11.3.8  Access Setpoint:  AcSP

This function controls the parameters in a separate
menu which provides direct access to the alarm
setpoints when the transmitter is in the display
mode i.e. when it is displaying temperature.  See
section 11.4 for a full description.    This menu
allows an operator to adjust the two alarm
setpoints without having access to the Programme,
Trim or Alarm Menus.  A separate security code
may be defined to prevent unauthorised access.

This separate direct access menu is enabled and a
separate security code entered from the 'AcSP'
function in the Programme Menu - see Fig 13.   To
change the menu parameters select 'AcSP' from
the Programme Menu and press 

P

  which will

display the enable prompt 'EnbL'.  Press 

P

 again to

reveal if the direct access menu is 'On' or 'OFF'.
The 

Up

 or 

Down

 buttons will toggle the display

between the two conditions.  

If 'OFF' is selected, the operator will not have
access to the setpoints from the display mode.
Return to the 'AcSP' prompt in the main menu by
pressing

 E

 twice.  

If 'On' is selected, the operator will have direct
access to the alarm setpoints from the display
mode via a separate optional security code.   To
define the four digit numerical code press 

P

 to

return to the 'Enbl' prompt followed by the 

Up

 or

Down

 button to select the access code prompt

'AcCd'.   Pressing 

will reveal the current security

code.  Each digit of the code may be changed by
operating the 

Up

 and 

Down

 push-buttons, and the

P

 button to move to the next digit.  When the

required code has been entered, press 

E

 twice to

return to the 'AcSP' prompt in the Programme
Menu.

Code 0000 will disable the security code allowing
direct access to the setpoints by pressing the

  P

and 

Up

 buttons simultaneously.

New instruments are supplied with this function
disabled and the security code set to 0000

11.4  Adjusting the alarm setpoints from the

   display mode.

Access to the alarm setpoint when the BA374C
transmitter is in the display mode is obtained by
operating the 

P

 and 

Up

 push-buttons simultane-

ously - see Fig 14.   If the setpoints are not
protected by a security code the alarm setpoint one
'SP1' will be displayed.  If the setpoints are
protected by a security code,  'COdE' will be
displayed first.  Pressing 

P

 again will  enable the

alarm security code to be entered digit by digit
using the 

Up

 and 

Down

 buttons to change the

flashing digit, and the 

P

  push-button to move to

the next digit.   If the correct code is entered press-
ing 

E

 will cause alarm setpoint one 'SP1' to be

displayed.  Pressing the 

Up

 or 

Down

 button will

toggle the display between 'SP1' and 'SP2'.  

Fig 14  Setpoint adjustment from display mode

If an incorrect code is entered, or a button is not
pressed for ten seconds, the transmitter will
automatically return to the display mode. 

To adjust an alarm setpoint select 'SP1' or 'SP2'
and press 

P

  which will reveal the current setting.

Each digit of the setpoint may be adjusted using
the 

Up

 and 

Down

 push-buttons, and the 

button

to move to the next digit.  When the required
setpoint has been entered, pressing  

E

  will return

the display to the 'SP1' or 'SP2' prompt from which
the other setpoint may be selected, or the transmit-
ter may be returned to the display mode by press-
ing 

E

 again. Direct access to the alarm setpoints is

only available when the menu is enabled - see
section 11.3.8

      26

Summary of Contents for BA374C

Page 1: ...BA374C Intrinsically safe field mounting indicating temperature transmitter Issue 5 3rd December 2003...

Page 2: ...ut current calibration 6 7 Security code 6 8 Calibrating the internal references 6 8 1 Conditioning internal references 6 8 2 Voltage input reference 6 8 3 3 wire RTD reference 6 8 4 4 wire RTD refere...

Page 3: ...Section 6 you will find information on setting up for Section 6 3 Thermocouple input Section 6 4 Resistance thermometer input Section 6 5 Voltage input A word of warning Section 6 8 explains how you...

Page 4: ...4...

Page 5: ...ing look up tables stored in permanent memory The resulting temperature is shown on the internal display and controls the 4 20mA output current The transmitter and the optional alarms are powered from...

Page 6: ...BA374C to be installed in all Zones and to be used with most common industrial gases at ambient temperatures between 40 60o C Note minimum operating temperature 20o C 3 4 Certification information la...

Page 7: ...Any certified diode return barrier may be used in the return wire For guidance System Certificate Ex96D2505 list some of these devices Fig 3 BA374C powered from a common supply When designing any loo...

Page 8: ...d such that the environmental conditions specified by the instru ment datasheet and the EC Type Examination Certificate are not exceeded Please consult BEKA associates if the instrument is to be insta...

Page 9: ...ogramme menu calibration procedure using the trim menu and the calibration example in sections 6 1 7 1 and 8 are read prior to changing function or calibrating the transmitter Figs 7A 7B and 9 show th...

Page 10: ...ctions in the programme menu is described in the following summary with a cross reference to more detailed information Figs 7A and 7B illustrates the location of each function within the menu Display...

Page 11: ...11...

Page 12: ...12...

Page 13: ...will reveal the current setting This setting may be changed by scrolling through the menu using the Up or Down buttons When the required input is displayed pressing P will reveal a sub menu enabling...

Page 14: ...esistance thermometer input from the InPut sub menu press P to reveal the tYPE sub menu Press P again to display the current type of resistance thermometer which may be changed by scrolling through th...

Page 15: ...transfer control to the next digit When the least significant digit has been adjusted press E to return to the InPut prompt from which the display prompt dISP can be selected by pressing the Up or Dow...

Page 16: ...Voltage input 3 wire RTD 4 wire RTD Current output The input voltage reference must be adjusted first irrespective of the transmitter application but it is only necessary to adjust the other three ref...

Page 17: ...ly 4mA The transmitter output current shown on the external current measuring instrument should be adjusted to 4 000 0 001mA using the transmitter Up and Down buttons When correct press the E push but...

Page 18: ...temperature of the primary element operate the Up or Down buttons until the transmitter display is correct Immediately the Up or Down button is operated the annunicator in the top left hand corner of...

Page 19: ...ple With tHC displayed press P to enter the thermocouple sub menu The first parameter tYPE will be displayed pressing P again will give access to the seven different types of thermocouple Select J usi...

Page 20: ...erature although this may be less accurate With the transmitter displaying the ZEro prompt and the correct input connected to the transmitter push P which will cause the transmitter to display the the...

Page 21: ...hazardous area but only certified test equipment should be used unless a gas clearance certificate is available If a BA374C fails after it has been functioning correctly the procedure shown in sectio...

Page 22: ...74C can be supplied with two solid state single pole alarm outputs Each output may be programmed as a high or low alarm with a normally open or a normally closed output Fig 10 illustrates the conditio...

Page 23: ...ary of programmable alarm functions Display Summary of function EnbL Alarm enable Enables or disables the alarm function without changing the alarm parameters See section 11 3 1 SP1 Alarm setpoint 1 A...

Page 24: ...24 Fig 13 Programme structure for optional alarms...

Page 25: ...rm output status select no nc from the alarm sub menu and press P reveal the current setting The function can be changed by pressing the Up or Down button followed by the E button to return the no nc...

Page 26: ...AcSP prompt in the Programme Menu Code 0000 will disable the security code allowing direct access to the setpoints by pressing the P and Up buttons simultaneously New instruments are supplied with thi...

Page 27: ...or galvanic isolator may be used providing the output parameters do not exceed Uo 30V dc Io 159mA Po 0 8W For guidance the system certificates list some of the devices which may be used Fig 15 Backli...

Reviews: