Display Summary of function
'H - - L' High & low current output limits
Defines the lower ‘Lo’ and upper ‘Hi’
4/20mA Set Point Station output current
limits.
See section 5.6
'P5Et'
Pre-set outputs
The values of the five pre-set current
outputs are defined by this function. The
pre-set output currents are identified
‘5Et1’ to ‘5Et5’ and are displayed in
engineering units.
This function only appears in the
configuration menu when ‘P5Et’, which
allows pre-set values to be viewed and
selected in the operating mode, is
selected in the ‘P.Fn’ function.
See section 5.7
'rAtE'
Maximum output rate of change
Enables the maximum rate of change of
the 4/20mA output current to be defined.
Adjustable between approximately 1 and
100 seconds for full scale output travel.
0 disables this rate of change limit.
See section 5.8
'P.Fn'
Function of
P
push button in
operating mode.
The Set Point Station may be configured
to display the output current in milliamps,
the output current as a percentage or to
provide access to the five pre-set outputs
when the
P
push button is pressed in the
operating mode.
See section 5.9
'EnC'
Encoder
In addition to the Set Point Station
4/20mA output being adjusted by the
front panel push buttons, an external
quadrature encoder may be connected to
provide control via a rotary knob. This
function allows the number of pulses per
revolution of the knob to be entered.
See section 5.10
Display
Summary of function
'CodE'
Security code
Defines a four digit numeric code that
must be entered to gain access to the
configuration menu. Default code 0000
disables this security function and allows
unrestricted access to all conditioning
functions.
See section 5.11
'r5Et'
Reset
Returns the Set Point Station
configuration to the default condition. To
prevent accidental use, reset must be
confirmed by entering ‘5urE’ before it will
be executed.
See section 5.12