Important:  Assembly  /  maintenance  of  the  appliance  must  be  carried  out  by  qualified  personnel  and  in
accordance  with applicable laws and regulations.
The  manufacturer  assumes  no  responsibility  for  the  use  of  products  that  have  to  comply  with  particular
environmental and / or installation standards.

Important note
Before connecting the equipment, it is recommended that you read the instruction manual carefully and keep
it for future reference. It is also recommended to perform the electrical connections correctly as per enclosed
drawings, observing  the instructions  and  the Standards.
N.B. Refer to the documentation in all cases where the symbol is on the side

Channel:  Beinat  gas  solutions

Electric connections also available on

CONFORMITY

Installation
and user guide

INSTALL  IN  SAFE
AREA,  NO 

 ATEX

EN 50194

EN 45544-1-3

EN 50270

EN 61010-1

Compliant  EN 60079-29-1

Installation  EN 60079-29-2

Reports issued by  TUV Italia

Through the connection of  remote sensor, the BX180 control unit has been designed and built according to European
regulations to detect the presence of

 

toxic and/or explosive gas flexibly.

A microprocessor is used to create a complete surveillance and control system with maximum flexibility. Thanks to this
and its other features, the BX180 is suitable for civil and industrial applications.

The BX180 control unit has two danger levels:
1

st

 LEVEL, 1

st

 Pre-Alarm. This was set at 13 % of L.E.L. for all sensors.

2

nd

 LEVEL, Main Alarm. This was set at 20% of L.E.L.

Other technical features make this control unit extremely versatile and reliable; for example, by using a series of micro-
switches it is possible to:
Select or disable the probe when not installed or faulty;
Select the type of gas to be detected (toxic or explosive);
Choose the relay functioning mode (pulsed or continuous);
Choose the main alarm relay shut-down time.

A TEST button checks the efficiency of both the unit and connected probe to ensure total control of  the BX180.
Thanks to the Omega-type format both small and large systems can be built by exploiting the modularity of the DIN
rail in the previously set electrical panels.
In addition to the alarm signal light, it is fitted with an internal buzzer.

Control Unit 1 Conventional sensor  BX180

                                                                  Rev. 10

Summary of Contents for BX180

Page 1: ...uilt according to European regulations to detect the presence of toxic and or explosive gas flexibly A microprocessor is used to create a complete surveillance and control system with maximum flexibility Thanks to this and its other features the BX180 is suitable for civil and industrial applications The BX180 control unit has two danger levels 1st LEVEL 1st Pre Alarm This was set at 13 of L E L f...

Page 2: ...ation can damage the appliance Cleaning Never clean the device with chemical products If necessary wash with a moist cloth Technical Specifications Page 2 Precautions Mains Power 110 230VAC 50 60Hz 10 Secondary Power Through Battery max 2 2 Ah 12 7 V 10 Battery Charger max 2 2 Ah By means of a microprocessor PowerDemand 4 W max 230V Power Demand 3 W max 12 V Relay Contact Range 10A 250V Pre Alarm ...

Page 3: ...SGF110 Electrochemical IP64 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SGF112 Catalytic IP64 Zone 2 Hydrogen 0 100 LEL 4 20 mA 5 Yes Yes CO100r Electrochemical IP55 Tertiary C O 0 300 ppm 4 20 mA 5 Yes Yes CO100Ar Electrochemical IP66 Zone 2 C O 0 300 ppm 4 20 mA 5 Yes Yes SG800duct Catalytic IP66 Zone 2 CH4LPG 0 100 LEL 4 20 mA 5 Yes Yes CO200duct Electrochemical IP66 Zone 2 C O 0 300 ppm 4 20 mA 5 Y...

Page 4: ...e check the battery and the connection cables OVER LOAD BATTERY LED battery overload If this led turns on it means the battery is not connected properly or it has an anomalous voltage absorption Please check the battery and the connection cables 5 RESET BUTTON This button is pressed to reset all memories 6 TEST BUTTON Pressing and holding down this button you can obtain a gas leakage simulation Th...

Page 5: ...osition the intrinsic safety function is enabled In the OFF position the intrinsic safety function is disabled The relay is energized only when the BX180 goes into the mainl alarm Switch 2 Working mode of the relay and the main alarm In the OFF continuous position the relay remains closed until the RESET button is pressed In the ON impulse position the relay remains closed for 20 seconds and then ...

Page 6: ...the voltage is correct Carefully follow the instructions and the connections according to Regulations in force keeping in mind that the signal cables should be laid separate from the power cables An automatic cut off switch appropriately identified as devicesectioning of the detector should be incorporated in the electrical system adequatelylocated and easily accessible BX180 Pre Alarm Main Alarm ...

Page 7: ... permitted An external power unit must always be used The BX180 gives a max current of 50mA Control unitpower supplyandconnection of one solenoid valve with sirens to 12VDC trough an alternative source and recharge battery C NC NO C NC NO C NC NO PH N 4 5 6 7 8 9 10 Fault 1 Threshold Solenoid valve NC Ph N 230 VAC C NC NO C NC NO C NC NO PH N 4 5 6 7 8 9 10 Fault 1 Threshold Alarm Solenoid valves ...

Page 8: ...rk well is connected to the BX180 Direct connection of 12VDC solenoid valves or sirens to the BX180 is not permitted An external power unit must always be used The BX180 gives a max current of 50mA Ph N C NC NO C NC NO C NC NO PH N 4 5 6 7 8 9 10 Fault 1 Threshold Alarm Solenoid valves Diode 1N 5406 12 V Powersupply 230 12V Ph N 230 VAC 230 VAC 3 2 1 Probe 1 1 2 3 4 5 R1 NC NA ...

Page 9: ... they should be positioned at different heights depending on the type of gas to be detected These heights are 30 cm from the lowest point of the floor in order to detect Heavy gases L P G etc 30 cm from the highest point of the ceiling in order to detect light gases Methane etc 160 cm from the lowest point of the floor in order to detect volatile gases CO etc It is important to note that the remot...

Page 10: ...orrectly connected If powered by the battery check that the 12Vdc power is correctly connected If the Fault LED lights up Check that the connecting cables from the BX180 to the probes are intact that the probes are properly powered and that the signal cable is correctly connected If the Over Load Probe LED lights up Check that the power polarity has not been inverted that no short circuit is prese...

Page 11: ...Page 11 NOTE ...

Page 12: ...ning shall be excluded from the warranty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the app...