Status
Serv ice
POP
1
2
7
10
8
5
9
6
Powe r
Adaption
0.5
Tool
3
4
(1) Direction of stroke switch
Switching: Direction of stroke changes
(2) Cover, POP button
(3) POP button
(4) Scale for manual adjustment
(5) Position for adjustment with tool
(6) Service plug
For connecting the parameterisation and service tools
(7) Gear disengagement button, temporary
Press button: Gear disengages, motor stops, manual override possible
Release button: Gear engages, standard mode
(8) Service button for commissioning with LONWORKS®
Press button: Service Pin Message is sent on LONWORKS® network
(9) Push-button
Press button: Switches on stroke adaption, followed by standard mode
(
10) Manual override
Clockwise: Actuator spindle extends
Counterclockwise: Actuator spindle retracts
LED displays (8, yellow) and (9, green)
yellow: Off; green: Illuminated; The actuator is linked to the LONWORKS® network and
ready for operation
yellow: Illuminated; green: Illuminated; No application software is loaded in the actuator
yellow: Blinking (flashing interval 2 s); green: Illuminated; The actuator is ready for
operation, but not linked to the LONWORKS® network (unconfigured)
yellow: Off; green: Blinking; POP functions active
yellow: Illuminated; green: Off; Pre-charging time SuperCap / Fault SuperCap / Wiring
error in supply
yellow: Off; green: Off; Not in operation
AVK24ALON
Globe valve actuator, communicative, modulating,
AC/DC 24 V, 2000 N
Indicators and operating elements
www.belimo.com
AVK24ALON
• en-gb • 2013-04-03 • Subject to modification
10
Connection with active sensor, e.g. 0 ... 10V @ 0 ... 50°C
5 6 7
3
2
1
MFT
LO
N
LO
N
T
~
+
–
T
~
+
–
Possible voltage range:
0 ... 32V (Resolution 30 mV)
Sensor scaling: The sensors can
be scaled with the sensor plug-in
(sensor table)
Electrical installation