A1.4
Special conditions for use in IIIC dusts
The ATEX certificate has an ‘X’ suffix indicating
that special conditions apply for safe use. In
addition to the electrostatic special conditions
specified in section 3.3 for installations in IIIC dust
atmospheres, the certificate states:
‘For use in Group IIIC conductive gas
atmospheres, the Rate Totaliser shall be
mounted such that the instrument
terminals have at least IP6X protection.’
To prevent the instrument terminals becoming
contaminated by conductive dust the BA358E must
be installed in a panel, cubicle or enclosure
providing a minimum of IP6X protection.
The gasket supplied to seal the joint between the
indicator and the mounting panel should be used
and the BA358E should be secured with four panel
mounting clamps.
Note:
These additional special installation
conditions only apply for indicators exposed to IIIC
conductive dust atmospheres.
38