BEKA BA537E Manual Download Page 24

If removing a segment from a configured lineariser,
the segment to be deleted, which is shown on the left
hand side of the display, can be selected using the

&

or

*

push button.

When a segment is deleted,

the identification numbers of all segments above the
deleted segment are decreased by one.

Press

)

to return to the

dEL

prompt in the lineariser

sub-menu.

6.5   Input frequency:  

PuL5E Fr

PuL5E Fr

is a sub-menu in the

FACtor

function for

entering the pulse input frequency at which each of
the lineariser segments starts, see Fig 8.

To enter the input pulse frequency at which one or
more lineariser segments start, select

FACtor

in the

configuration menu and press

(

which will reveal

one of four sub-functions. If

PuL5E Fr

is not displayed

repeatedly press the

&

or

*

button to select

PuL5E Fr

followed by

(

to display the current

segment for which the start frequency will be entered
and the total number of segments that have already
been defined using the

Add

and

dEL

functions, see

below.

The required segment, which is shown on the left
hand side of the display, can be selected using the

&

or

*

push button.

When selected press

(

which

will reveal the current input frequency with one digit
flashing.

The value of the flashing digit may be

changed by pressing the

&

or

*

button. When this

digit is correct pressing

(

will transfer control to the

next digit.

When the input frequency for this

lineariser segment is set as required, press the

)

button to return to the segment identification display
from which the next segment may be selected using

&

 or 

*

 push button.   

When the input frequency for all of the segments has
been entered, return to the

FACtor

prompt in the

configuration menu by operating the

 )

 

push button.

6.6   Flowmeter K-factor  

L-Factor

L-FACtor

is a sub-menu in the

FACtor

function for

entering the flowmeter K-factor for each of the
lineariser segments, see Fig 9.  

The rate totaliser pulse input is divided by

L-FACtor

,

which is adjustable between 0.0001 and 99999; for
flow applications it should be set to the K-factor of the
flowmeter. K-factor is the number of pulses that the

flowmeter produces per unit volume of flow e.g. 20
pulses per litre,

L-FACtor

therefore converts the

flowmeter output into engineering units ready for
further scaling to produce the required rate and total
flow displays.

To enter the flowmeter K-factor for one or more
segments, select

FACtor

in the configuration menu

and press

(

, which will reveal one of four sub-

functions.

If

L-FACtor

is not displayed in the sub-

menu repeatedly press the

&

or

*

button to select

L-FACtor

followed by

(

to display the current

segment for which

L-FACtor

will be entered and the

total number of segments that have already been
defined using the 

Add

 and 

dEL

 functions.

The required segment, which is shown on the left
hand side of the display, can be selected using the

&

 or 

*

 push button, see below.

When selected, press

(

which will reveal the

current

L-FACtor

for the selected segment with one

digit flashing. The value of the flashing digit may be
changed by pressing the

&

or

*

button. When

this digit has been adjusted as required, pressing

(

will transfer control to the next digit. When all

the digits have been adjusted pressing

(

will

transfer control to the decimal point that may be
positioned between any of the digits, or may be
omitted by moving it to the right of the least
significant digit.  

When

L-FACtor

for this lineariser segment is set as

required, press the

)

button to return to the

segment identification display from which the next
segment may be selected using

&

or

*

push

button. When

L-FACtor

for all of the segments has

been entered, return to the

FACtor

prompt in the

configuration menu by operating the

)

push button

twice.

6.7  Lineariser error message

If an attempt is made to position a segment at an
input frequency which is not greater than the
frequency of the preceding segment, or at an input
frequency which is not less than the frequency of the
following segment, the error message

value.err

will

be displayed.

24

Summary of Contents for BA537E

Page 1: ...Issue 5 9th July 2019 BA537E and BA538E One input General Purpose pulse input Rate Totalisers Issue 5...

Page 2: ...s 6 3 Add a segment add 6 4 Remove a segment del 6 5 Input frequency pul5efre 6 6 K factors l factor 6 7 Lineariser error messages 7 Configuration example 7 1 Configuration procedure 8 Maintenance 8 1...

Page 3: ...E and BA538E have a single pair of input terminals for connection to all types of transducer When counting pulses from a transducer requiring energising such as a switch contact open collector or a tw...

Page 4: ...ts when the Rate Totaliser is fitted with optional alarms and the AC5P setpoints function has been enabled See 9 4 13 Access to configuration menu 2 3 Displays The BA537E and BA538E have two digital d...

Page 5: ...eshold Input transducer Switching thresholds Lower Upper Open collector 2k 10k Voltage pulse low 1 0V 3 0V Voltage pulse high 3 0V 10 0V Magnetic pick off 0mV 40mV peak Proximity detector 1 2mA 2 1mA...

Page 6: ...configuration menu VoLt5 L and VoLt5 H as shown in section 3 2 The Rate Totalisers contain a configurable debounce circuit to prevent false triggering of the instrument Three levels of de bounce prote...

Page 7: ...o prevent vibration damage Note Optional backlight is internally powered Fig 3A BA537E dimensions terminals Cut out dimensions Recommended for all installations Mandatory to achieve an IP66 seal betwe...

Page 8: ...ing is supported Fig 4 Fitting panel mounting clamps 4 4 Scale card The Rate Totaliser s units of measurement are shown on a printed scale card in a window at the right hand side of the display The sc...

Page 9: ...configured totalisation continues so that any flow occurring during this time is recorded 5 1 Configuration structure Fig 6 shows the BA537E and BA538E calibration structure The rate and total displa...

Page 10: ...figuration menu is shown diagrammatically in Fig 7 When returning to the totalisation mode following reconfiguration the Rate Totaliser will display dAtA followed by 5AVE while the new information is...

Page 11: ...of litres in 1 000 imperial gallons 5CALE t may be adjusted between 0 0001 and 99999 The total flow display is independent of the rate display See section 5 13 Display Summary of function 5CALE r Rat...

Page 12: ...tored See section 5 20 Display Summary of function CLr Gtot Reset grand total from configuration menu This function resets the grand total to zero from within the configuration menu when CLr YE5 is se...

Page 13: ...dEbounCE which configure the Rate Totaliser input and input noise rejection 5 6 Input type inP tYPE inP tYPE is a sub menu in the inPut function which defines the type of flowmeter or input pulse that...

Page 14: ...14...

Page 15: ...15...

Page 16: ...on will scroll through the three levels When the required level has been selected pressing twice will enter the selection and return the display to the inPut prompt in the configuration menu 5 8 Displ...

Page 17: ...control to the decimal point that may be positioned between any of the digits or may be omitted by moving it to the right of the least significant digit When set as required press to return to the FAC...

Page 18: ...play stability and a fast response to a large rate signal change To check or change the filter select FiLtEr in the configuration menu and press which will reveal the existing settings with the first...

Page 19: ...ge the setting followed by the button twice to enter the change and return to the LoC clr prompt in the configuration menu 5 21 Grand total reset from configuration menu Clr Gtot The grand total is a...

Page 20: ...from the configuration menu and press which will result in a 0000 display with the first digit flashing This is a request to confirm the reset to factory default instruction by entering 5urE Using th...

Page 21: ...ibration certificate specifying the average K factor and the flow range over which it applies For use over extended flow ranges and for non linear devices multiple K factors will be specified often in...

Page 22: ...22...

Page 23: ...of four sub functions If Add is not displayed repeatedly press the or button to select Add followed by which will cause the current segment and the total number of lineariser segments to be displayed...

Page 24: ...s divided by L FACtor which is adjustable between 0 0001 and 99999 for flow applications it should be set to the K factor of the flowmeter K factor is the number of pulses that the flowmeter produces...

Page 25: ...ction If the Rate Totaliser is subsequently found to miscount the noise rejection can be increased Enter the selection and return to the inPut prompt in the configuration menu by pressing the button t...

Page 26: ...o be displayed in the required engineering units The rate display timebase is determined by t bA5E that is adjusted in Step 11 In this example the rate of flow display is required in imperial gallons...

Page 27: ...eveal the sub menu Again using the or button select the local total reset function clr tot and press This function is required so using the or button select on followed by to return to the clr tot pro...

Page 28: ...Alarms have been disabled following calibration change Re enable both alarms 8 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE If a BA537E or a BA538E fails after i...

Page 29: ...ory fitted backlight that produce green illumination enhancing display contrast and enabling it to be read at night or in poor lighting conditions Both the BA537E and BA538E backlights are internally...

Page 30: ...hat total alarms do not have hysteresis Alarm AL2 is identical to alarm AL1 The following table summarises each of the alarm configuration functions and includes a cross reference to more detailed inf...

Page 31: ...push button will toggle the selection between rAtE and totAL when set as required press the button to return to the alarm sub menu Note When tYPE is changed the alarm configuration is automatically re...

Page 32: ...32...

Page 33: ...ss to enter the value and return to the dELA prompt in the alarm sub menu The Rate Totaliser s alarm annunciator will start flashing immediately an alarm condition occurs and will continue for the del...

Page 34: ...ained by operating the and push buttons simultaneously as shown in Fig 16 If the setpoints are not protected by a security code the alarm setpoint prompt 5P1r or 5P1t will be displayed depending upon...

Page 35: ...tor closes P2 is connected to P1 and a pulse output current flows through the resistor R1 The current flowing in the circuit is determined by resistor R1 which should be chosen to limit the output cur...

Page 36: ...the output pulse 1 10 100 1000 10000 Using the or push button select diVidE in the pulse output sub menu and press which will reveal the existing divisor The selected divisor can be changed by pressin...

Page 37: ...ut to be controlled by the rate or the total display and to be scaled Fig 17 4 20mA output configuration sub menu 9 6 3 4 20mA output 4 20 oP Access the Rate Totaliser s configuration menu as describe...

Page 38: ...t 20 000 in the 4 20mA output sub menu and press which will reveal the existing rate or total display with one digit flashing The required display can be entered using the or push button to adjust the...