BEINAT BX180 Manual Download Page 10

Page  10

1)  Apply  power  using  the  proper  switch.  This  switch  should  be  fitted  with  protection  fuses.

2)  You  will  notice  that  some  LEDs  will  light  up  in  turn  for  about  20  seconds,  so  as  to  test  the  LEDs.

3)  The  COUNTDOWN  begins  that  lasts  about  90  seconds  (warm  up)  afer  this  the  unit  is  ready  to  detect.

4)  By  pressing  the  MANUAL  TEST  button,  you  get  the  simulation  of  a  gas  leak  and  the  unit  carries  out  the
following:

a)  The  Pre-alarm  LED  lights  up  calibrated  to  13%  LEL  or  200  ppm  (referred  to  CO)  switching  the  relay  the
buzzer  will  issue  a  low  frequency  sound

b)  The  Main  alarm  LED  lights  up  calibrated  to  20%  LEL  or  300  ppm  (referred  to  CO)  switching  the  relay.
The  Main  alarm  LED  starts  flashing;  the  buzzer  will  issue  a  hight  frequency  sound

5)    To  complete  the  general  test,  issue  gas  from  a  pre-calibrated  aerosol

6) If  you  want  to  simulate  a  zone  fault,  you  only  need  to  disconnect  the  return  cable  of  the  corresponding
p rob e .
-lights  up  the  flashing  LED  and  FAULT  led  of  the  MAIN  ALARM  led;
-the  buzzer  emits  a  continuous  sound;
-the  fault  relay  and  the  main  alarm  relay  will  switch.
Reconnect  the  return  cable  and  press  the  RESET  button  to  restore  the  functioning  of  the  control  unit.

If  other  problems  arise,  a  specialised  and/or  authorised  technician  and/or  the  Distributor  of  BEINAT
S.r.l.
  should  be  contacted  directly.

If  the  device  does  not  start  up.
Check that the 230V mains power is correctly connected. If powered by the battery, check that the 12Vdc power
is  correctly  connected.
If  the  Fault  LED  lights  up.
Check  that  the  connecting  cables  from  the  BX180  to  the  probes  are  intact,  that  the  probes  are  properly
powered,  and  that  the  signal  cable  is  correctly  connected.

If  the  Over  Load  Probe  LED  lights  up.
Check:  that  the  power  polarity  has  not  been  inverted,  that  no  short-circuit  is  present,
that  the  probes  were  not  damaged  during  installation,
that  no  excessive  current  absorption  is  present.
If  the  Over  Load  Battery  LED  lights  up.
Check  that  the  connection  cables  are  not  short-circuited,  that  the  polarity  has  not  been  inverted,  or  that  the
battery  is  not  damaged.
If  the  Control  Unit  is  repeatedly  issuing  an  alarm.  Check  that  there  are  no  gas  leaks.
If  the  alarm  signal  and  the  FAULT  indicator  light  turn  on  together,  check  the  probes.
If  the  Control  Unit  is  issuing  an  alarm  and  does  not  shut  off  the  devices  connected  to  it.
Check  that  the  wiring  is  correct  and  that  the  jumper  that  carries  power  to  the  relay  has  been  set  properly.  All
relays  must  be  free  from  electrical  power
.
Check  the  drawing  of  the  connections.
If  a  12Vdc  solenoid  valve,  which  does  not  work  well,  is  connected  to  the  BX180.
Direct  connection  of  12Vdc  solenoid  valves  or  sirens  to  the  BX180  is  not  permitted.  An  external  power  unit
must  always  be  used
The  BX180  gives  a  max  current  of  50mA.

Turning the BX180 ON

Troubleshooting and solutions  before calling a technician

0

1

3

2

1,1

V.

Vol tmeter

WARNING.
This  measurement  should
be  performed  in  clean  air

12 V

+

+

Optional

3   2   1

Probe  1

1    2    3    4    5

R1

Summary of Contents for BX180

Page 1: ...uilt according to European regulations to detect the presence of toxic and or explosive gas flexibly A microprocessor is used to create a complete surveillance and control system with maximum flexibility Thanks to this and its other features the BX180 is suitable for civil and industrial applications The BX180 control unit has two danger levels 1st LEVEL 1st Pre Alarm This was set at 13 of L E L f...

Page 2: ...ation can damage the appliance Cleaning Never clean the device with chemical products If necessary wash with a moist cloth Technical Specifications Page 2 Precautions Mains Power 110 230VAC 50 60Hz 10 Secondary Power Through Battery max 2 2 Ah 12 7 V 10 Battery Charger max 2 2 Ah By means of a microprocessor PowerDemand 4 W max 230V Power Demand 3 W max 12 V Relay Contact Range 10A 250V Pre Alarm ...

Page 3: ...SGF110 Electrochemical IP64 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SGF112 Catalytic IP64 Zone 2 Hydrogen 0 100 LEL 4 20 mA 5 Yes Yes CO100r Electrochemical IP55 Tertiary C O 0 300 ppm 4 20 mA 5 Yes Yes CO100Ar Electrochemical IP66 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SG800duct Catalytic IP66 Zone 2 CH4LPG 0 100 LEL 4 20 mA 5 Yes Yes CO200duct Electrochemical IP66 Zone 2 C O 0 300 ppm 4 20 mA 5 Y...

Page 4: ...e check the battery and the connection cables OVER LOAD BATTERY LED battery overload If this led turns on it means the battery is not connected properly or it has an anomalous voltage absorption Please check the battery and the connection cables 5 RESET BUTTON This button is pressed to reset all memories 6 TEST BUTTON Pressing and holding down this button you can obtain a gas leakage simulation Th...

Page 5: ...osition the intrinsic safety function is enabled In the OFF position the intrinsic safety function is disabled The relay is energized only when the BX180 goes into the mainl alarm Switch 2 Working mode of the relay and the main alarm In the OFF continuous position the relay remains closed until the RESET button is pressed In the ON impulse position the relay remains closed for 20 seconds and then ...

Page 6: ...the voltage is correct Carefully follow the instructions and the connections according to Regulations in force keeping in mind that the signal cables should be laid separate from the power cables An automatic cut off switch appropriately identified as devicesectioning of the detector should be incorporated in the electrical system adequatelylocated and easily accessible BX180 Pre Alarm Main Alarm ...

Page 7: ... permitted An external power unit must always be used The BX180 gives a max current of 50mA Control unitpower supplyandconnection of one solenoid valve with sirens to 12VDC trough an alternative source and recharge battery C NC NO C NC NO C NC NO PH N 4 5 6 7 8 9 10 Fault 1 Threshold Solenoid valve NC Ph N 230 VAC C NC NO C NC NO C NC NO PH N 4 5 6 7 8 9 10 Fault 1 Threshold Alarm Solenoid valves ...

Page 8: ...rk well is connected to the BX180 Direct connection of 12VDC solenoid valves or sirens to the BX180 is not permitted An external power unit must always be used The BX180 gives a max current of 50mA Ph N C NC NO C NC NO C NC NO PH N 4 5 6 7 8 9 10 Fault 1 Threshold Alarm Solenoid valves Diode 1N 5406 12 V Powersupply 230 12V Ph N 230 VAC 230 VAC 3 2 1 Probe 1 1 2 3 4 5 R1 NC NA ...

Page 9: ... they should be positioned at different heights depending on the type of gas to be detected These heights are 30 cm from the lowest point of the floor in order to detect Heavy gases L P G etc 30 cm from the highest point of the ceiling in order to detect light gases Methane etc 160 cm from the lowest point of the floor in order to detect volatile gases CO etc It is important to note that the remot...

Page 10: ...orrectly connected If powered by the battery check that the 12Vdc power is correctly connected If the Fault LED lights up Check that the connecting cables from the BX180 to the probes are intact that the probes are properly powered and that the signal cable is correctly connected If the Over Load Probe LED lights up Check that the power polarity has not been inverted that no short circuit is prese...

Page 11: ...Page 11 NOTE ...

Page 12: ...ning shall be excluded from the warranty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the app...

Reviews: