repeatedly press
(
until the total number of
segments is reduced to the required number.
If removing a segment from a configured lineariser,
the segment to be deleted, which is shown on the
left hand side of the display, can be selected using
the
&
or
*
push button.
When a segment is
deleted, the identification numbers of all segments
above the deleted segment are decreased by one.
Press
)
to return to the
dEL
prompt in the lineariser
sub-menu.
7.5 Input frequency:
PuL5E Fr
PuL5E Fr
is a sub-menu in the
FACtor
function for
entering the pulse input frequency at which each of
the lineariser segments starts, see Fig 12.
To enter the input pulse frequency at which one or
more lineariser segments start, select
FACtor
in the
configuration menu and press
(
which will reveal
one of four sub-functions.
If
PuL5E Fr
is not
displayed repeatedly press the
&
or
*
button to
select
PuL5E Fr
followed by
(
to display the
current segment for which the start frequency will be
entered and the total number of segments that have
already been defined using the
Add
and
dEL
functions, see below.
The required segment, which is shown on the left
hand side of the display, can be selected using the
&
or
*
push button.
When selected press
(
which will reveal the current input frequency with
one digit flashing. The value of the flashing digit
may be changed by pressing the
&
or
*
button.
When this digit is correct pressing
(
will transfer
control to the next digit.
When the input frequency
for this lineariser segment is set as required, press
the
)
button to return to the segment identification
display from which the next segment may be
selected using
&
or
*
push button.
When the input frequency for all of the segments
has been entered, return to the
FACtor
prompt in the
configuration menu by operating the
)
push button.
7.6 Flowmeter K-factor
L-Factor
L-FACtor
is a sub-menu in the
FACtor
function for
entering the flowmeter K-factor for each of the
lineariser segments, see Fig 12.
The rate totaliser pulse input is divided by
L-FACtor
,
which is adjustable between 0.0001 and 99999; for
flow applications it should be set to the K-factor of
the flowmeter. K-factor is the number of pulses that
32
Summary of Contents for BA337E
Page 4: ...4 ...
Page 22: ...22 ...
Page 23: ...23 ...
Page 30: ...30 ...
Page 41: ...41 ...
Page 50: ...50 ...
Page 51: ...51 ...
Page 52: ...52 ...
Page 53: ...53 ...
Page 54: ...54 ...
Page 55: ...55 ...
Page 56: ...56 ...
Page 57: ...57 ...
Page 58: ...58 ...
Page 59: ...59 ...
Page 60: ...60 ...
Page 61: ...61 ...