Additional Installation Tips

6.5 Safety

Most of the operator panels are fed with 24 V DC.

4

1

2

4

3

4

Power supply
230 V AC to 24 V DC

Power supply
230 V AC to 24 V DC

Power supply
230 V AC to 24 V DC

Operator panel

Operator panel

Operator panel

Distance?

Small controller with expansion unit

+24 V

+24 V

+24 V

0 V

0 V

0 V

230 V AC

COM1

COM100

Ch0

Ch1

Ch100

Ch101

5355

If a power supply that meets safety standards is used and only feeds the operator
panel, there is no problem. See 1 in drawing above.
However, if a 24 V unit that also feeds other units is used, there is reason to be
cautious, see 2 in drawing above. The operator panel does not have insulation
that meets safety requirements in the event of a potential short circuit between
230 V AC and 24 V DC. It is assumed that the 24 V feed is secure, for example,
SELV according to EN 60950 (protection against electric shock) and UL 950.

Example:

Here is an example that explains why a secure 24 V DC feed can be ruined by mixing
24 V relay contacts with 230 V AC relay contacts in a smaller controller. Check that the
clearances and creepage distances between 24 V DC and 230 V AC fulfill EN 60950 or
UL 950. If not, input a separate 24 V unit into the operator panel.

If there is a substantial distance between the relay contacts for 24 V DC and
230 V AC, it is OK to use the same 24 V devices for all feeds. See 3 in drawing
above.
Connect 0 V on the 24 V feed to the ground, see 4 in drawing above. This offers
three advantages:

Safety is increased. The 24 V feed will not be live in the event of a faulty
connection or short circuit between 0 V (24 V) and 230 V phase.

Transients on the 24 V feed are connected to the ground.

No risk that the 24 V feed is at a high level in relationship to the ground. This
is not unusual since there is high static electricity.

Beijer Electronics, MAEN017F

25

Summary of Contents for iX T10A

Page 1: ...iX T10A Installation Manual English MAEN017F 2013 09...

Page 2: ...all its group companies assumes no responsibility for any errors that may appear in this document Read the entire installation manual prior to installing and using this equipment Only quali ed personn...

Page 3: ...rals 11 3 TechnicalData 12 4 ChemicalResistance 14 4 1 MetalCasing 14 4 2 Touch Screen and Overlay 15 4 2 1 Auto ex EBA 180L 15 4 2 2 Touch Screen Surface 16 4 2 3 Auto ex EBA 180L 16 5 Operator Panel...

Page 4: ...liquidto congeal become isotopic The LCDdisplay liquidcontainsa powerful irritant Incase of skincontact wash immediately with plenty ofwater In case of eye contact holdthe eye open ush with plenty of...

Page 5: ...must onlybe changedin an areaknown tobe non hazardous Replace the battery with aBR 2032 battery Use of another type ofbattery maypresent a risk of re orexplosion Warning Battery may explode if mistre...

Page 6: ...ergency stopand othersafety functions may notbe controlled from the operator panel Do not use toomuch force or sharp objects when touchingthe keys touchscreen etc 1 5 Service and Maintenance Onlyquali...

Page 7: ...uch screen contains airand in rare cases appearance ofbubbles can arise This is purely cosmeticanddoes notaffect anyfunctionalityof the panel The appearance can occurundercertain environmental conditi...

Page 8: ...ce Requirements Maximum installation plate thickness 8 mm Space requirements in millimeterswhen installingthe operatorpanel 100 228 50 100 100 280 50 Note The dimensions on the drawing are not proport...

Page 9: ...r lettingit fallmay cause damage 2 Use the cut out dimensions thatare included on the outline drawing found in section Operator PanelDrawings and in theTechnical Data table to cut acorrectopeningin th...

Page 10: ...cables from signal and supply cables 24V DC RS232 RS422 RS485 24V DC A D Controller Power B Ethernet C Connect cable A Connect cable B usingan M5 screwand agroundingconductor asshort as possible with...

Page 11: ...rator panelto the controller please refer to the help le for the driverin question 2 2 2 Other Connections and Peripherals Cables peripheral equipment and accessories must be suitable forthe applicati...

