2

Adapter Harness
Remove and discard.

Old Style ECM Inducer

New Style ECM Inducer

A13034

Fig. 1 -- ECM Inducers

DESCRIPTION AND USAGE

Use this inducer assembly kit to replace a failed inducer assembly.

The assembly cannot be disassembled to remove or repair individual

components. The kit contains the following items shown in

Table 1

.

NOTE

:

Inducer assembly consists of motor, wheel, inducer

housing, inlet gasket, inlet choke plate and condensate drain
gasket. It will be necessary to reuse some components from the old
inducer assembly.

UNIT DAMAGE HAZARD

Failure to follow this caution may result in unit damage.
Using the incorrect inducer motor assembly could result in no

pressure switch operation, poor ignition, poor combustion,

erratic burner operation/burner pulsations, flame roll--out or

noise.

CAUTION

!

Table 1 – Kit Contents

NAME

QUANTITY

Inducer Assembly

1

Installation Instructions

1

Inlet Choke Plate (PSC only)

1 -- 2

Inducer Outlet Restrictor (40,000 input only)

1

Two--stage to Single--stage Adapter Harness (PSC

only except 140,000 input)

1

1/2--in.. # 8 Hex Head Screws 1 /2--in.

5

3/8--in. # 8 Hex Head Screws

2

Table 2 – Model Numbers

SINGLE STAGE MODELS

INPUT

KIT NUMBER

26,000

337938--776--CBP*

40,000
60,000

337938--774--CBP*

80,000

100,000

337938--775--CBP*

120,000
140,000

337938--763--CBP*

TWO STAGE MODELS

INPUT

KIT NUMBER

40,000

337938--776--CBP*

60,000

337938--774--CBP*

80,000

100,000

337938--775--CBP*

MODULATING MODELS

INPUT

KIT NUMBER

60,000

337938--781--CBP*

80,000

100,000
120,000

SINGLE STAGE EXPORT MODELS (220 VOLT, 50 HZ ONLY)

INPUT

KIT NUMBER

100,000

337938--782--CBP*

120,000
140,000

*All Brands

INSTALLATION

Unit Shut Down

ELECTRICAL SHOCK AND FIRE HAZARD

Failure to follow this warning could result in personal injury,

death, and/or property damage.
Turn off the gas and electrical supplies to the furnace and

install lockout tag before performing any maintenance or

service. Follow the operating instructions on the label

attached to the furnace.

!

WARNING

1. Set room thermostat to lowest setting or “OFF”.
2. Disconnect power at external disconnect, fuse or circuit

breaker.

3. Turn off gas at external shut-off or gas meter.
4. Remove outer doors and set aside.
5. Turn electric switch on gas valve to OFF.

Vent Pipe Removal

NOTE

: The vent pipe may be connected to the furnace at the

rubber vent pipe support. Before cutting the vent pipe, loosen the
clamps around the vent pipe coupling and move the vent pipe

337938

Summary of Contents for 337938-763-CBP

Page 1: ...equipment If you do not possess these do not attempt to perform any maintenance on this equipment other than those procedures recommended in the Owner s Manual WARNING FIRE EXPLOSION ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD Failure to follow instructions could result in personal injury death or property damage Improper installation adjustment alteration service maintenance or use can ...

Page 2: ...ews 2 Table 2 Model Numbers SINGLE STAGE MODELS INPUT KIT NUMBER 26 000 337938 776 CBP 40 000 60 000 337938 774 CBP 80 000 100 000 337938 775 CBP 120 000 140 000 337938 763 CBP TWO STAGE MODELS INPUT KIT NUMBER 40 000 337938 776 CBP 60 000 337938 774 CBP 80 000 100 000 337938 775 CBP MODULATING MODELS INPUT KIT NUMBER 60 000 337938 781 CBP 80 000 100 000 120 000 SINGLE STAGE EXPORT MODELS 220 VOLT...

Page 3: ...rews that attach the pressure switch assembly to the inducer 4 Remove the back pressure switch tube that connects to the inducer assembly PSC only 5 Remove the wires from the back pressure switch Note the location of the wires for reassembly PSC only 6 Set the pressure switches aside 7 If the relief tube for the condensate trap is routed across the inducer assembly remove the tube from the port on...

Page 4: ... hand Do not use a screw gun or over tighten the mounting screws 7 Connect the inducer leads from the main wiring harness to the inducer motor harness On Variable Speed furnaces with old style ECM inducers verify adapter harness has been removed before connecting harness to new ECM motor See Fig 3 Otherwise connect furnace wiring harness directly to motor On 2 stage furnaces connect furnace wiring...

Page 5: ...me nue por vérifier la présence des fuites de gaz Pour la vérification de tous les joints utiliser plutôt une solution savonneuse commerciale fabriquée spécifiquement pur la détection des fuites de gaz Un incendie ou une explosion peut entraîner des dommages matériels des blessures ou la mort WARNING 4 Check for gas leaks with a commercially available soap solution made specifically for the detect...

Page 6: ...out is complete set thermostat below room temperature 17 Verify that burner shuts down and blower completes selected off delay time 18 Verify furnace operates properly and set thermostat to desired room temperature 19 Re install outer door Copyright 2016 CAC BDP D 7310 W Morris St D Indianapolis IN 46231 Edition Date 08 16 Manufacturer reserves the right to change at any time specifications and de...

Reviews: