Performance definition

Qmax is the set maximum power output on the heat exchanger (in power control operating 

mode)

100%

Y [V]

   [kW]  

   

max

Creep flow suppression

Given the very low flow speed in the opening point, this can no longer be measured by the 

sensor within the required tolerance. This range is overridden electronically.

Opening valve

The valve remains closed until the volumetric flow required by the positioning signal Y 

corresponds to 0.5% of  nom(DN15-DN50) / 1.25 of  nom(DN65-DN150). The control 

along the valve characteristic curve is active after this value has been exceeded.

Closing valve (DN15-DN50)

The control along the valve characteristic curve is active up to the required flow rate of 1% 

of  nom. Once the level falls below this value, the flow rate is maintained at 1% of  nom. If 

the level falls below the flow rate of 0.5% of  nom required by the reference variable Y, then 

the valve will close. 

Closing valve (DN65-DN150)

The control along the valve characteristic curve is active up to the required flow rate of 2.5% 

of  nom. Once the level falls below this value, the flow rate is maintained at 2.5% of  nom. 

If the level falls below the flow rate of 0.5% of  nom required by the reference variable Y, 

then the valve will close.

max is the maximum flow rate which has been 

set with the greatest positioning signal, e.g. 10V. 

max can be set to between 30% and 100% of 

nom.

min 0% (non-variable).

0

100%

30%

100%

nom

max

Y [V]

 [m

3

/h]

0

1%

0.5% 1%

100%

Y [V]

 [m

3

/h]

0

2.5%

0.5%

2.5%

100%

Y [V]

 [m

3

/h]

DN15-DN50

DN65-DN150

EV..R+BAC / P6..W..EV-BAC

Product features

Summary of Contents for Energy Valve EV015R+BAC

Page 1: ...Belimo Asia Pacific Technical Databook Belimo Pressure Independent Version 3 2 Control Valve Range Energy Valve...

Page 2: ......

Page 3: ...Energy Valve Energy Valve measures the load coil supply and return temperature and calculates the power or energy consumed and communicates to Higher Building Management levels...

Page 4: ...6EV BAC P6150W4506EV BAC 50 60 50 60 50 60 50 60 50 60 50 60 50 60 50 50 50 50 50 60 60 60 60 60 15 20 25 32 40 50 50 65 80 100 125 150 65 80 100 125 150 5Nm 5Nm 5Nm 10Nm 10Nm 20Nm 20Nm 20Nm 20Nm 40Nm...

Page 5: ...nical data sheet EV R BAC Type overview Technical data Electrical data Nominal voltage AC DC 24V Nominal voltage frequency 50 60Hz Nominal voltage range AC 19 2 28 8V DC 21 6 28 8V Power consumption i...

Page 6: ...N16 Closing pressure ps 1380kPa Differential pressure pmax 350kPa Flow characteristic Equal percentage VDI VDE 2178 linear Leakage rate Air bubble tight Leakage rate A EN12266 1 Pipe connections Inter...

Page 7: ...nom Functional data Torque motor 20Nm DN 65 80 40 Nm DN 100 150 Communication protocol BACnet IP BACnet MS TP TCP IP Belimo MP Bus Positioning signal Y DC 0 10V Operating range Y DC 2 10V Operating ra...

Page 8: ...l 0 8kV Control pollution degree 3 Ambient temperature 10 50 C Non operating temperature 20 80 C Ambient humidity 95 r h non condensing Materials Housing EN JL1040 GG25 with protective paint Measuring...

Page 9: ...trol valve Heat exchanger transfer response Depending on the construction temperature spread medium and hydraulic circuit the power Q is not proportional to the volumetric flow of the water curve 1 Wi...

Page 10: ...15 DN50 The control along the valve characteristic curve is active up to the required flow rate of 1 of nom Once the level falls below this value the flow rate is maintained at 1 of nom If the level f...

Page 11: ...wer output Nevertheless heating or cooling machines must provide the energy at a lower degree of effectiveness Pumps circulate too much water and increase energy consumption unnecessarily With the aid...

Page 12: ...push button possible the gear is disengaged for as long as the button is pressed or remains locked High functional reliability The actuator is overload protected requires no limit switches and automat...

Page 13: ...Display and operating elements Recommended installation positions The ball valve can be installed upright to horizontal The ball valve may not be installed in a hanging position i e with the stem poin...

Page 14: ...the measuring pipe flange Its dimensions should be at least 5x DN Installation of immersion sleeve and temperature sensor DN15 DN50 The valve is equipped with two fully wired temperature sensors T2 Th...

Page 15: ...theor m3 h Example DN25 with the desired maximum flow rate 50 nom Example DN100 with the desired maximum flow rate 50 nom Installation of immersion sleeve and temperature sensor DN65 DN150 The valve...

Page 16: ...69 22 75 177 G1 4 80 247 77 6 0 L H min X min Y D K d If Y 180 mm then the extension of the hand crank must be dismantled as necessary Type DN mm L mm H mm D mm d mm K mm X mm Y mm Weight approx kg P6...

Page 17: ...Representative for details BACnet MS TP 90 90 5 x DN AC 24 V DC 24 V 3 5 6 C1 1 2 T U DC 0 10 V Web Browser Y DC 0 10 V 7 C2 BACnet IP 3 5 6 C1 1 2 Web Browser TCP IP 7 C2 T 3 5 6 C1 1 2 T 7 C2 C2 D B...

Page 18: ...V3 2 03 2015 Subject to modification 18 UL marked actuators is optional please contact your local Sales Representative for details 1 0 8 m 3 0 m EV R BAC Mounting instructions...

Page 19: ...ct to modification UL marked actuators is optional please contact your local Sales Representative for details A AB M Y T 2 1 1 1 2 3a 3b 4 1 3 4 2 1 3 4 2 6 5 7 8 5 M18 130 Nm M20 190 Nm P6 W EV BAC M...

Page 20: ...details 90 90 10 m G L T L DN L 1 G LT 65 400 30 mm 15 mm 1 DN 65 30 mm AC 24 V DC 24 V 1 2 3 5 Y DC 0 10 V U DC 0 10 V T 6 C1 7 C2 Web Browser BACnet IP BACnet MS TP MP Bus 1 2 3 5 T 6 C1 7 C2 TCP IP...

Page 21: ...21...

Page 22: ...22...

Page 23: ...ongkong belimo ch Indonesia Office Belimo Actuators Ltd Graha Kencana Building 8th Floor Block B Jl Raya Perjuangan 88 Kebon Jeruk Jakarta Barat 11530 Indonesia Tel 62 21 5367 8278 Fax 62 21 5366 0688...

Page 24: ...06810 USA Tel 800 543 9038 203 791 9915 Fax 800 228 8283 203 791 9919 AP Belimo Actuators Ltd Room 1601 6 16 F New Commerce Centre 19 On Sum Street Shatin N T Hong Kong Tel 852 2687 1716 Fax 852 2687...

Reviews: