Step 6

Enter the rate timebase

Select ‘t-bASE’ from the main menu
and press 

P

 to show the current

setting.  In this example the rate
display is required in litres per hour.
Using the 

Up

 or 

Down

 button scroll

through the three options and select
‘tb-3600’ which will multiply the rate
display by 3600. Return to the ‘t-bASE’
prompt in the main menu by pressing

E

.

Step 7

Adjust the rate filter

The rate display filter parameters
should be adjusted experimentally after
installation to provide a stable rate
display with an acceptable step
response.

During commissioning it is recommend
that initially the second digit of the rate
parameters is set to 0 (step response
off) and the first digit (amount of
filtering) is adjusted to provide
acceptable rate display stability. The
second digit should them be increased
until acceptable rate display stability is
once again achieved.

To adjust the filter parameters select
‘FILtEr’ from the main menu and press

P

 to reveal the current setting.  The

first digit will be flashing and may be
adjusted using the 

Up

 or 

Down 

button.

The 

P

 button will transfer control to the

second digit.  When both are set as
required, return to the ‘FILtEr’ prompt
in the main menu by pressing 

E

.

Step 8    Enter the total scaling factor

The K factor of the flowmeter in this
example is 1050.0 pulses per litre and
the total display is required in cubic
metres.

There are 1000 litres in a cubic metre
so the BA538C is required to display 1
cubic metre for every 1,050 x 1,000
pulses received.  ‘SCALE-t’ should
therefore be set to 1,050,000

Select ‘SCALE-t’ from the main menu
and press 

P

 which will reveal the

current setting with one digit flashing.
To position the decimal point, operate
the 

P

 push-button to move the flashing

digit to the least significant position.
Pressing the 

Up

 and 

Down

 buttons

simultaneously will then remove the
decimal point.

Using the 

Up

 and 

Down

 buttons to

adjust each digit in turn and the 

P

button to transfer control between
digits, enter 1050000    Finally return to
the 'SCALE-t' prompt in the main menu
by pressing 

E

.

Step 9

Define clip-off

In this example totalisation is to be
inhibited at flow rates below 300 litres
per hour.

Select ‘CLIP-OFF’ from the main menu
and press 

P

 which will reveal the clip-

off threshold in litres per hour i.e. the
same units already selected for the
rate display.  The most significant digit
of the display will be flashing,
indicating that this digit may be
adjusted.    Pressing 

five times will

move the flashing digit to the third
lease significant digit.

Using the 

Up

 and 

Down

 buttons set

the third least significant digit to 3  i.e.
a clip-off threshold of 300.     Finally
return to the 'CLIP-OFF' prompt in the
main menu by pressing 

E

.

Step 10 Turn local reset on

In this example the operator needs to
reset the total display to zero by
pressing the 

Up

 and 

Down

 buttons

simultaneously.  To activate the local
reset function select ‘LOC.rSEt’ from
the main menu and press 

P

 to display

the current setting.  Pressing the 

Up

 or

Down

 button will toggle the display

between ‘On’ and ‘OFF’.  Select ‘On’
and press 

E

 to return to the ‘LOCrSEt’

prompt in the main menu.

Summary of Contents for BA538C

Page 1: ...ssue 12 25th March 2014 Label information Rate display Annunciators for optional alarms Rotating flow indicator Total display BA538C Externally powered pulse input panel mounting rate totaliser issue 12 ...

Page 2: ...otal 5 15 Security code 6 Calibration Example 6 1 Calibration procedure 7 Maintenance 7 1 Fault finding during commissioning 7 2 Fault finding after commissioning 7 3 Servicing 7 4 Routine maintenance 7 5 Guarantee 7 6 Customer comments 8 Accessories 8 1 Scale card 8 2 Tag number 8 3 Alarms 8 3 1 Solid state output 8 3 2 Programming and adjustment 8 3 3 Alarm enable 8 3 4 Type of alarm 8 3 5 Setpo...

