background image

2

 

INSTALLATION INSTRUCTION 

 

 

Asia-Pacific 

+86 755 298 85888

 

Europe, Middle East 

+353 61 225 977

 

North America 

+1

 

408

 

785 5200

 

© 2020 Bel Power Solutions & Protection

 

BCM.00428_AC

 

 

AC INPUT 

100 

 277 V ~, 17 

 12.5 A, 50/60 Hz  

240 

 380 V , 13 

 9 A 

(Input selection is automatic; no manual change is required.) 

OUTPUTS 

V1 (12.3 V): see below table   

  

  

 

Vsb (12.0 V): 

MODEL 

INPUT VOLTAGE 

AMBIENT TEMPERATURE: 50°C 

AMBIENT TEMPERATURE:  60°C 

TET3000-12-069RA   

100-200 VAC  

81.3-244 A  

65 -195.2 A  

200-277 VAC, 240-380 VDC  

244 A  

195.2 A  

 

 

AMBIENT TEMPERATURE: 45°C

 

 

TET3200-12-069RA   

100-200 VAC  

92-260 A  

75-211 A  

200-277 VAC, 240-380 VDC  

260 A  

211 A  

 

 

CAUTION 

These component level power supplies are intended exclusively for installation within other equipment by an industrial assembly operation or by professional installers. 
This is a Class 1 power supply; the unit must be properly connected to earth ground in  end use. A component power supply should be installed in end-use equipment 
according to the requirements of the safety standard used for that equipment. This power supply is not designed to be operated outside of an enclosure which provides 
a means of mechanical, electrical, and fire protection. To maintain ES1 requirements, the outputs should not be connected together in any manner which causes the total 
output voltage to exceed 60 VDC. 

PROTECTIVE EARTHING 

The Power Supply must be properly grounded to mains protective earthing termination at end use. 

WARNING 

This is a class A product. In a domestic environment this product may cause radio interference, in which case the user may be required to take adequate measures. 

声明

 - 

此为

A

级产品,在生活环境中,

 

该产品可能会造成无线电干扰。

 

在这种情况下,可能需要用户对其干扰采取切实可行的措施。

 

 

ENVIRONMENTAL CONDITIONS 

TRANSPORTATION & STORAGE: 

Ambient Temperature Range: -40 °C to +70 °C 
Relative Humidity Range:        5% to 95% RH Non-Condensing 
Altitude:                                   0 to 13000 meters ASL 

 

OPERATION 

Ambient Temperature Range:  -40°C to +60°C (See output table for details)

 

Relative Humidity Range:         7% to 93% RH Non-Condensing 
Altitude:                                    0 to 2000 meters ASL at 0 °C to +50°C (TET3000-12-069RA)   
                                                 0 to 2000 meters ASL at 0 °C to +45°C (TET3200-12-069RA)  
                                                 0 to 5000 meters ASL at 0 °C to +40 °C  

SAFETY APPROVALS 

Approved to the latest version of the following safety standards: UL/CSA 62368-1, IEC/EN 62368-1 and IEC/EN 60950-1. 

FUSING 

CAUTION: DOUBLE POLE/NEUTRAL FUSING.

  

Fuses F300 and F301 are rated 25 A, 500 V/500 V (fast acting).  
Equipment is rated higher than 16 A. Type of connection to Mains must be determine in the end use equipment. 

SERVICING 

In case of failure, the Power Supply must be returned to a Bel Power Solutions Authorized Service Center. There are no user serviceable parts in the Power Supply. 

LIMITED WARRANTY 

Bel Power Solutions warrants each power supply of its manufacture for a period of two years from the date of original shipment. This warranty applies to defects in 
materials and workmanship that result in non-performance to published specifications. The product(s) must be returned to a Bel Power Solutions Authorized Service 
Center for repair with a Bel Power Solutions preassigned RMA number. 
Bel Power Solutions assumes no liabilities for consequential damages of any kind through the use or misuse of its products by any user. No other obligations are 
expressed or implied. 
Please note that the specifications, terms, and conditions stated are subject to change without notice. 

NUCLEAR AND MEDICAL APPLICATIONS 

Bel Power Solutions products are not designed, intended for use in, or authorized for use as critical components in life support systems, equipment used in hazardous 
environments, or nuclear control systems without the express written consent of the respective divisional president of Bel Power Solutions. 

TECHNICAL REVISIONS 

The appearance of  products, including safety agency  certifications pictured on labels, may change depending  on the date manufactured. Specifications are subject to 
change without notice. 

 

 

 

 

 

Summary of Contents for TET3000-12-069RA

Page 1: ...m Abkühlen des Gerätes bevor Sie es berühren Lassen Sie keine Flüssigkeiten oder Fremdkörper in die Geräte eindringen Um Überschläge zu vermeiden schließen Sie das Gerät nicht an oder trennen Sie es nicht ohne vorher die Eingangsspannung abgeschaltet zu haben und warten Sie die Entladung der internen Kondensatoren ab mindestens 2 Minuten RISCHIO USTIONI ESPLOSIONE INCENDIO SCOSSA LESIONI GRAVI Non...

Page 2: ...ION Ambient Temperature Range 40 C to 60 C See output table for details Relative Humidity Range 7 to 93 RH Non Condensing Altitude 0 to 2000 meters ASL at 0 C to 50 C TET3000 12 069RA 0 to 2000 meters ASL at 0 C to 45 C TET3200 12 069RA 0 to 5000 meters ASL at 0 C to 40 C SAFETY APPROVALS Approved to the latest version of the following safety standards UL CSA 62368 1 IEC EN 62368 1 and IEC EN 6095...

Page 3: ... 603 7 20 15 20 35 AIRFLOW DIRECTION LED INDICATORS OPERATING CONDITION LED SIGNALING AC LED AC Line within range Solid Green AC Line UV condition Off LED Normal Operation Solid Green PSON_L High Blinking Yellow 1 1 V1 or VSB out of regulation Solid Yellow Over temperature shutdown Output over voltage shutdown V1 or VSB Output under voltage shutdown V1 or VSB Output over current shutdown V1 or VSB...

Page 4: ...rotective Earth Pin Control Pins A1 PSKILL Power supply kill trailing pin active low B1 PWOK_L Power OK signal output active low C1 INOK_L Input OK signal active low D1 PSON_L Power supply on input active low A2 PRESENT_L Power supply present trailing pin active low B2 SGND Signal ground1 return C2 SGND Signal ground1 return D2 SGND Signal ground1 return A3 SCL I2C clock signal line B3 SDA I2C dat...

Reviews: