10.3.2. 200 – 240 Volt (+/- 10%), 3 Phase Input, 3 Phase Output
Frame
Size
Power
Rating
Input
Current
Fuse or MCB
(Type B)
Maximum Cable
Size
Rated
Output
Current
Maximum
Motor Cable
Length
Recommended
Brake
Resistance
kW
HP
A
Non UL
UL
mm
AWG/kcmil
A
m
ft
Ω
2
0.75
1
5.7
10
10
8
8
4.3
100
330
100
2
1.5
2
10.5
16
15
8
8
7
100
330
50
2
2.2
3
13.2
16
17.5
8
8
10.5
100
330
35
3
4
5
20.9
32
30
8
8
18
100
330
20
3
5.5
7.5
26.4
32
35
8
8
24
100
330
20
4
7.5
10
33.3
40
40
16
5
30
100
330
22
4
11
15
50.1
63
70
16
5
46
100
330
22
5
15
20
63.9
80
80
35
2
61
100
330
12
5
18.5
25
74.0
100
90
35
2
72
100
330
12
6
22
30
99.1
125
125
150
300MCM
90
100
330
6
6A
22
30
80.6
100
100
150
300MCM
90
100
330
6
6
30
40
121.0
160
150
150
300MCM
110
100
330
6
6B
30
40
97.8
125
125
150
300MCM
110
100
330
6
6
37
50
159.7
200
200
150
300MCM
150
100
330
6
6B
37
50
139.7
200
175
150
300MCM
150
100
330
6
6
45
50
187.5
250
225
150
300MCM
180
100
330
6
6B
45
60
163.4
200
200
150
300MCM
180
100
330
6
6B
55
75
185.9
250
225
150
300MCM
202
100
330
6
7
55
50
206.5
250
250
150
300MCM
202
100
330
6
7
75
50
246.3
315
300
150
300MCM
248
100
330
6
10
Technical Data