background image

4

2.1   Controls

Both models are controlled and calibrated via four
front panel push buttons which may be operated
while the indicator is energised in a hazardous
area.

In the display mode i.e. when the indicator

is displaying a process variable, these push
buttons have the following functions:

(

While this button is pushed the
indicator will display the input current
in mA, or as a percentage of the
instrument span depending upon how
the indicator has been configured.
When the button is released the
normal display in engineering units
will return. 

&

While this button is pushed the
indicator will display the numerical
value and analogue bargraph

 

1

the

indicator has been calibrated to
display with a 4mA

 2

input.

When

released

the

normal

display

in

engineering units will return.

*

While this button is pushed the
indicator will display the numerical
value and analogue bargraph 

1

the

indicator has been calibrated to
display with a 20mA 

2

input. When

released

the

normal

display

in

engineering units will return.

)

No function in the display mode
unless the tare function is being used.

(

 + 

&

Indicator displays firmware number
followed by version.

(

 + 

)

Provides access to the configuration
menu via optional security code.

Notes:

1

 

Only the BA324SG has a bargraph

2

 

If

the

indicator

has

been

calibrated

using

the

CAL

function, calibration

points

may not be 4 and 20mA.

3.    CERTIFICATION

Both models have IECEx and ATEX Ex eb
increased safety and Ex tb dust ignition protection
by enclosure certification.  

This section of the instruction manual describes
IECEx and ATEX Ex eb certification for installation
in gas hazardous areas.

Ex tb certification for

installation in dust hazardous areas is described in
Appendix 1.

3.1   IECEx and ATEX Ex eb certification

Increased safety Ex eb is a type of electrical
equipment protection which provides increased
security against the possibility of excessive
temperatures and against the occurrence of arcs
and sparks.

The requirements are defined by

international standard IEC 60079-7 which is
published in the UK as BS EN 60079-7.  

To allow the BA304SG and BA324SG to be
installed in Zone 1, both indicators incorporate an
encapsulated Ex mb assembly. This encapsulated
assembly has an intrinsically safe Ex ib output
which powers the display and optional display
backlight. 

Certification Body Intertek Testing and Certification
Ltd have issued both models with a common
Certificate of Compliance

IECEx ITS 19.0018X
Ex eb ib mb IIC T5 Gb 
-40°C ≤ Ta ≤ +60°C 

Intertek have also issued an ATEX EU - Type
Examination Certificate:

ITS19ATEX304891X  
II 2G  Ex eb ib mb IIC T5 Gb
- 40°C ≤ Ta ≤ +60°C.  

Note:

Types of protection on both certificates are

listed in alphabetical order.

The ATEX certificate confirms compliance with
harmonised European standards which has been
used to support a manufacturer's Declaration of
Conformity

confirming

compliance

with

the

European

ATEX

Directive

for

Group II,

Category 2GD equipment.

The indicators carry the community mark and,
subject to local codes of practice, may be installed
in any of the European Economic Area (EEA)
member countries.

ATEX certificates are also

acceptable for installations in Switzerland and
some other countries - see Blue Book.

This section of the instruction manual describes
installations

in

explosive

gas

atmospheres

conforming

with IEC / EN 60079-14

Electrical

installations design, selection and erection

. When

designing systems for installation outside the UK
the local Code of Practice should be consulted.

For more information about the certification
techniques employed in these indicators, please
see BEKA Application Guide AG320 which may be
viewed and downloaded from the BEKA website
www.beka.co.uk

Summary of Contents for BA304SG

Page 1: ...Issue 2 30th September 2020 BA304SG BA324SG Increased safety Ex eb and dust ignition protection by enclosure Ex tb loop powered field mounting indicators Issue 2 ...

Page 2: ... format and calibration bAr 6 8 Function of the push button C P 6 9 Tare function tArE 6 10 Security code CodE 6 11 Reset to factory defaults r5Et 6 12 Under and over range 7 Lineariser 7 1 Lineariser calibration using an external current source 7 1 1 Example Adding break points to a new indicator 7 2 Lineariser calibration using internal reference 7 2 1 Example Adding break points to a new indica...

Page 3: ...y backlight is available as an option Model Display BA304SG 4 digits 34mm high BA324SG 5 digits 29mm high and 31 segment bargraph This instruction manual supplements the instruction sheet supplied with each instrument The main application of both models is to display a measured variable or control signal in a gas or dust hazardous process area The zero and span of the display are independently adj...

Page 4: ...cation Increased safety Ex eb is a type of electrical equipment protection which provides increased security against the possibility of excessive temperatures and against the occurrence of arcs and sparks The requirements are defined by international standard IEC 60079 7 which is published in the UK as BS EN 60079 7 To allow the BA304SG and BA324SG to be installed in Zone 1 both indicators incorpo...