Page 12: ...RS232 RTS CTS chassis mounted female with standard locking screws 4 40 UNC Serial port for COM3 RS232 and COM4 RS422 RS485 9 pin D sub contact with RS232 RTS CTS chassis mounted female with standard...

Page 13: ...backlight 640 480 pixels 64 k colors Active area of display W H 211 2 158 4 mm Operating temperature 10 C 60 C Storage temperature 20 C 70 C Relative humidity 5 85 non condensed Approvals and certifi...

Page 14: ...ollowing chemicals at room temperature Butanol Nitric acid 3 Hydrochloric acid 5 Nitric acid 10 Isopropyl alcohol Phosphoric acid 43 Na hypochlorite 10 Turpentine Note If exposure to any of the above...

Page 15: ...ption 1 SBP 60 95 1 Ariel powderin solution 1 Hydrochloricacid 36 Sulfuric acid 10 Bleach 1 Linseed oil Tomato ketchup Castoroil Methanol Trichloroacetic acid 50 Causticsoda 40 1 Nitric acid 10 White...

Page 16: ...oflex EBA 180L It is recommended to use the Auto ex EBA 180Ltouch displayprotection lm that can be ordered from Beijer Electronics Solvent Resistance Auto ex EBA 180L withstands exposure to the same c...

Page 17: ...female Pin COM1 COM2 COM3 COM4 1 RS422 Tx RS485 Tx Rx RS422 Tx RS485 Tx Rx 2 RS232 RxD RS232 RxD 3 RS232 TxD RS232 TxD 4 RS422 Rx RS422 Rx 5 GND GND GND GND 6 RS422 Tx RS485 Tx Rx RS422 Tx RS485 Tx Rx...

Page 18: ...Operator PanelDrawings Note Only iX T10A panels with part number 630000301 are equipped with terminated COM ports Beijer Electronics MAEN017F 18...

Page 19: ...SD memory card slot Expansion port COM3 RS232 COM4 RS422 RS485 COM1 RS232 COM2 RS422 RS485 Ethernet 24 V DC 209 9 9 7 44 228 max 8 mm 262 9 9 280 Note A Step CAD file is available on the web site www...

Page 20: ...wire between the operator panel s quick connect plinth and the panel s chassis see 2 in drawing above 2 Connect a6 mm2 or 4 mm2 wire orgroundingbraid betweenthe operator panel s chassis and the closes...

Page 21: ...RJ45 RJ45 RJ45 Industrial Ethernet Operator panel Operator panel Operator panel Operator panel Shielded Short and unshielded 0 1 F 250 V 1 1 3 3 8 8 2 2 In some industrialunits forEthernet the RJ45 c...

Page 22: ...istobreak the shield see 3 in drawing above A more elegant methodistoexpand the shielded Ethernet cablingwith a piece of unshielded Ethernetcable see 4 in drawingabove The shield canbe grounded via an...

Page 23: ...s to connect the otherend of the shield to the ground via a 0 1 F 250 V plastic capacitor Both ends are then connected tothe ground in terms ofHF but only connected to the ground at one end in terms o...

Page 24: ...to heat The lifespan of an electrolytic capacitoris cut in halfwith an 8 10 C increase in temperature A 15 20 C temperature increase resultsin a quarter of the lifespanetc Rittal has a goodprogram for...

Page 25: ...ccording to EN 60950 protection against electric shock andUL 950 Example Here is an example that explains why a secure 24 V DC feed can be ruined by mixing 24 V relay contacts with 230 V AC relay cont...

Page 26: ...a USB memory stick keyboard or similar device is plugged in If anumberofunitsare connectedthat have a0 Vand a groundconnection and these are connected to various groundingpoints there is a substantial...

Page 27: ...hield mustbe grounded at one end The other end is usuallygrounded but with longerdistances or whenthere is adifference in the ground potential the shield should be connected tothe ground via 0 1 F 250...

Page 28: ...Head office Beijer Electronics AB Box 426 201 24 Malm Sweden www beijerelectronics com 46 40 358600...

Reviews: