![BEKA A504G-SS-PM Manual Download Page 22](http://html1.mh-extra.com/html/beka/a504g-ss-pm/a504g-ss-pm_manual_2723865022.webp)
22
8.3.2
Configuration and adjustment
When optional alarms are fitted to a loop powered
indicator the configuration menu is extended as
shown in Fig 17. The additional functions appear
between the
5Et
and the
C--P
functions for the
BA504G-SS-PM and between
bAr
and
C--P
for the
BA524G-SS-PM indicator. For simplicity, Fig 17
only shows the additional functions for alarm 1, but
alarm 2 has identical functions.
The following table summarises each of the alarm
configuration functions and includes a cross
reference to more detailed information. Again only
the functions on Alarm 1 are listed, but alarm 2 has
identical facilities.
Summary of alarm configuration functions
Display
Summary of function
EnbL
Alarm enable
Enables or disables the alarm without
changing the alarm parameters.
See section 8.3.3
5P1
Alarm setpoint 1
Adjusts the alarm setpoint. The alarm is
activated when the indicator display
equals the setpoint.
See section 8.3.4
Hi.
Lo
Alarm function
Defines the alarm function as High or
Low.
See section 8.3.5
no
.
nC
Normally open or normally closed
output
Sets the alarm output open or closed in
the non-alarm condition.
See section 8.3.6
H5tr
Hysteresis
Adjusts the alarm hysteresis.
See section 8.3.7
dELA
Alarm delay time
Introduces adjustable delay between the
display equalling the setpoint and the
alarm output being activated.
See section 8.3.8
5iL
Alarm silence time
Defines the time that the alarm output
remains in the non-alarm condition
following acceptance of an alarm.
See section 8.3.9
FL5H
Flash display when alarm occurs
When enabled, alternates the numerical
display between process value and alarm
reference,
ALr1
or
ALr2
, when an alarm
output is activated.
See section 8.3.10
AC5P
Access setpoint
Sub-menu which enables direct access
to the alarm setpoints from the indicator
display mode, and defines a separate
security code.
See section 8.3.11