7. CALIBRATION EXAMPLE
In this example a BA458C batch controller is
required to control the dispensing of a liquid
into a tank as shown in Fig. 17. It is a stand-
alone system so galvanic isolators have been
used for the interface between the safe and
hazardous area. The batch controller is
powered by an isolator with a 28V, 93mA
output safety description. Two more identical
devices are used to power the intrinsically safe
solenoid valves that are controlled by Control 1
and Output 2. Output 3, which is configured
as a flow alarm, is connected to a switch
transfer isolator which produces a switch
contact closure in the safe area.
The BA358C batch controller is required to:
Dispense 1,000 or 500 litres of product into
a tank having a maximum capacity of
1,100 litres. Two volumes to be identified
Full volume and Half volume respectively.
The flowmeter incorporates a proximity
detector and produces an output of 25
pulses per litre.
Display the dispensed total with a
resolution of 0.1 litres.
Batch Controller to count upwards from
zero to the batch setpoint.
Control two parallel valves (2 stage
control).
At start of the batch valve 2 is to open 10
seconds after valve 1 and to close when
50 litres of product remain to be
dispensed.
Compensate for errors resulting from
actuator delays.
Initiate an alarm if the flow rate falls below
0.2 litres per second. Alarm to be
inhibited for the first 20 seconds of the
batch.
Operator needs to select the batch size
from the operator menu, but must not be
able to adjust the two setpoints. The
operator requires access to the history of
the last ten batches but must not have
access to the configuration menu.
The process is to be controlled by the
batch controller’s front panel switches. The
Reset function is not required.
The Operator Menu is not to be protected by a
security code, but the Configuration Menus are
to be protected by code 1209.
Fig 17 Liquid dispensing system
System Settings
Function Setting
Language
English
User Controls
Local
Signal Input
Prox Detector
Lineariser
Off
Restart
Quick
Output 2
Control 2
Output 3
Flow Alarm
Clear Grand Total
Yes
Security
Config Code
1209
Operator Code
0000
Operator Menu Batch Sizing
Off
Batch Select
On
History
On
Config Menu
Off
Operator Screens
Screen 1
Summary of Contents for BA458C
Page 1: ...Issue 5 1st December 2010 BA458C Intrinsically safe Panel mounting Batch Controller Issue 5 ...
Page 16: ...16 Fig 11 System Settings ...
Page 21: ...21 BLANK PAGE ...
Page 22: ...22 Fig 14 Batch Settings ...
Page 27: ...27 BLANK PAGE ...
Page 28: ...28 Fig 16 Rate Settings ...
Page 35: ...35 ...
Page 36: ...36 ...
Page 37: ...37 APPENDIX 2 Information menu ...
Page 39: ...39 ...
Page 40: ...40 ...
Page 41: ...41 ...
Page 42: ...42 ...
Page 43: ...43 ...
Page 44: ...44 ...
Page 45: ...45 ...