Page 3: ...unction on the rate or total displays further extend the instrument s applications Fig 1 Simplified block diagram of BA538C 2 1 Initialisation Each time power is applied to the instrument initialisation is performed After a short delay the following display sequence occurs All segments of the display are activated for about 2 seconds The product firmware number and the version number are displayed...

Page 4: ...et Activated when the instrument Annunciator is being reset 3 SYSTEM DESIGN 3 1 Flow transmitter loops The BA538C may be connected to almost any pulse output flowmeter and calibrated to display rate of flow and total flow in the same or different engineering units Fig 2 illustrates the basic circuit that is used for all BA538C installations For simplicity connections for the optional pulse output ...

Page 5: ...y be used as an inhibit function There is no practical limit on the distance that the reset switch may be from the totaliser Alternatively the BA538C may be programmed so that the total display is reset to zero when the Up and Down push buttons are operated simultaneously for more than two seconds see 5 12 4 INSTALLATION 4 1 Location The BA538C is housed in a robust aluminium enclosure with a poly...

Page 6: ...closure and the panel c Connect the panel wiring to the rear terminal block s as shown in Fig 4 To simplify installation the terminals are removable so that panel wiring can be completed before the instrument is installed Fig 4 Installation and terminal connections 4 3 EMC The BA538C complies with the requirements of the European EMC Directive 2004 108 EEC For specified immunity all wiring should ...

Page 7: ...l decimal points Moving the position of a decimal point in a scale factor will therefore affect the instrument calibration The BA538C updates its total flow calculation twice per second If the instrument is used for batching applications this resolution may define the accuracy of the system Note The total and rate displays may be updated less frequently depending upon the display update time selec...

Page 8: ...8 ...

Page 9: ...LAY 2 Lower display Turns the lower display which normally shows rate on or off See section 5 7 Display Description of function SCALE r Rate Scale Factor Defines the arithmetic relationship between the pulse input frequency and the rate display May be adjusted between 0 001 and 99999999 When used with a flowmeter SCALE r should be set to the flowmeter K factor pulses per unit of measurement if the...

Page 10: ... current input type Pressing Up or Down will scroll through the five options UOLts Voltage pulse input Threshold 1V and 3V 5kHz max Input terminals 3 and 4 COIL Low voltage pulse Threshold 20mV peak 5kHz max Input terminals 3 and 4 Pr dEt NAMUR proximity detector Threshold 1 2 and 2 1mA 5kHz max Input terminals 5 and 6 COntACt Switch contact Threshold 100 and 1000 100Hz max Input terminals 5 and 6...

Page 11: ...te display by 1 60 or 3 600 depending upon whether the BA538C is required to display rate per second per minute or per hour See Fig 5 To check or change the timebase select t bASE from the main menu and press P which will reveal the current setting Pressing the Up or Down button will index through the three options tb 1 for flow second tb 60 for flow minute tb 3600 for flow hour Select the require...

Page 12: ... rates that over long periods may result in significant totalisation errors the BA538C may be programmed to stop totalising when the flow rate falls below an adjustable threshold To check or change the clip off threshold select CLIP OFF from the main menu and press P which will reveal the current setting The threshold is shown in the units already selected for the flow rate display One digit will ...

Page 13: ...re access to the programme menu is granted New instruments are programmed with the default security code 0000 which allows unrestricted access to all programming functions without entering a security code To enter a new security code select COdE from the menu and press P which will cause the instrument to display the current security code Each digit of the code can be changed using the Up and Down...

Page 14: ...p or Down button scroll through the main menu until InPut is displayed then press P to reveal the existing setting Select COIL the input for a magnetic pick off using the Up or Down button and return to the InPut prompt in the main menu by pressing E Note The BA538C has two pairs of input terminals 3 4 for voltage inputs and 5 6 for switch contact proximity detector or open collector inputs Ensure...

Page 15: ... metre for every 1 050 x 1 000 pulses received SCALE t should therefore be set to 1 050 000 Select SCALE t from the main menu and press P which will reveal the current setting with one digit flashing To position the decimal point operate the P push button to move the flashing digit to the least significant position Pressing the Up and Down buttons simultaneously will then remove the decimal point ...

Page 16: ...strument to the CLr Gtot prompt in the main menu Step 12 Define the security code Defining a security code prevents unauthorised access to the programme functions Select COdE from the main menu and press P which will reveal the existing security code Using the Up and Down buttons enter the new code 1209 digit by digit The P button will transfer control between digits When the new code has been ent...

Page 17: ...ation Alarms do not function Alarms have been disabled following calibration change Re enable both alarms 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE If a BA538C fails after it has been functioning correctly the following table may help to identify the cause of the failure Symptom Cause Check No display No power supply That there is between 10 and 30Von te...

Page 18: ...ons such as a shut down system When the BA538C power supply is turned off or disconnected both BA538C alarm outputs will open irrespective of whether normally open or normally closed outputs have been selected When designing a system an open output should therefore be the alarm condition Alarm annunciators on the instrument display indicate the status of both alarms If an alarm delay or silence ti...

Page 19: ...rm operates on the rate or total display See section 8 3 4 SPr1 Alarm setpoint 1 or Adjusts the alarm setpoint The SPt1 alarm is activated when the rate or total display equals the setpoint Note SPr1 is displayed for a rate alarm and SPt1 for a total alarm See section 8 3 5 HI LO Alarm function Defines whether the alarm has a high or low function See section 8 3 6 no nc Normally open or normally c...

Page 20: ...ed or the alarm type has been changed Both alarms must therefore be enabled after calibration changes 8 3 4 Type of alarm tYPE Alarm 1 and Alarm 2 may both be rate or total alarms or one may be conditioned for rate and the other for total To check or change the type of alarm select tYPE from the alarm menu and press P which will reveal the current setting The function can be changed by pressing th...

Page 21: ...eresis select HStr from the alarm menu and press P which will reveal the existing figure Each digit can be adjusted using the Up and Down push buttons and the P button to move to the next digit When the required hysteresis has been entered press E to return to the alarm menu e g A BA538C calibrated to display a flow of 0 to 5000 with a high alarm set at 4000 and hysteresis of 100 will perform as f...

Page 22: ...to the setpoints in the display mode by pressing the P and Up buttons simultaneously New instruments with alarms are supplied with the security code set to 0000 8 3 12 Adjusting alarm setpoints from the display mode Access to the two alarm setpoints from the instrument display mode is obtained by operating the P and Up push buttons simultaneously as shown in Fig 11 If the setpoints are not protect...

Page 23: ...g 12 Display backlight 8 5 Pulse output The BA538C may be supplied with an opto isolated solid state pulse output The output is a polarised current sink that closes for a programmable duration each time the least significant digit of the BA538C display changes A programmable divider enables the pulse output frequency to be divided by 10 100 1 000 or 10 000 See Fig 13 The output pulse is not synchr...

Page 24: ...isplay corresponding to an output current of 4 000mA Pressing P will reveal the existing setting with the most significant digit flashing The decimal point will be fixed in the position already defined for the rate display by the d P function The value of the flashing digit may be changed by pressing the Up or Down buttons When this digit is set as required pressing P will transfer control to the ...

Page 25: ...output are powered from separate supplies the 4 20mA output current will continue to flow when the BA538C supply fails or is turned off Powering both from a common supply as shown in Fig 15 eliminates this effect Fig 16 4 20mA output programme structure ...

Page 26: ...5 4 dISPLAY 2 5 7 d P 5 6 EnbL 8 3 2 8 3 3 Fault finding during commissioning 7 1 after commissioning 7 2 FILtEr 5 10 Flow indicator 2 3 Grand total 2 3 clear 5 14 Guarantee 7 5 HI LO 8 3 2 8 3 6 HStr 8 3 2 8 3 8 InPut 5 5 Installation 4 2 Subject Section LOC rSEt 5 13 Local reset 5 13 Location 4 1 Maintenance 7 0 routine 7 4 no nc 8 3 2 8 3 7 Output Pulse 8 5 4 20mA 8 6 Push buttons Down 2 2 E 2 ...

Reviews: