BEKA BA627E Instruction Manual Download Page 13

5.8  Maximum output rate of change:  ‘rAtE’

To minimise  plant disturbance  when  the Set  Point

Station output current is adjusted, the maximum rate
of change is defined by this function.  The maximum
rate is adjustable between approximately 1 and 100
seconds for full scale output travel from 4 to 20mA.
If 0 seconds is selected the function is disabled.

To define the maximum rate of change of the Set

Point   Station   output   select   'rAtE'   from   the
configuration menu and press

 

which will reveal the

present   maximum   rate   of   change   in   seconds   with
one   digit   flashing.     The   flashing   digit   may   be
adjusted by pressing the ▲ or ▼ buttons, when the
flashing   digit   is   correct   pressing  

P

 

will   transfer

control to the next digit.   When all the digits have
been adjusted, press  

E

  to enter the new value and

return to the configuration menu.

When   the   output   rate   of   change   limitation   is

functioning,   in   the   operating   mode   the   Set   Point
Station digital display will show the requested output
and will  flash until the requested  output current  is
achieved.   The bargraph display always shows the
Set Point Station’s actual output.

Pressing the 

E

 button while the output is ramping to

a new requested value will stop the output changing.

5.9   Function of the  

P

  push-button in operating

mode:   ‘P.Fn’

Using   this   function   the   Set   Point   Station   may   be

configured to display the output current in milliamps,
the   output   current   as   a   percentage   of   the   output
range,   or   to   provide   access   to   the   five   pre-set
outputs   when   the  

P

  button   is   pressed   in   the

operating mode.

To   check   or   change   the   function   of   the  

P

  push

button select 'P.Fn' from the configuration menu and
press  

P

 to reveal the present setting.   Pressing the

▲ or ▼ button will scroll the setting between:

'PC' 

Output as a percentage of output 
range.

'4-20' 

Output current in milliamps

‘P5Et’

Access to the five pre-set outputs
see 6.7

When set as required, press 

E

 to return to the ‘P.Fn’

prompt in the configuration menu.

5.10  Encoder:   ‘EnC’

For   applications   requiring   the   Set   Point   Station’s
4/20mA output current to be controlled by a rotary
knob,   an   external   three   wire   quadrature   encoder
may be directly connected to terminals 5, 6 and 7.

The BEKA BA490 Is a panel mounting encoder that
generates  12   contact   pulses  per  revolution   and   is
intended for use with the BA627E.  Other encoders
that   produce   a   different   number   of   contact   pulses
per revolution may also be used.  So that all external
encoders have a similar adjustment resolution, the
‘EnC’   function   enables   the   number   of   pulses
between 6 and 48 per revolution to be defined.

To enter the number of pulses per revolution that the
external   encoder   generates,   select   'EnC'   from   the
configuration menu and press

 

which will reveal the

existing setting with one digit flashing.  The flashing
digit   may   be   adjusted   by   pressing   the   ▲   or   ▼
button, when the flashing digit is correct pressing 

P

will   transfer control to the  other digit.     When both
digits have been adjusted press  

E

  t

o return to the

‘EnC’ prompt in the configuration menu.

Section 7.4 contains information about the use of an
external rotary encoder.

5.11  Security code:  ‘CodE’

Access to the instrument configuration menu may be
protected by a four digit security code which must be
entered   to   gain   access.       New   instruments   are
configured with the default security code 0000 which
allows   unrestricted   access   to   all   configuration
functions.

To enter a new security code select 'CodE' from the
configuration menu and press

 

P

 which will cause the

Set   Point   Station   to   display   the   existing   security
code with one digit flashing.   The flashing digit can
be adjusted using the ▲ and

 ▼

 push buttons, when

set as required operating the  

P

  button will transfer

control to the next digit.     When all the digits have
been   adjusted   press

 

E

  to   return   to   the   ‘CodE’

prompt. The revised security code will be activated
when   the   Set   Point   Station   is   returned   to   the
operating mode.   Please contact BEKA associates
sales department if the security code is lost.

5.12  Reset to factory defaults:  ‘rSEt’

This   function   quickly   returns   to   the   BA627E   Set
Point   Station   to   the   factory   default   configurations
shown in   section 5.

To reset the Set Point Station select ‘rSEt’ from the
configuration   menu   and   press  

P.

    To   prevent

accidental resetting the request must be confirmed
by entering ‘5urE’.   Using the ▲ button set the first
flashing digit to ‘5’ and press 

P

 to transfer control to

the second digit, which should be set to ‘u’.   When
‘5urE’ has been entered pressing the  

E

  button will

reset the configuration menus and return the display
to the ‘rSEt’ function in the configuration menu.

13

Summary of Contents for BA627E

Page 1: ...Issue 7 16th September 2015 BA627E General Purpose 2 wire 4 20mA manual set point station For instruments with firmware 1 03 and earlier Issued before June 2015 Issue 7 ...

