Display
Summary of function
FiLtEr
Display filter
Is an adjustable digital filter to reduce
the noise on the rate display. The
filter has two parameters each
represented by a digit adjustable
between 0 and 9. The first digit
defines the amount of filtering applied
to the display, the second digit the
deviation from the displayed rate at
which the filter will be overridden and
the rate display will move rapidly to
the new value.
See section 6.20
up or dn
Direction of count
Determines whether pulses at inputs
A and b increment or decrement the
total display.
See section 6.21
CLr VAL
Reset value
Defines a preset number to which the
total display will be set when the
BA364NG Counter is locally or
remotely reset. Enables the
instrument to count down from a
preset number.
See section 6.22
LoC CLr
Local reset
Contains sub-menu with two
functions enabling the total and the
grand total to be reset via the front
panel push buttons while the Counter
is in the display mode.
See section 6.23
Clr tot
Local total reset
When
on
is selected total display is
reset when
&
and
*
buttons are
operated simultaneously for more
than 3 seconds in the display mode.
See section 6.24
Clr Gtot
Local grand total reset
When
on
is selected the grand total
may be reset when
)
and
*
buttons are operated simultaneously
for more than 10 seconds in the
display mode - see section 2.2 for
details.
Note:
Once reset, the grand total can
not be restored.
See section 6.25
Display
Summary of function
Clr Gtot
Resets grand total to zero from
within configuration menu.
This function resets the grand total
to zero from within the
configuration menu when
CLr YE5
is selected.
Note
: Once reset, the grand total
can not be recovered.
See section 6.26
CodE
Access code
Defines a four digit alphanumeric
code that must be entered to gain
access to the configuration menu.
Default code 0000 disables the
security function and allows
unrestricted access to all
configuration functions.
See section 6.27
r5Et dEF
Reset configuration to factory
defaults.
Returns the BA364NG Counter to
the factory defaults shown in
section 6.0 To prevent accidental
use the request must be confirmed
by entering
5urE
before the reset
will be executed.
See section 6.28