34 mm

50 mm

  Embedded box 503

70 mm

1

0

5

 mm

5 mm

1

5

0

 mm

84 mm

115mm

1)  MAINS  connected  indication  LED.  When  the  unit  turns  on,  this  LED  blinks  and  a  test  of  the  gas  detection
sensors’  efficiency  status  is  carried  out.  This  phase  takes  about  100  seconds.  Afterwards  the  LED  stays  on
without  blinking.  During  the  test  period,  the  CHCO  does  not  detect  the  gas.
2)  FAULT  indication  LED.  If  this  LED  turns  on,  it  means  that  one  of  the  gas  detection  sensors  is  not  working
efficiently  and  must  be  replaced  in  an  authorized  centre.
A  relay  is  connected  to  the  fault  circuit  as  well  as  the  light  indication  and  a  “cricket”  siren.
3)  CO  ALARM  indication  LED.  This  LED  will  light  up  when  the  gas  concentration  level  has  reached  the  300ppm
concentration,  or  when  the  accumulation  level  is  reached.  The  relay  contact  is  closed,  and  an  impulsive  sound
is  issued.
4)  Explosive  GAS  ALARM  indication  LED.  This  LED  will  light  up  and  blink  when  the  gas  concentration  level  has
reached  10  %  of  LEL.  The  relay  contact  is  closed,  and  an  intermittent  sound  is  issued.
5)  Electrochemical  Cell  sensor  for  Carbon  Monoxide  detection
6)  Catalytic  sensor  for  Methane  explosive  gas  detection.
7)  TEST  button.  This  button  is  used  to  simulate  a  gas  leak,  after  installation.
8)  Identification  label,  serial  number  and  manufacturing  year,  located  under  the  ABS  small  dome.

9

)  Label  of  the  gas  sensor  expiration  date.

This  label  must  be  applied  by  the  technician  during  the  installation

  and  remembering  that    the  gas

sensor  must  be  reviewed  after  5  Years.

Components and commands

 Applicare Etichetta
di scadenza

BUZZER

Summary of Contents for CHCO

Page 1: ...Installation EN 60079 29 2 The CHCO Detector has been designed and built according to European regulations to detect the presence of toxic and explosive gas A microprocessor is used to create a complete surveillance and control system with maximum flexibility Thanks to this and its other features this detector is suitable for household applications IThe CHCO Detector can detect the presence of two...

Page 2: ...on 10A 250V resistive Insulation Class II Explosive Gas Explosive gas sensor Catalytic Explosion Alarm Threshold At 10 of L E L Toxic Gas CO toxic gas sensor Electrochemical Cell CO detector alarm sensitivity 30 300ppm CO gas detector alarm threshold according to norm EN 50291 on gas accumulation ALARMS 30 ppm within 120 minutes 50 ppm within 60 minutes 100 ppm within 10 minutes 300 ppm within 3 m...

Page 3: ... concentration level has reached the 300ppm concentration or when the accumulation level is reached The relay contact is closed and an impulsive sound is issued 4 Explosive GAS ALARM indication LED This LED will light up and blink when the gas concentration level has reached 10 of LEL The relay contact is closed and an intermittent sound is issued 5 Electrochemical Cell sensor for Carbon Monoxide ...

Page 4: ...cording to Regulations in force keeping in mind that the signal cables should be laid separate from the power cables An automatic cut off switch appropriately identified as devicesectioning of the detector should be incorporated in the electrical system adequatelylocated and easily accessible N Power Supply 230 VAC Ph 1 2 3 4 5 6 7 8 N C C NO N C C NO Relay Alarme Gas CO Relay Alarm Gas methane N ...

Page 5: ...etectors with a normally close valve 230VAC Electricalconnections 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 NC C NO NC C NO NC C NO NC C NO Connection 230 VAC N Ph 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 NC C NO NC C NO NC C NO NC C NO Connection 230 VAC N Ph N Power Supply 230 VAC Ph 1 2 3 4 5 6 7 8 N C C NO N C C NO solenoid valve NA Fan ...

Page 6: ...the state of work Ceased the alarm the Led turns off it stops the sound of the buzzer and the connected devices will be disabled Test run with GAS a To test the explosive gas emit the gas from a pre calibrated bottle within 20 of the LEL inside the sensor concerned see item 6 of page 3 N B This test is recommended to be performed once a year Nota Do a test with a common cigarette lighter could dam...

Page 7: ...the CHCO detection capsule status They may faulty or to have exhausted after 5 6 years must be replaced If the detector is repeatedly issuing an alarm 1 Check that there are no gas leaks 2 Check that there is not a persistent low concentration of CO Check see table on page 4 Make sure that together with the alarm it does not turn on even the FAULT led in this case proceed to the control of the sen...

Page 8: ...cluded from the warranty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicable collecti...