![BEL LDX-U20 User Manual Download Page 24](http://html.mh-extra.com/html/bel/ldx-u20/ldx-u20_user-manual_2725183024.webp)
belfuse.com/power-solutions
USER MANUAL
24
NAME
SHORT NAME
VALUE
ALARM_OUTPUT_OVERLOAD_START
OOLS
Threshold current triggering the alarm.
Description
The measured output current exceeds the alarm threshold. The alarm threshold is set to 22A.
NAME
SHORT NAME
VALUE
ALARM_OUTPUT_OVERLOAD_END
OOLE
The maximum output current reached during the
alarm.
Description
The measured output current returns below the alarm threshold.
NAME
SHORT NAME
VALUE
ALARM_BATTERY_UNDERVOLT_START
BUVS
Threshold voltage triggering the alarm.
Description
The measured battery voltage is lower than the alarm threshold. The threshold is 80% of the battery deep discharge voltage (§5.2.7).
NAME
SHORT NAME
VALUE
ALARM_BATTERY_UNDERVOLT_END
BUVE
The minimum battery voltage reached during the
alarm.
Description
The measured battery voltage returns above the alarm threshold.
NAME
SHORT NAME
VALUE
ALARM_BATTERY_LOW_START
BLOWS
Threshold voltage triggering the alarm.
Description
During discharge the measured battery voltage is lower than the battery low voltage threshold (§5.2.8).
NAME
SHORT NAME
VALUE
ALARM_BATTERY_LOW_END
BLOWE
The minimum battery voltage reached during the
alarm.
Description
The measured battery voltage returns above the battery low voltage threshold (§5.2.8).
NAME
SHORT NAME
VALUE
ALARM_BATTERY_OVERVOLT_START
BOVS
Threshold voltage triggering the alarm.
Description
The measured battery voltage exceeds the alarm threshold. The threshold is the battery charge voltage (§5.2.5) + 10%.
NAME
SHORT NAME
VALUE
ALARM_BATTERY_OVERVOLT_END
BOVE
The maximum battery voltage reached during
the alarm.
Description
The measured battery voltage returns below the alarm threshold.
NAME
SHORT NAME
VALUE
ALARM_BATTERY_OVERTEMP_START
BOTS
Threshold temperature triggering the alarm.
Description
The measured battery temperature exceeds the alarm threshold. The threshold is the battery maximum temperature (§5.2.11).
NAME
SHORT NAME
VALUE
ALARM_BATTERY_OVERTEMP_END
BOTE
The maximum battery temperature reached
during the alarm.
Description
The measured battery temperature returns below the alarm threshold.