UK24BAC
Belimo Gateway MP to BACnet MS/TP
www.belimo.com
UK24BAC • en • v1.9 • 06.2018 • Subject to changes
15 / 20
BACnet object description
(continued)
Object Name
Object Type / Instance
Description
Values
Default
MIN_STPT_[n]
Analog Value
[n*100+1]
Minimum limit (position or flow) in %
Attention: Changing the limit may result in
malfunction of the device.
0…100
-
MAX_STPT_[n]
Analog Value
[n*100+2]
Maximum limit (position or flow) in %
Attention: Changing the limit may result in
malfunction of the device.
20…100
-
NOM_FLOW_[n]
Analog Value
[n*100+3]
Nominal volumetric flow (or pressure)
The unit depends on the node type:
[m3/h] for VAV controllers
[Pa] for VAV controller in STP mode
[l/min] for EPIV units
0…65535
-
Connecting the PC-Tool for parameterisation of the MP/MFT(2) actuators
The MP network can be scanned, actuators can be addressed and actuator-specific parameters
(e.g. running time) can be readily adjusted with the Belimo PC-Tool.
The PC -Tool can be accessed directly on the MP-Bus via the RJ12 socket of the
UK24BACMOD. The Gateway recognises the connected PC-Tool automatically and stops
communications with the MP drives.
MP-Bus
Belimo
PC-Tool
ZK6-GEN
Summary of Contents for UK24BAC
Page 20: ......