Page 5: ...rom a SELV separated or safety extra low voltage or PELV protected extra low voltage supply or from an adequately approved supply providing double or reinforced insulation as specified in IEC 60079 14 This requirement also applies to flameproof equipment and does not usually cause any difficulties because the power supply is required to be safe for personnel contact In European terms compliance wi...

Page 6: ...y with the requirements of IEC 60079 14 Electrical installations design selection and erection Figs 2 illustrates a typical application in which an indicator is connected in series with a 2 wire flameproof Ex d transmitter Alternatively an increased safety Ex e pressurised Ex p or in Zone 2 a Type n Ex nA transmitter could be used Fig 2 Typical application showing indicator displaying transmitter ...

Page 7: ... intrinsic safety should be mechanically robust having a toughened outer sheath or armour Wiring should have adequate voltage and current rating and should comply with the requirements of IEC60079 14 Section 9 Cables and Wiring Systems Cables should be suitable for the anticipated operating temperature protected from voltage overloads and have a clearly defined means of isolation No additional cab...

Page 8: ...8 Fig 6 Installation procedure Fig 7 Dimensions of BA304SG and BA324SG Fig 8 Terminal connections ...

Page 9: ...lied when the indicator is ordered a blank scale card will be fitted which can easily be marked on site with a dry transfer or a permanent marker Custom printed scale cards are available from BEKA associates as an accessory To remove the scale card from an indicator carefully pull the transparent tab at the rear of the indicator assembly away from the indicator as shown in Fig 9a Fig 9a Removing s...

Page 10: ...efault Configuration BA304SG BA324SG Access code CodE 0000 0000 Function FunC Linear Linear Display at 4mA 2ero 0 0 0 00 Display at 20mA 5PAn 100 0 100 00 Resolution rE5n 1 digit 1 digit Bargraph start BarLo 0 00 Bargraph finish BarHi 100 00 button in display mode C P Tare tArE Off Off 6 1 Summary of configuration functions This section summarises each of the main configuration functions and inclu...

Page 11: ...11 ...

Page 12: ...ion Lin 16 segment adjustable lineariser To reveal the indicator s existing function select FunC from the configuration menu and press If the function is set as required press to return to the menu or press the or button to change the setting followed by the button to return to the configuration menu 5td Linear Provides a linear relationship between the 4 20mA indicator input current and the indic...

Page 13: ...ing the difference between the two currents is greater than 4mA If these conditions are not complied with the indicator displays FaiL and aborts the calibration c If the zero current is greater than the span current the instrument will be reverse acting i e an increasing input current will cause the display to decrease 6 6 Calibration using internal reference 5Et Using the 5Et function the indicat...

Page 14: ...etting between on and oFF When set as required press to return to the tARE prompt in the configuration menu 6 10 Security code CodE Access to the instrument configuration menu may be protected by a four digit security code that must be entered to gain access New instruments are configured with the default security code 0000 which allows unrestricted access to all configuration functions To enter a...

Page 15: ...allows direct calibration of the lineariser with an external current source and is the preferred method when traceability is required If the exact system non linearity is unknown this method also allows direct calibration from the variable to be displayed e g the output from a level sensor in an irregular tank may be displayed in linear volumetric units by filling the tank with known incremental v...

Page 16: ...16 ...

Page 17: ...ing break point 7 1 1 Example Adding break points to a new indicator When adding break points to a new indicator or to a lineariser following resetting to the factory defaults using the r5et function described in section 6 11 each additional break point should be added before the highest existing breakpoint The first additional break point should be added before the default break point 1 1 which w...

Page 18: ...ction by pressing the button The corresponding indicator display at each of the break points can now be defined using the di5P sub function Using the and buttons select the di5P sub function and press which will reveal the starting point for the first break point 0 n where n is the total number of break points entered Press and use the and buttons and the button to move between digits to enter the...

Page 19: ... eb and Ex tb certified indicators The instrument enclosure should only be opened when the indicator is de energised or a gas dust clearance certificate has been issued If an indicator fails after it has been functioning correctly follow the procedure shown in section 8 1 If this does not reveal the cause of the fault it is recommended that the instrument is replaced 8 3 Servicing BA304SG and BA32...

Page 20: ...394G panel mounting kit which consists of two 316 stainless steel brackets will secure an indicator into a panel aperture The kit does not seal the joint between the panel and the instrument and is intended for mounting an indicator onto an open panel APPENDIX 1 Dust Certification A1 0 Ex tb dust certification In addition to IECEx and ATEX certification permitting installation in explosive gas atm...

Page 21: ...m foreign bodies It is good practice to prevent dust accumulating on the indicator enclosure If this can not be avoided care should be taken to ensure that the layer thickness does not exceed 5mm for dusts having a minimum ignition temperature of 155 C A1 3 Cable glands and conduit fittings Both back box cable entries have M20 x 1 5 threads The right hand entry is fitted with an Ex e and Ex t cert...

Reviews: