AVK24ALON
Globe valve actuator, communicative, modulating,
AC/DC 24 V, 2000 N
www.belimo.com
AVK24ALON
• en-gb • 2013-04-03 • Subject to modification
7
Notes
More detailed information on the functional
profiles can be found on the website of
LONMARK®. (www.lonmark.org).
Functional profile according to LONMARK®
Functions Inputs Occupancy
Occupancy
specification from
nviOccCmd command
centre
Occupancy switch
nviSenOccCmd
Room operating
status
Comfort extension
OC_OCCUPIED
OC_OCCUPIED
Comfort
OC_UNOCCUPIED Comfort
OC_NUL (default)
Comfort
OC_STANDBY
OC_OCCUPIED
Bypass
Occupied time is
extended by the amount
of the bypass time
(comfort time) (can be
adjusted in the plug-in)
OC_UNOCCUPIED Pre-Comfort
OC_NUL (default)
Pre-Comfort
OC_UNOCCUPIED
OC_OCCUPIED
Building Protection
OC_UNOCCUPIED Building Protection
OC_NUL (default)
Building Protection
OC_NUL (default)
OC_OCCUPIED
Comfort
OC_UNOCCUPIED Pre-Comfort
OC_NUL (default)
Comfort
Funktion nvoHeatCoolOut
100
66
33
0
0
10
33
66
100
90
nvoHeatOutput 0%
nvoHeatOutput 100%
nvoCoolOutput 100
%
nvoCoolOutput 0%
Y
nvoHeatCoolOut
SNVT_lev_percent
[%]
[%]
Frost
Heating
Neutral zone
(dew point not reached)
Cooling
Note
The function nviOccCmd has a higher priority
than the function nviSenOccCmd.
Typical application
Heating / cooling with Belimo
6-way characterised control valve.
Note chilled ceiling application
In the case of active DewPointAlarm
(nviDewPointAlarm), the controller will be
set to the Building Protection setpoints. The
cooling sequence is deactivated.