6.  MAINTENANCE

6.1 Fault finding during commissioning

If a BA627E Set Point Station fails to function during
commissioning   the   following   procedure   should   be
followed:

Symptom

Cause

Solution

No loop current

Incorrect wiring

Check wiring

There should be 
6.1 to 30V 
between terminals 
1 & 3 with terminal
1 positive.  
 
With an optional 
backlight which is 
loop powered, 
there should be 
10V to 30V 
between  terminals
3 & 12 with 
terminal 12 
positive.  

No loop current
0V between 
terminals 1 & 3 or 
between terminals 
3 & 12 if optional 
backlight is loop 
powered.

Incorrect wiring 
or no power 
supply

Check supply 
voltage and 
voltage drop 
caused by all the 
instruments in the 
loop.

Unstable 4/20mA 
loop current.

Noisy power 
supply or 
insufficient 
voltage to power
all the 
instruments in 
the loop. 

Eliminate ripple on
power supply or 
increase supply 
voltage.

Unable to enter 
configuration 
menu.

Incorrect 
security code 
entered.

Enter correct 
security code, or 
contact BEKA if 
the code has been
lost.

BA627E displays
‘LP Lo’

Voltage between
BA627E terminal
1 & 3 is too low, 

Increase 4/20mA 
loop supply 
voltage.

6.2  Fault finding after commissioning

ENSURE PLANT SAFETY BEFORE

STARTING MAINTENANCE

If a BA627E Set Point Station fails after it has been
functioning correctly follow the procedure shown in
section 6.1.  If this does not reveal the cause of the
fault, it is recommended that the Set Point Station is
replaced.

6.3  Servicing

We   recommend   that   faulty   BA627E   Set   Point
Stations are returned to BEKA associates or to our
local agent for repair.

6.4  Routine maintenence

The   mechanical   and   electrical   condition   of   the
instrument   should   be   regularly   checked.     Initially
annual   inspections   are   recommended,   but   the
inspection frequency should be adjusted to suit the
environmental conditions.

6.5  Guarantee

Set   Point   Stations   which   fail   within   the   guarantee
period   should   be   returned   to   BEKA   associates   or
our local agent.  It is helpful if a brief description of
the fault symptoms is provided.

6.6  Customer comments

BEKA   associates   is   always   pleased   to   receive
comments from customers about our products and
services.     All   communications   are   acknowledged
and   whenever   possible,   suggestions   are
implemented.

14

Summary of Contents for BA627E

Page 1: ...Issue 7 16th September 2015 BA627E General Purpose 2 wire 4 20mA manual set point station For instruments with firmware 1 03 and earlier Issued before June 2015 Issue 7 ...

Page 2: ... 5 7 Pre set outputs 5 8 Maximum output rate of change 5 9 Function of P push button in operating mode 5 10 Encoder 5 11 Security code 5 12 Reset to factory defaults 6 Maintenance 6 1 Fault finding during commissioning 6 2 Fault finding after commissioning 6 3 Servicing 6 4 Routine maintenance 6 5 Guarantee 6 6 Customer comments 7 Accessories 7 1 Scale card 7 2 Tag information 7 3 Display backligh...

Page 3: ... current changes slowly but after the button has been pressed for five seconds the rate of change accelerates to allow large changes to be made quickly The five pre set outputs which are selectable via the instruments front panel push butons allow the operator to quickly select frequently used plant set points To prevent plant disturbance the maximum rate of output current change initiated by oper...

Page 4: ...ng both buttons will leave the selected pre set value or Abort legend flashing for ten seconds during which time operating the E button will update the Set Point Station output to the displayed pre set value If the E button is not operated during this period the Set Point Station output will not be changed and the original engineering display will be shown While this button is pushed the Set Point...

Page 5: ...mum voltage drop 11 3V The power supply voltage must therefore be greater than 11 3V but less than 30V which is the maximum operating voltage of the BA627E Fig 2 Typical application 4 INSTALLATION 4 1 Location The BA627E Set Point Station has a robust glass reinforced Noryl enclosure with a toughened glass window The front of the instrument has IP66 protection and a gasket seals the joint between ...

Page 6: ... to the rear terminal block s as shown in Fig 3 To simplify installation the terminals are removable so that the panel wiring can be completed before the instrument is installed Fig 4 Fitting panel mounting clamps 4 4 Scale card The engineering units of measurement represent by the Set Point Station s 4 20mA output current may be shown on a printed scale card in a window at the right hand side of ...

Page 7: ...lf adhesive printed scale card onto the flexible strip and insert the strip into the Set Point Station as shown below Fig 5 Inserting flexible strip carrying scale card into slot at the rear of Set Point Station 7 ...

Page 8: ...default configuration Default Configuration Resolution rE5n 10 Display at 4mA output 2ero 0 00 Display at 20mA output 5PAn 100 00 Output current limits H L 03 000 22 000 Maximum output rate of change 000 P button in operating mode P Fn PC Pulses per rev of external encoder EnC 12 Security access code CodE 0000 Default configuration can easily be changed on site 5 1 Summary of configuration functio...

Page 9: ...n in operating mode The Set Point Station may be configured to display the output current in milliamps the output current as a percentage or to provide access to the five pre set outputs when the P push button is pressed in the operating mode See section 5 9 EnC Encoder In addition to the Set Point Station 4 20mA output being adjusted by the front panel push buttons an external quadrature encoder ...

Page 10: ...10 ...

Page 11: ...t Station display to be entered The bargraph is not displayed while using the CAL function Although calibration is normally performed at 4 000mA and 20 000mA other currents may be used providing they differ by more than 4mA To calibrate the Set Point Station display select CAL from the configuration menu and press P to enter the 2Ero sub menu used for calibrating the display at the lower of the tw...

Page 12: ...isplay the selected output current limit in milliamps with one digit flashing The flashing digit may be adjusted by pressing the or button when the flashing digit is correct pressing P will transfer control to the next digit When all the digits have been adjusted press E to return to the Lo or Hi prompt followed by E to enter the adjustments and return to the H L prompt in the configuration menu N...

Page 13: ...mounting encoder that generates 12 contact pulses per revolution and is intended for use with the BA627E Other encoders that produce a different number of contact pulses per revolution may also be used So that all external encoders have a similar adjustment resolution the EnC function enables the number of pulses between 6 and 48 per revolution to be defined To enter the number of pulses per revol...

Page 14: ...s LP Lo Voltage between BA627E terminal 1 3 is too low Increase 4 20mA loop supply voltage 6 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE If a BA627E Set Point Station fails after it has been functioning correctly follow the procedure shown in section 6 1 If this does not reveal the cause of the fault it is recommended that the Set Point Station is replaced 6...

Page 15: ... be loop or separately powered When loop powered the backlight produces background illumination enabling the display to be read at night or in poor lighting conditions No additional power supply or field wiring are required but the Set Point Station s minimum operating voltage is increased When separately powered the backlight is brighter but additional field wiring and a power supply are required...

Page 16: ... Point Station s output current can still be controlled by the and buttons when an external encoder is connected 7 4 1 BEKA BA490 rotary encoder The BEKA BA490 quadrature output rotary encoder has been designed to operate with the BA627E Set Point Station It is an IP66 panel mounting device with a 20mm diameter control The two output waveforms and connections are shown in Fig 10 Fig 10 BA490 rotar...

Reviews: