Gateway MP to L
ON
W
ORKS
®
●
MP/LON interface
●
MFT(2)/MP actuators (with MP
communications capability)
linked to L
ON
W
ORKS
®
through
a UK24LON unit
●
Up to 8 actuators
can be connected
●
L
ON
M
ARK
®
certified
Application
The UK24LON unit is a Belimo gateway
that has been certified by L
ON
M
ARK
®
. It
allows the Belimo MP-Bus to be linked to
L
ON
W
ORKS
®
.
Up to 8 MP capable actuators can be
connected to the MP-Bus side of the sys-
tem (damper actuators, valve actuators
and VAV-Compact).
Mode of operation
Through the UK24LON unit the actua-
tors can be controlled digitally over the
MP-Bus and they also provide feedback
of their current operating status. In the
UK24LON unit the digital data for control
and feedback is converted to standard
network variables (SNVT’s). This allows
the functions of the actuators to be linked
directly to L
ON
W
ORKS
®
.
Sensor connection
One sensor can be connected to each
MFT2 actuator. It can be either a passive
resistance-type sensor (Pt1000, Ni1000
or NTC), an active sensor (e.g. with a
DC 0...10 V output) or a switching con-
tact. This provides a simple means of
digitising the analogue signal from the
sensor through the actuator so that it
can be passed on to L
ON
W
ORKS
®
via the
UK24LON unit.
Parameterising MFT(2)/MP actuators
Using the Belimo PC-Tool it is very easy to
preset specific parameters (e.g. running
time) for individual actuators. An MFT pa-
rameterising tool can be connected to the
3-pole plug socket of the UK24LON unit.
Important installation note!
Do not energise the system
(UK24LON and actuators) until
all the wiring has been finished.
4
Technical data
UK24LON unit
Power supply
AC 24 V 50/60 Hz, DC 24 V
Functional range
AC 19.2...28,8 V, DC 21.6...28.8 V
For wire sizing
3 VA (without MFT(2)/MP actuators connected)
Power consumption
1.5 W
Connections
L
ON
W
ORKS
®
:
push-screw terminals, 2-pole
Power:
push-screw terminals, 3-pole
MFT(2)/MP-
push-screw terminals, 4-pole
actuators:
(all terminals for 1,5 mm
2
)
MFT-H:
plug socket, 3-pole
(f
or MFT parameterising tools)
Processor/Memory
Neuron 3150
®
; 10 MHz; 48 kB flash memory, 8 kB RAM
Transceiver
FTT-10A compatible with LPT-10
Functional Profile
Damper Actuator 8110; see page 8
For further detailed information refer to the L
ON
M
ARK
®
web site (www.lonmark.org)
LNS-Plug-In
The following are available for LonMaker 2.0:
(configuration
Modifiable
– MFT(2)/MP actuator addresses
software)
with Plug-In:
– Min./Max. limits
– Definition of sensors connected
to the MFT(2)/MP actuators
Communication with
Belimo-MP-Bus: Master-Slave system 1200 Baud
MFT(2)/MP actuators
No of MFT(2)/MP actuators up to 8 actuators can be connected
Maximum MP
Depends on the number of MFT(2)/MP actuators connected,
conductor length
types of actuators, type of power supply and crosssectional
area of the conductor. Refer to the diagram on page 7
L
ON
W
ORKS
®
In accordance with Echelon recommendations
conductor lengths and
transmission media
Ambient temp. range
0 ºC...+50 ºC
Protection class
(safety extra-low voltage)
Degree of protection
IP20
EMC
CE in accordance with 89/336/EU, 92/31/EU, 93/68/EU
Mounting
DIN rail 35 mm
Weight
ca. 500 g
24 V
MP
T~/+
~
-
+
T
AC 24 V
DC 24 V
Connect
through a safety
transformer
MP-Bus
MP-Bus
It is essential to take account of the dimen-
sion data of the connected MFT(2)/MP
actuators when selecting the ratings for the