Application 

 

The filling level limit switch 

SRA – 100  8M

 

is used, to evaluate one or two filling levels resp. limit levels in 

electrically conductive liquids with a conductivity of minimum 0,125µS/cm resp. a resistance of maximum 8M

.  

 

For the connection of level resp. measurement transducer in explosion hazardous areas, the device is equipped 

with two intrinsically safe supply and signal circuits. 

 

Function 

 

Measuring principle 

 

The signal circuit of the filling level limit switch is connected to the reference electrode or the metallic wall of the 

container resp. pipe and to the measuring electrode. 

 

The alternating voltage, that is generated by the integrated electronic is than applied either between the 

electrode rods or between the electrode rods and the metallic wall of the container resp. pipe that is connected 

to the metallic process connection, realizing the reference electrode. 

 

Due to the use of a alternating voltage the corrosion at the electrode rod and the electrolytic decomposition of 

the filling liquid is avoided. 

 

As soon as the electrically conductive liquid makes a connection between the electrodes resp. between the 

electrode and the metallic wall of the container resp. pipe, an alternating current flows, that causes a decrease 

of the alternating voltage. 

 

Signal evaluation 

 

An evaluation circuit supervises this alternating voltage. A voltage drop is detected and the evaluation circuit 

switches the relay resp. relays, depending on the set safety function. 

 

The switching state of the relays is indicated at the front side of the device by two yellow LED’s. 

 

Switching delay 

 

In some applications it is necessary to compensate heavy signal fluctuations that may be produced by mixing 

machines or at fill-in resp. emptying of containers, to avoid spurious switching actions. 

 

Two switches at the front side of the device allows the configuration of a switching delay of 0,5 / 3 / 5 / 8 s.

  

This delay time effects both channels separately, at activation and deactivation of the filling level relays.

 

 

Sensitivity range 

 

The device can be adjusted in the resistance range 1 to 8 M

. Within this range a fine adjustment can be 

carried out by a trimmer at the front side of the device.

 

 

Configuration of the second output relay S2 

 

The second output relay can be configured in two operation modes: 

  2nd filling level relay to electrode at CH1 (relay switches like filling level relay S1 – parallel mode) 

  Filling level relay to electrode at CH2 (two channel mode: CH1 to S1 / CH2 to S2) 

 

 

Summary of Contents for SRA-100

Page 1: ...ATEX II 1 G Ex ia Ga IIB IIC resp ATEX II 1 D Ex ia Da IIIB IIIC Certification for the connection of conductive level transducer in explosion hazardous areas Measuring range adjustable up to 8M resp 0...

Page 2: ...n 3 Function 3 4 Safety notes 5 Safety notes 5 Installation 5 Maintenance 5 Repair 5 Electrical connection 6 Operation and display elements 7 Technical data 8 Order code SRA 100 U0 8M Basic variant Ex...

Page 3: ...between the electrode and the metallic wall of the container resp pipe an alternating current flows that causes a decrease of the alternating voltage Signal evaluation An evaluation circuit supervises...

Page 4: ...safety function must be set identically for both channels CH1 and CH2 This can be carried out by two switches one per channel at the front side of the filling level limit switch Two position control...

Page 5: ...principally by specialist staff The device meets the classification II 1 G Ex ia Ga IIB IIC resp II 1 D Ex ia Da IIIB IIIC The device is conceived for detection of limit levels at liquids in explosiv...

Page 6: ...ading wires If more than two limit levels with the same reference potential should be evaluated several filling level limit switches could be connected in parallel For this purpose only the reference...

Page 7: ...FF Switch 4 function output relay S1 switch switching state ON switching state OFF 4 two position control s limit level function Switch 5 safety function channel 1 CH1 switch switching state ON switch...

Page 8: ...A 5 A at ATEX variant 300 W 100 W at ATEX variant 110 V 0 3 A 33 W 220 V 0 12 A 26 4 W Switching cycles 100 000 switching cycles at maximum contact load Signal inputs Level transducer One resp two fil...