Technical data sheet

NF24A-MOD

www.belimo.com

NF24A-MOD • en-us • 2022-03-15 • Subject to change

1 / 7

Communicative rotary actuator fail-safe for 
adjusting dampers in technical building 
installations

• Air damper size up to approx. 2 m²
• Torque motor 90 in-lb [10 Nm]
• Nominal voltage AC/DC 24 V
• Control modulating, communicative, Hybrid
• Conversion of sensor signals
• Communication via BACnet MS/TP, Modbus 

RTU, Belimo-MP-Bus or conventional control

Technical data

Electrical data Nominal voltage

AC/DC 24 V

Nominal voltage frequency

50/60 Hz

Nominal voltage range

AC 19.2...28.8 V / DC 21.6...28.8 V

Power consumption in operation

7 W

Power consumption in rest position

3.5 W

Power consumption for wire sizing

9.5 VA

Connection supply / control

cable 3 ft. [1 m], 6 x 0.75 mm²

Data bus communication Communicative control

BACnet MS/TP
Modbus RTU (default setting)
MP-Bus

Number of nodes

BACnet / Modbus see interface description
MP-Bus max. 8

Functional data Torque motor

90 in-lb [10 Nm]

Torque Fail-Safe

10 Nm

Operating range Y

2...10 V

Operating range Y variable

0.5...10 V

Position feedback U

2...10 V

Position feedback U note

Max. 1 mA

Position feedback U variable

Start point 0.5...8 V
End point 2...10 V

Position accuracy

±5%

Direction of motion motor

selectable with switch L/R

Direction of motion fail-safe

selectable by mounting L/R

Manual override

by means of hand crank and locking switch

Angle of rotation

Max. 95°

Angle of rotation note

adjustable starting at 33% in 2.5% steps (with 
mechanical end stop)

Running Time (Motor)

150 s / 90°

Running time motor variable

40...150 s

Running time fail-safe

<20 s @ -4...122°F [-20...50°C], <60 s @ -22°F 
[-30°C]

Adaptation Setting Range

manual

Adaptation Setting Range Variable

No action
Adaptation when switched on
Adaptation after using the hand crank

Override control, controllable via bus 
communication

MAX (maximum position) = 100%
MIN (minimum position) = 0%
ZS (intermediate position) = 50%

Override control variable

MAX = (MIN + 32%)...100%

MIN = 0%...(MAX – 32%)

ZS = MIN...MAX

Summary of Contents for NF24A-MOD

Page 1: ...Modbus see interface description MP Bus max 8 Functional data Torque motor 90 in lb 10 Nm Torque Fail Safe 10 Nm Operating range Y 2 10 V Operating range Y variable 0 5 10 V Position feedback U 2 10 V...

Page 2: ...pecially in aircraft or in any other airborne means of transport Outdoor application only possible in case that no sea water snow ice insolation or aggressive gases interfere directly with the actuato...

Page 3: ...tically stops when the end stop is reached The first time the supply voltage is switched on i e at the time of commissioning the actuator carries out a synchronization The synchronization is in the ho...

Page 4: ...connection to MP PP terminal ZK2 GEN Electrical installation Supply from isolating transformer The wiring of the line for BACnet MS TP Modbus RTU is to be carried out in accordance with applicable RS...

Page 5: ...15 Subject to change 5 7 Connection with switching contact e g p monitor Requirements for switching contact The switching contact must be able to accurately switch a current of 16 mA 24 V Modbus RTU B...

Page 6: ...ommunication Service plug For connecting parametrisation and service tools Operating elements The manual override locking switch and direction of rotation switch elements are available on both sides S...

Page 7: ...th Min 85 Min 15 Clamping range Further documentation Tool connections BACnet Interface description Modbus Interface description Overview MP Cooperation Partners MP Glossary Introduction to MP Bus Tec...

Reviews: