Electrical connection

 

 

The electrical connection of the device must be carried out according to the respective country specific 

standards. Incorrect installation or adjustment could cause applicationally conditioned risks. 

 

Power supply input, measuring input and relay output channels are safe galvanically isolated from each other. 

This is also valid for both relay output channels among each other. 

 

Connection of the signaling transmitter resp. measuring transducer – measuring inputs 

 

For the two or three-wire connection cable between the filling level limit switch and the signaling transmitter 

resp. measuring transducer a standard installation cable or multi-wire cable for measuring intends with a 

maximum of 25 

 per wire can be used. 

 

The use of a shielded signal cable is not required in principle, but is recommended, if strong electromagnetic 

influences could happens, e.g. due to machines or radio equipment. In that case the shielding of the cable 

should be connected to earth only at the side of signaling transmitter resp. measuring transducer. 

The signal cable should be installed separated from power leading wires. 

 

If more than two limit levels with the same reference potential should be evaluated, several filling level limit 

switches could be connected in parallel. For this purpose only the reference connection of all devices must be 

connected with each other (see scheme below - right).

 

 

Connection of the signaling and control equipments – relay outputs 

 

Inductive loads at the relay contacts, e.g. auxiliary contactors or magnetic vents may only be used with a free-

wheeling diode or a RC protection circuit to avoid high voltage peaks. 

 

For inauguration it is suggested, to deactivate all connected control devices, to avoid unwanted control 

reactions. 

 

Connection of the power supply voltage 

 

Due to the integrated wide range power supply, for connection to supply voltages from 20...253V AC / DC, the 

filling level limit switch is suitable for using in all common energy supply networks. 

At variants with ATEX certificate, the supply voltage range is 20...253V AC resp. 20...125V DC.  

The connection is reverse polarity protected. 

 

A switch, that is marked as separator as well as a over current protection switch (nominal current 

 10 A) must 

be installed near the device into the supply lead.  

 

     single channel operation                   two channel operation                       four channel operation 

                              resp.                    by parallel connection of two 

                              two-position-control 

s                filling level limit switch SRA – 100 

 

 

Summary of Contents for SRA-100

Page 1: ...ATEX II 1 G Ex ia Ga IIB IIC resp ATEX II 1 D Ex ia Da IIIB IIIC Certification for the connection of conductive level transducer in explosion hazardous areas Measuring range adjustable up to 8M resp 0...

Page 2: ...n 3 Function 3 4 Safety notes 5 Safety notes 5 Installation 5 Maintenance 5 Repair 5 Electrical connection 6 Operation and display elements 7 Technical data 8 Order code SRA 100 U0 8M Basic variant Ex...

Page 3: ...between the electrode and the metallic wall of the container resp pipe an alternating current flows that causes a decrease of the alternating voltage Signal evaluation An evaluation circuit supervises...

Page 4: ...safety function must be set identically for both channels CH1 and CH2 This can be carried out by two switches one per channel at the front side of the filling level limit switch Two position control...

Page 5: ...principally by specialist staff The device meets the classification II 1 G Ex ia Ga IIB IIC resp II 1 D Ex ia Da IIIB IIIC The device is conceived for detection of limit levels at liquids in explosiv...

Page 6: ...ading wires If more than two limit levels with the same reference potential should be evaluated several filling level limit switches could be connected in parallel For this purpose only the reference...

Page 7: ...FF Switch 4 function output relay S1 switch switching state ON switching state OFF 4 two position control s limit level function Switch 5 safety function channel 1 CH1 switch switching state ON switch...

Page 8: ...A 5 A at ATEX variant 300 W 100 W at ATEX variant 110 V 0 3 A 33 W 220 V 0 12 A 26 4 W Switching cycles 100 000 switching cycles at maximum contact load Signal inputs Level transducer One resp two fil...