UK24BAC
Belimo Gateway MP to BACnet MS/TP
www.belimo.com
UK24BAC • en • v1.9 • 06.2018 • Subject to changes
7 / 20
Electrical installation
(continued)
With DC 24 V supply:
Calculation of the maximum signal
conductor lengths
To be read out from the mass of curves:
For cables with wire-Ø
[mm²]
Cable length
[m]
0.75
55
1.00
75
1.50
110
2.50
190
The power consumption [W] of the MP/MPL/MFT(2) actuators used is to be added, and the
corresponding signal conductor lengths are to be read from the diagram.
Example:
The following is connected to the MP-Bus: 1 pc. NM24A-MP, 1 pc. SM24A-MP, 1 pc. LMV-D3-
MP and 1 pc. NV24A-MP
Total power rating 3.5 W + 4 W + 3 W + 3 W = 13.5 W
Dimensions
Dimensional drawings [mm]