background image

Technical data sheet

NM24A-MP

www.belimo.com

NM24A-MP • en-gb • 2020-12-14 • Subject to change

2 / 7

Override control variable

MAX = (MIN + 32%)...100%

MIN = 0%...(MAX – 32%)

ZS = MIN...MAX

Sound power level, motor

35 dB(A)

Mechanical interface

Universal shaft clamp 8...26.7 mm

Position indication

Mechanically, pluggable

Safety data Protection class IEC/EN

III Safety Extra-Low Voltage (SELV)

Protection class UL

UL Class 2 Supply

Degree of protection IEC/EN

IP54

Degree of protection NEMA/UL

NEMA 2

Enclosure

UL Enclosure Type 2

EMC

CE according to 2014/30/EU

Certification IEC/EN

IEC/EN 60730-1 and IEC/EN 60730-2-14

Certification UL

cULus according to UL60730-1A, UL60730-2-14 and 

CAN/CSA E60730-1:02

Certification UL note

The UL marking on the actuator depends on the 
production site, the device is UL-compliant in any 
case

Mode of operation

Type 1

Rated impulse voltage supply / control

0.8 kV

Control pollution degree

3

Ambient temperature

-30...50°C

Storage temperature

-40...80°C

Ambient humidity

Max. 95% r.H., non-condensing

Servicing

maintenance-free

Weight Weight

0.77 kg

Safety notes

The device must not be used outside the specified field of application, especially not in aircraft or in any 
other airborne means of transport.

Outdoor application: only possible in case that no (sea) water, snow, ice, insolation or aggressive gases 
interfere directly with the device and that it is ensured that the ambient conditions remain within the 
thresholds according to the data sheet at any time.

Only authorised specialists may carry out installation. All applicable legal or institutional installation 
regulations must be complied during installation.

The device may only be opened at the manufacturer's site. It does not contain any parts that can be 
replaced or repaired by the user.

Cables must not be removed from the device.

To calculate the torque required, the specifications supplied by the damper manufacturers concerning 
the cross-section, the design, the installation site and the ventilation conditions must be observed.

The device contains electrical and electronic components and must not be disposed of as household 
refuse. All locally valid regulations and requirements must be observed.

Product features

Conventional operation:
The actuator is connected with a standard modulating signal of 0...10 V and drives to the position defined 
by the positioning signal. The measuring voltage U serves for the electrical display of the actuator position 
0.5...100% and as slave control signal for other actuators.
Operation on Bus:
The actuator receives its digital positioning signal from the higher level controller via the MP-Bus and 
drives to the position defined. Connection U serves as communication interface and does not supply an 
analogue measuring voltage.

Mode of operation

Summary of Contents for NM24A-MP

Page 1: ...nicative control MP Bus Operating range Y 2 10 V Input Impedance 100 k Operating range Y variable Start point 0 5 30 V End point 2 5 32 V Options positioning signal Open close 3 point AC only Modulati...

Page 2: ...solation or aggressive gases interfere directly with the device and that it is ensured that the ambient conditions remain within the thresholds according to the data sheet at any time Only authorised...

Page 3: ...osition defined by the positioning signal A range of settings can be adapted using the PC Tool see MFT P documentation Accessories Gateways Description Type Gateway MP zu BACnet MS TP UK24BAC Gateway...

Page 4: ...ration for flat installation ZG NMA Service tools Description Type Adapter for Service Tool ZTH MFT C Belimo PC Tool Software for adjustments and diagnostics MFT P Service Tool with ZIP USB function f...

Page 5: ...Functions with basic values conventional mode Override control with AC 24 V with relay contacts Override control with AC 24 V with rotary switch Control remotely 0 100 with positioner SG Minimum limi...

Page 6: ...relay contacts Override control and limiting with AC 24 V with rotary switch 1 Caution This function is only guaranteed if the start point of the operating range is defined as min 0 5 V Control open...

Page 7: ...rawings Clamping range Option Accessory K NA Option Shaft clamp mounted below accessories K NA needed Min 40 Min 20 Further documentation Overview MP Cooperation Partners Tool connections Introduction...