. . 

. . 

. . 

. . 

. . 

. . 

. . 

. . 

. . 

. . 

. . 

. . 

. . 

. . 

. . 

. . 

. . 

. . 

. . 

. . 

.

Summary of Contents for VRD3-RE2-SET

Page 1: ...thout prior notification For the current edition of the operating instructions see www belimo eu 1 VAV controller VRD3 RE2 2 Damper actuator NM24A V RE2 3 Pick up device ZPD RE2 4 Anti rotation strap...

Page 2: ...B mm 280 220 315 247 355 279 400 314 1 1 4 3 2 4 D 100 250 D 280 400 Dismantling the existing VAV controller Electrical connection 1 In the control cabinet undo supply signal cable to the outgoing ter...

Page 3: ...he VAV unit The auxiliary template is located on the packaging of the set 2 Mount pick up device seal 3 Bore an opening in the duct hole size 36 mm Installation 1 Installation of the pick up device in...

Page 4: ...of the new damper actuator Spindle clamp installation The damper actuator for VAV boxes NM24A V RE2 is equipped with the base plate for form fit mounting The front mounting clip may not be used under...

Page 5: ...orientation aid for placing the end stops 25 1mm Note Incorrect settings can lead to damage to the damper blade and to a diminishment of the quality of the control Installation of the new damper actua...

Page 6: ...s or universal mounting brackets are not required and remain left over after completion of the installation Operation setup connection Setup connections VRD2 VRD3 50 60Hz 24VA C DC 1 5W 3VA IP42 Power...

Page 7: ...m3 h 1134 m3 h min x 100 20 230 m3 h 1134 m3 h max x 100 88 1000 m3 h 1134 m3 h min x 100 20 230 m3 h 1134 m3 h Operation setup connection continued Connecting terminals 1 7 Terminal Designation Funct...

Page 8: ...ffective value 0 100 Tool PP Tool parameterised value Automatic adjustment via potentiometer position w write Tool r w r read Note concerning difference min setting VRD3 VRD2 The adjustment range of t...

Page 9: ...angle of rotation adaption of the damper actuator is recommended at the time of initial commissioning An angle of rotation adaption must however be carried out after the adjustment of the angle of ro...

Reviews: