18
6.4.7 Restart
This function determines what happens at the
end of each batch. There are three options:
Normal:
The display screen shows the
volume that has been
dispensed. Before another
batch can be started the Reset
push-button must be operated.
The screen will then display
‘Ready’.
Quick:
The display screen shows the
volume that has been
dispensed. Operating the Start
pushbutton will reset the batch
controller and start another
batch.
Auto restart: The display screen shows the
volume that has been
dispensed. After a configurable
restart delay (See 6.5.19) the
batch controller automatically
resets and starts another batch.
The number of batch cycles to
be performed is defined by the
Batch Cycle function, which is
contained in the Batch Setting
menu. See 6.5.18
Normal
Quick
Auto
Set Batch Restart
Highlight the required option and press E to
enter the selection.
6.4.8 Output 2
Output 2 is an isolated single pole solid state
switch contact that is connected to terminals
A3 and A4. It may be configured to output any
one of six different signals, or may be unused.
Unused
Control 2
Control 3
Flow alarm
Reset status
Batch status
Pulse Output
Set O/P 2 Function
Highlight the required option and press E to
enter the selection.
Note:
Two or more of the outputs may be
configured to output the same function.
6.4.9 Output 3
As Output 2 except terminals are A5 and A6.
6.4.10 Optional outputs 4, 5 and 6
Only available when factory fitted option is
installed in the BA458C batch controller.
Configuration is the same as for Output 2,
except terminal numbers are:
Output
Terminal numbers
4
A7 & A8
5
A9 & A10
6
A11 & A12
6.4.11 Pulse Output
Any of the batch controller outputs may be
configured as a pulse output. The number of
output pulses is proportional to the total
volume dispensed by the batch controller.
This Pulse Output function enables the pulse
output frequency to be reduced by one of five
dividing factors between 10 and 100,000.
Display / 1
Display / 10
Display / 100
Display / 1000
Display / 10000
Display / 100000
Set Output Rate
Highlight the required option and press E to
enter the selection.
Note:
Maximum output frequency is 4 Hz.
6.4.12 Clear Grand Total
The Grand Total is a record of the total
quantity of product dispensed since the Grand
Total was last reset to zero. It must be zeroed
every time the batch controller scaling is
changed
The Grand Total can be viewed in the
Information section of the System Menu – see
section 6.2.
CAUTION
After zeroing the old grand total
can not be recovered
To prevent the Grand Total being accidentally
zeroed, the clear instruction has to be
confirmed before it will be executed.
Clear G Total
Cancel
Clear Grand Total
Summary of Contents for BA458C
Page 1: ...Issue 5 1st December 2010 BA458C Intrinsically safe Panel mounting Batch Controller Issue 5 ...
Page 16: ...16 Fig 11 System Settings ...
Page 21: ...21 BLANK PAGE ...
Page 22: ...22 Fig 14 Batch Settings ...
Page 27: ...27 BLANK PAGE ...
Page 28: ...28 Fig 16 Rate Settings ...
Page 35: ...35 ...
Page 36: ...36 ...
Page 37: ...37 APPENDIX 2 Information menu ...
Page 39: ...39 ...
Page 40: ...40 ...
Page 41: ...41 ...
Page 42: ...42 ...
Page 43: ...43 ...
Page 44: ...44 ...
Page 45: ...45 ...