Page 2: ... 5 7 Pre set outputs 5 8 Maximum output rate of change 5 9 Function of P push button in operating mode 5 10 Encoder 5 11 Security code 5 12 Reset to factory defaults 6 Maintenance 6 1 Fault finding during commissioning 6 2 Fault finding after commissioning 6 3 Servicing 6 4 Routine maintenance 6 5 Guarantee 6 6 Customer comments 7 Accessories 7 1 Scale card 7 2 Tag information 7 3 Display backligh...

Page 3: ... current changes slowly but after the button has been pressed for five seconds the rate of change accelerates to allow large changes to be made quickly The five pre set outputs which are selectable via the instruments front panel push butons allow the operator to quickly select frequently used plant set points To prevent plant disturbance the maximum rate of output current change initiated by oper...

Page 4: ...ng both buttons will leave the selected pre set value or Abort legend flashing for ten seconds during which time operating the E button will update the Set Point Station output to the displayed pre set value If the E button is not operated during this period the Set Point Station output will not be changed and the original engineering display will be shown While this button is pushed the Set Point...

Page 5: ...mum voltage drop 11 3V The power supply voltage must therefore be greater than 11 3V but less than 30V which is the maximum operating voltage of the BA627E Fig 2 Typical application 4 INSTALLATION 4 1 Location The BA627E Set Point Station has a robust glass reinforced Noryl enclosure with a toughened glass window The front of the instrument has IP66 protection and a gasket seals the joint between ...

Page 6: ... to the rear terminal block s as shown in Fig 3 To simplify installation the terminals are removable so that the panel wiring can be completed before the instrument is installed Fig 4 Fitting panel mounting clamps 4 4 Scale card The engineering units of measurement represent by the Set Point Station s 4 20mA output current may be shown on a printed scale card in a window at the right hand side of ...

Page 7: ...lf adhesive printed scale card onto the flexible strip and insert the strip into the Set Point Station as shown below Fig 5 Inserting flexible strip carrying scale card into slot at the rear of Set Point Station 7 ...

Page 8: ...default configuration Default Configuration Resolution rE5n 10 Display at 4mA output 2ero 0 00 Display at 20mA output 5PAn 100 00 Output current limits H L 03 000 22 000 Maximum output rate of change 000 P button in operating mode P Fn PC Pulses per rev of external encoder EnC 12 Security access code CodE 0000 Default configuration can easily be changed on site 5 1 Summary of configuration functio...

Page 9: ...n in operating mode The Set Point Station may be configured to display the output current in milliamps the output current as a percentage or to provide access to the five pre set outputs when the P push button is pressed in the operating mode See section 5 9 EnC Encoder In addition to the Set Point Station 4 20mA output being adjusted by the front panel push buttons an external quadrature encoder ...

Page 10: ...10 ...

Page 11: ...t Station display to be entered The bargraph is not displayed while using the CAL function Although calibration is normally performed at 4 000mA and 20 000mA other currents may be used providing they differ by more than 4mA To calibrate the Set Point Station display select CAL from the configuration menu and press P to enter the 2Ero sub menu used for calibrating the display at the lower of the tw...

Page 12: ...isplay the selected output current limit in milliamps with one digit flashing The flashing digit may be adjusted by pressing the or button when the flashing digit is correct pressing P will transfer control to the next digit When all the digits have been adjusted press E to return to the Lo or Hi prompt followed by E to enter the adjustments and return to the H L prompt in the configuration menu N...

Page 13: ...mounting encoder that generates 12 contact pulses per revolution and is intended for use with the BA627E Other encoders that produce a different number of contact pulses per revolution may also be used So that all external encoders have a similar adjustment resolution the EnC function enables the number of pulses between 6 and 48 per revolution to be defined To enter the number of pulses per revol...

Page 14: ...s LP Lo Voltage between BA627E terminal 1 3 is too low Increase 4 20mA loop supply voltage 6 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE If a BA627E Set Point Station fails after it has been functioning correctly follow the procedure shown in section 6 1 If this does not reveal the cause of the fault it is recommended that the Set Point Station is replaced 6...

Page 15: ... be loop or separately powered When loop powered the backlight produces background illumination enabling the display to be read at night or in poor lighting conditions No additional power supply or field wiring are required but the Set Point Station s minimum operating voltage is increased When separately powered the backlight is brighter but additional field wiring and a power supply are required...

Page 16: ... Point Station s output current can still be controlled by the and buttons when an external encoder is connected 7 4 1 BEKA BA490 rotary encoder The BEKA BA490 quadrature output rotary encoder has been designed to operate with the BA627E Set Point Station It is an IP66 panel mounting device with a 20mm diameter control The two output waveforms and connections are shown in Fig 10 Fig 10 BA490 rotar...

Reviews: