BEINAT BX180 Manual Download Page 3

Page 3

Main Compatible Probes

MAINTENANCE

The  user  periodically  (every  6  months)  must  perform  a  check  of  the  operation  of  the

control  unit  by spraying a  suitable  test  gas  at  the  base  of  the  probes connected  until the

alarm  condition  is  reached.

•  At  least  once  a  year  make  a  more  accurate  check  by  a  specialist  technician.
                •  Disabling  the  detector  must  be  carried  out  by  qualified  personnel.

Installation  of  the  detector  does  not  exonerate.  From  the  observance  of  all  rules  regarding  the  characteristics,
installation and use of gas appliances. The ventilation of the premises and the discharge of the combustion products
prescribed by UNI norms as from ART. 3 LAW 1083/71 and the relevant provisions of law

.

SG500

Catalytic

IP30

Domestic  Use

CH4-LPG

0÷100% LEL      4÷20 mA

±5 %

NO

NO

SG544

Catalytic

IP44

Tertiary

CH4-LPG

0÷100% LEL       4÷20 mA

±5 %

NO

NO

SGM595

Catalytic

IP55

Tertiary

See  catalogue

0÷100% LEL       4÷20 mA

±5 %

Yes

NO

SGM595/A

Catalytic

IP66

Zone  2

See  catalogue

0÷100% LEL       4÷20 mA

±5 %

Yes

NO

SGM533

Catalytic

IP55

Tertiary

See  catalogue

0÷100% LEL       4÷20 mA

±5 %

Yes

Yes

SG800

Catalytic

IP66

Zone  2

See  catalogue

0÷100% LEL       4÷20 mA

±5 %

Yes

Yes

HCF100

SemiCondut

IP55

Tertiary

FREON

0÷300% ppm     4÷20 mA

±5 %

NO

Yes

SG895

Pellistor

ATEX

Zone  1

See  catalogue

0÷100% LEL       4÷20 mA

±5 %

Yes

NO

SG580

Catalytic

IP66

Zone  2

See  catalogue

0÷100% LEL       4÷20 mA

±5 %

Yes

NO

SGF100

Catalytic

IP64

Zone  2

Methane

0÷100% LEL       4÷20 mA

±5 %

Yes

Yes

SGF102

Catalytic

IP64

Zone  2

LPG

0÷100% LEL       4÷20 mA

±5 %

Yes

Yes

SGF104

Optical  Fluores

IP64

Zone  2

Oxygen

In  %

  4÷20 mA

±5 %

Yes

Yes

SGF106

SemiCondut

IP64

Zone  2

FREON

0÷300% ppm     4÷20 mA

±5 %

Yes

Yes

SGF108

Elettrochimica

IP64

Zone  2

H2S

0÷300% ppm     4÷20 mA

±5 %

Yes

Yes

SGF110

Electrochemical

IP64

Zone  2

C O

0÷300% ppm     4÷20 mA

±5 %

Yes

Yes

SGF112

Catalytic

IP64

Zone  2

Hydrogen

0÷100% LEL       4÷20 mA

±5 %

Yes

Yes

CO100r

Electrochemical IP55

Tertiary

C O

0÷300% ppm     4÷20 mA

±5 %

Yes

Yes

CO100Ar

Electrochemical IP66

Zone  2

C O

0÷300% ppm      4÷20 mA

±5 %

Yes

Yes

SG800

duct

Catalytic

IP66

Zone  2

CH4LPG

0÷100% LEL        4÷20 mA

±5 %

Yes

Yes

CO200

duct

Electrochemical IP66

Zone  2

C O

0÷300% ppm      4÷20 mA

±5 %

Yes

Yes

Application  in:

Domestic:  family  accommodation.  Local  boilers  up  to  70  kW-h
Tertiary  Areas:  Large  Rooms  Boilers,  Workshops,  Material  Deposits,  Industrial  Kitchens,  Large  Buildings,  Buildings.
Zone  2  -  Mixed  IP66  ATEX:  High  probability  of  escape,  high  risk  locations,  premises  for  which  applicable  regulations  apply.
Zone  1  -  Hazardous  Area,  High  Risk  Hazards,  Rooms  for  Which  Regulations,  Tanks,  Control  Valves  are  in  force.

Probe

Sensor          Degree     Suitable for

 Gas

  Range             Output          Precis.        Calibration  Relay

Protec.                           Detected        Working                                            Automatic

                Sensor

WARNING! Actions to be taken in case of alarm

Gas
1) P
ut out all free flames.
2) Close the main gas tap or the LPG cylinder tap.
3) Do not turn any lights on or off; do not turn on any electrical device or appliance.
4) Open windows and doors in order to increase ventilation.
If the alarm stops, its cause must be found and the relevant consequent measures taken.
If the alarm continues and the cause of gas presence cannot be found or removed, abandon the building and call
the emergency services when outside (fire department, distributors, etc.)

IMPORTANT:  The  operation  test  should  not  be  carried  out  with  the  gas  tap  as  this  does  not  guarantee  a  sufficient
concentration  to  activate  the  general  alarm.

Warning !!

If you have the following symptoms: vomiting, sleepiness, or else, go to the closest first aid station
and inform the operators that you could have been poisoned by Carbon Monoxide

or by an excess

or  deficiency  of  oxygen

Summary of Contents for BX180

Page 1: ...uilt according to European regulations to detect the presence of toxic and or explosive gas flexibly A microprocessor is used to create a complete surveillance and control system with maximum flexibility Thanks to this and its other features the BX180 is suitable for civil and industrial applications The BX180 control unit has two danger levels 1st LEVEL 1st Pre Alarm This was set at 13 of L E L f...

Page 2: ...ation can damage the appliance Cleaning Never clean the device with chemical products If necessary wash with a moist cloth Technical Specifications Page 2 Precautions Mains Power 110 230VAC 50 60Hz 10 Secondary Power Through Battery max 2 2 Ah 12 7 V 10 Battery Charger max 2 2 Ah By means of a microprocessor PowerDemand 4 W max 230V Power Demand 3 W max 12 V Relay Contact Range 10A 250V Pre Alarm ...

Page 3: ...SGF110 Electrochemical IP64 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SGF112 Catalytic IP64 Zone 2 Hydrogen 0 100 LEL 4 20 mA 5 Yes Yes CO100r Electrochemical IP55 Tertiary C O 0 300 ppm 4 20 mA 5 Yes Yes CO100Ar Electrochemical IP66 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SG800duct Catalytic IP66 Zone 2 CH4LPG 0 100 LEL 4 20 mA 5 Yes Yes CO200duct Electrochemical IP66 Zone 2 C O 0 300 ppm 4 20 mA 5 Y...

Page 4: ...e check the battery and the connection cables OVER LOAD BATTERY LED battery overload If this led turns on it means the battery is not connected properly or it has an anomalous voltage absorption Please check the battery and the connection cables 5 RESET BUTTON This button is pressed to reset all memories 6 TEST BUTTON Pressing and holding down this button you can obtain a gas leakage simulation Th...

Page 5: ...osition the intrinsic safety function is enabled In the OFF position the intrinsic safety function is disabled The relay is energized only when the BX180 goes into the mainl alarm Switch 2 Working mode of the relay and the main alarm In the OFF continuous position the relay remains closed until the RESET button is pressed In the ON impulse position the relay remains closed for 20 seconds and then ...

Page 6: ...the voltage is correct Carefully follow the instructions and the connections according to Regulations in force keeping in mind that the signal cables should be laid separate from the power cables An automatic cut off switch appropriately identified as devicesectioning of the detector should be incorporated in the electrical system adequatelylocated and easily accessible BX180 Pre Alarm Main Alarm ...

Page 7: ... permitted An external power unit must always be used The BX180 gives a max current of 50mA Control unitpower supplyandconnection of one solenoid valve with sirens to 12VDC trough an alternative source and recharge battery C NC NO C NC NO C NC NO PH N 4 5 6 7 8 9 10 Fault 1 Threshold Solenoid valve NC Ph N 230 VAC C NC NO C NC NO C NC NO PH N 4 5 6 7 8 9 10 Fault 1 Threshold Alarm Solenoid valves ...

Page 8: ...rk well is connected to the BX180 Direct connection of 12VDC solenoid valves or sirens to the BX180 is not permitted An external power unit must always be used The BX180 gives a max current of 50mA Ph N C NC NO C NC NO C NC NO PH N 4 5 6 7 8 9 10 Fault 1 Threshold Alarm Solenoid valves Diode 1N 5406 12 V Powersupply 230 12V Ph N 230 VAC 230 VAC 3 2 1 Probe 1 1 2 3 4 5 R1 NC NA ...

Page 9: ... they should be positioned at different heights depending on the type of gas to be detected These heights are 30 cm from the lowest point of the floor in order to detect Heavy gases L P G etc 30 cm from the highest point of the ceiling in order to detect light gases Methane etc 160 cm from the lowest point of the floor in order to detect volatile gases CO etc It is important to note that the remot...

Page 10: ...orrectly connected If powered by the battery check that the 12Vdc power is correctly connected If the Fault LED lights up Check that the connecting cables from the BX180 to the probes are intact that the probes are properly powered and that the signal cable is correctly connected If the Over Load Probe LED lights up Check that the power polarity has not been inverted that no short circuit is prese...

Page 11: ...Page 11 NOTE ...

Page 12: ...ning shall be excluded from the warranty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the app...