background image

Page  6

The position of the detector is a crucial factor for its correct functioning during gas detection. In order to obtain the
maximum results from a device and minimize the probability of false alarms, it is recommended to follow this scheme
and keep in mind the following general regulations. The CHCO is an equipment adapted to be mounted on a wall.
When installing is good to use reasonable care that requires an electronic device, and then:
- Install the detector away from sources of heat.
- Avoid that the liquids may come into contact with the detector, remembering that its box has a degree of protection
IP42.

The installation height of the detector CHCO must be from a minimum to a maximum of:
Maximum 30 cm from the highest point of the ceiling
Minimo 160 cm. from the floor

1)  When  powering  on  the  CHCO,  you  will  see  that  the  MAINS  LED  lights  up  and  starts  blinking  for  about  90
seconds.
Afterward the LED stays on without blinking, the CHCO is ready to detect.
2) Press the button placed on the side the sensor to simulate the presence of gas.
The  Led  alarm  lights  up,  the  relay  changes  the  state  of  work.
Ceased the alarm, the Led turns off, it stops the sound of the buzzer and the connected devices will be disabled.
Test run with GAS
a)
  To test the explosive gas emit the gas from a pre-calibrated bottle within 20% of the LEL inside the sensor
concerned, see item 6 (of page 3).
N.B. This test is recommended to be performed once a year.
Nota: Do a test with a common cigarette lighter could damage the sensor.
b) To test the toxic gas emit gas from a pre-calibrated bottle from 30 to 300 ppm, in the grey sensor, see item
5 (of page 3).
Using  other  types  of  gas  could  damage  the  sensor.
N.B.  This  test  is  recommended  to  be  performed  once  a  year.

Turn on and testing

Methane  and  carbon  monoxide
gas  detector
max.  30  cm  from  the  ceiling
min.  1,60  from  the  floor

0  15  30  45  60  75  90  105  120 135  150

Clean
  Air

Diagram  of  detection

G

a

s

 

d

e

te

c

ti

o

n

 

in

 

p

p

m

30 ppm CO
50 ppm CO
100 ppm CO
300 ppm CO

Time in  minutes

Installation measures and positioning

Table n° 2 of  EN 50291

“CONDITIONS                   ALARMS ”

30    ppm

120  minutes

50    ppm

60  minutes

100    ppm

10  minutes

300    ppm

within  3  minutes

Concentration  co 

 

         ALARM AFTER

The detector must not be installed
behind the barriers that hinder the
prompt  detection  of  gas  .  near  of
aspirators or fans and in areas where
the temperature falls below 10 ° C or
rises above 40 ° C.

Summary of Contents for CHCO

Page 1: ...Installation EN 60079 29 2 The CHCO Detector has been designed and built according to European regulations to detect the presence of toxic and explosive gas A microprocessor is used to create a complete surveillance and control system with maximum flexibility Thanks to this and its other features this detector is suitable for household applications IThe CHCO Detector can detect the presence of two...

Page 2: ...on 10A 250V resistive Insulation Class II Explosive Gas Explosive gas sensor Catalytic Explosion Alarm Threshold At 10 of L E L Toxic Gas CO toxic gas sensor Electrochemical Cell CO detector alarm sensitivity 30 300ppm CO gas detector alarm threshold according to norm EN 50291 on gas accumulation ALARMS 30 ppm within 120 minutes 50 ppm within 60 minutes 100 ppm within 10 minutes 300 ppm within 3 m...

Page 3: ... concentration level has reached the 300ppm concentration or when the accumulation level is reached The relay contact is closed and an impulsive sound is issued 4 Explosive GAS ALARM indication LED This LED will light up and blink when the gas concentration level has reached 10 of LEL The relay contact is closed and an intermittent sound is issued 5 Electrochemical Cell sensor for Carbon Monoxide ...

Page 4: ...cording to Regulations in force keeping in mind that the signal cables should be laid separate from the power cables An automatic cut off switch appropriately identified as devicesectioning of the detector should be incorporated in the electrical system adequatelylocated and easily accessible N Power Supply 230 VAC Ph 1 2 3 4 5 6 7 8 N C C NO N C C NO Relay Alarme Gas CO Relay Alarm Gas methane N ...

Page 5: ...etectors with a normally close valve 230VAC Electricalconnections 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 NC C NO NC C NO NC C NO NC C NO Connection 230 VAC N Ph 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 NC C NO NC C NO NC C NO NC C NO Connection 230 VAC N Ph N Power Supply 230 VAC Ph 1 2 3 4 5 6 7 8 N C C NO N C C NO solenoid valve NA Fan ...

Page 6: ...the state of work Ceased the alarm the Led turns off it stops the sound of the buzzer and the connected devices will be disabled Test run with GAS a To test the explosive gas emit the gas from a pre calibrated bottle within 20 of the LEL inside the sensor concerned see item 6 of page 3 N B This test is recommended to be performed once a year Nota Do a test with a common cigarette lighter could dam...

Page 7: ...the CHCO detection capsule status They may faulty or to have exhausted after 5 6 years must be replaced If the detector is repeatedly issuing an alarm 1 Check that there are no gas leaks 2 Check that there is not a persistent low concentration of CO Check see table on page 4 Make sure that together with the alarm it does not turn on even the FAULT led in this case proceed to the control of the sen...

Page 8: ...cluded from the warranty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicable collecti...

Reviews: