 PROBE INSTALLATION INFORMATION

Installation and positioning of the probe

The BX180 control unit belongs to group II and must be installed in a safe area;

Outside the ATEX zone

, however, not in boiler rooms or engine room.

The control unit must be accessible and visible to the user.

The BX180 is designed so that it can be mounted  into electrical panels.
The Control Unit complete cabinet is an equipment suitable for wall mounting and is powered by 110/240 VAC with
IP20 protection

When installing, it is good to use the normal care that an electronic equipment requires:
- Install the equipment away from excessive heat sources.
- Avoid liquids coming into contact with the control unit, remembering that its external structure has IP20 degree of
protection if installed on the Boxed version (cabinet) supplied to the source is ....

The sensor must be selected with an IP degree depending on the area to be controlled (Kitchens, Boiler
Rooms, Laboratory, etc.) by selecting one of the probes from Beinat from IP30 to ATEX. 
see page 3

Position of the detection sensor

You can connect many types of remote probes to this unit. Therefore, they should be positioned at different heights
depending on the type of gas to be detected.

These heights are:
- 30 cm from the lowest point of the floor in order to detect:

Heavy gases (L.P.G. etc.)

- 30 cm from the highest point of the ceiling in order to detect:

light gases (Methane, etc.)

- 160 cm from the lowest point of the floor in order to detect:

volatile gases (CO, etc.)

It is important to note that the remote probes should be installed according to the following restrictions:

1) The sensor hould not be placed near the appliances to be controlled (boilers, burners, industrial kitchens, etc.)
but on the opposite side.
2) The sensor should not be affected by smoke, vapour, and moving air, as they could distort their measurement.
3) The sensor should not be placed near sources of heat, ventilators or fans.
It should be noted that the internal GAS sensors of the probe are perishable components with a variable average
life span from 5 to 6 years (you can request the relative table). Therefore, after this period of time has elapsed it
is advisable to replace them.
4) The control of operation and maintenance  and / or extraordinary must be carried  at least once a year. good
to keep
When turning on leds fault is necessary make the replacement of the probe by a specialized technician.

 

30 cm Light Gases

  30 cm Heavy Gases

160 cm Volatile Gases

Summary of Contents for BX180

Page 1: ...uilt according to European regulations to detect the presence of toxic and or explosive gas flexibly A microprocessor is used to create a complete surveillance and control system with maximum flexibility Thanks to this and its other features the BX180 is suitable for civil and industrial applications The BX180 control unit has two danger levels 1st LEVEL 1st Pre Alarm This was set at 13 of L E L f...

Page 2: ...ation can damage the appliance Cleaning Never clean the device with chemical products If necessary wash with a moist cloth Technical Specifications Page 2 Precautions Mains Power 110 230VAC 50 60Hz 10 Secondary Power Through Battery max 2 2 Ah 12 7 V 10 Battery Charger max 2 2 Ah By means of a microprocessor PowerDemand 4 W max 230V Power Demand 3 W max 12 V Relay Contact Range 10A 250V Pre Alarm ...

Page 3: ...SGF110 Electrochemical IP64 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SGF112 Catalytic IP64 Zone 2 Hydrogen 0 100 LEL 4 20 mA 5 Yes Yes CO100r Electrochemical IP55 Tertiary C O 0 300 ppm 4 20 mA 5 Yes Yes CO100Ar Electrochemical IP66 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SG800duct Catalytic IP66 Zone 2 CH4LPG 0 100 LEL 4 20 mA 5 Yes Yes CO200duct Electrochemical IP66 Zone 2 C O 0 300 ppm 4 20 mA 5 Y...

Page 4: ...e check the battery and the connection cables OVER LOAD BATTERY LED battery overload If this led turns on it means the battery is not connected properly or it has an anomalous voltage absorption Please check the battery and the connection cables 5 RESET BUTTON This button is pressed to reset all memories 6 TEST BUTTON Pressing and holding down this button you can obtain a gas leakage simulation Th...

Page 5: ...osition the intrinsic safety function is enabled In the OFF position the intrinsic safety function is disabled The relay is energized only when the BX180 goes into the mainl alarm Switch 2 Working mode of the relay and the main alarm In the OFF continuous position the relay remains closed until the RESET button is pressed In the ON impulse position the relay remains closed for 20 seconds and then ...

Page 6: ...the voltage is correct Carefully follow the instructions and the connections according to Regulations in force keeping in mind that the signal cables should be laid separate from the power cables An automatic cut off switch appropriately identified as devicesectioning of the detector should be incorporated in the electrical system adequatelylocated and easily accessible BX180 Pre Alarm Main Alarm ...

Page 7: ... permitted An external power unit must always be used The BX180 gives a max current of 50mA Control unitpower supplyandconnection of one solenoid valve with sirens to 12VDC trough an alternative source and recharge battery C NC NO C NC NO C NC NO PH N 4 5 6 7 8 9 10 Fault 1 Threshold Solenoid valve NC Ph N 230 VAC C NC NO C NC NO C NC NO PH N 4 5 6 7 8 9 10 Fault 1 Threshold Alarm Solenoid valves ...

Page 8: ...rk well is connected to the BX180 Direct connection of 12VDC solenoid valves or sirens to the BX180 is not permitted An external power unit must always be used The BX180 gives a max current of 50mA Ph N C NC NO C NC NO C NC NO PH N 4 5 6 7 8 9 10 Fault 1 Threshold Alarm Solenoid valves Diode 1N 5406 12 V Powersupply 230 12V Ph N 230 VAC 230 VAC 3 2 1 Probe 1 1 2 3 4 5 R1 NC NA ...

Page 9: ... they should be positioned at different heights depending on the type of gas to be detected These heights are 30 cm from the lowest point of the floor in order to detect Heavy gases L P G etc 30 cm from the highest point of the ceiling in order to detect light gases Methane etc 160 cm from the lowest point of the floor in order to detect volatile gases CO etc It is important to note that the remot...

Page 10: ...orrectly connected If powered by the battery check that the 12Vdc power is correctly connected If the Fault LED lights up Check that the connecting cables from the BX180 to the probes are intact that the probes are properly powered and that the signal cable is correctly connected If the Over Load Probe LED lights up Check that the power polarity has not been inverted that no short circuit is prese...

Page 11: ...Page 11 NOTE ...

Page 12: ...ning shall be excluded from the warranty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the app...

Reviews: