Chassis GND
LED Board
AC ONLY SIGN
Chassis GND
GREEN Ground
BLACK 120VAC
RED 120-277VAC or ORANGE 200-277VAC
WHITE Neutral
LED Board
AC & UNIVERSAL DC SIGN
YELLOW Positive 6 to 24VDC
PURPLE Negative
Emergency Supply
FROM Battery Pack
SELF-POWERED SIGN
Chassis GND
24 hours
Unswitched Supply
GREEN Ground
BLACK 120-277VAC
WHITE Neutral
LED Board
DUAL UNIVERSAL AC SIGN
From Generator OR
Emergency Supply
BROWN 120 to 277VAC
BLUE Neutral
NOTE: Cap unused AC Wire!
NOTE: Cap unused AC Wire!
24 hours
Unswitched Supply
GREEN Ground
BLACK 120VAC
RED 120-277VAC or ORANGE 200-277VAC
WHITE Neutral
24 hours
Unswitched Supply
Chassis GND
LED Board
NOTE: Cap unused AC Wire!
GREEN Ground
BLACK 120VAC
RED 277VAC or ORANGE 120-277VAC
WHITE Neutral
24 hours
Unswitched Supply
Ni-Cd
Battery
CEILING/END MOUNT INSTALLATION
WALL MOUNT INSTALLATION:
1. Remove torx screws (9) to release clear cover (1). There are 4 O-rings (10) inserted to the clear cover screw holes.
Release the stencil (2) from the clear cover (1). Knockout to remove the chevron as necessary from the stencil.
Peel off backing paper from the tape on the back of the stencil and carefully position and stick the colored fibre to the
stencil.
2. To install canopy kit, knockout on the top (for ceiling mount) or the knockout on the side (for end mount). Position
canopy gasket and the canopy (14). Install the cap screws and the washers. Attach canopy nuts and then tighten.
Install the liquid tight bushing (12), feed the lead wired through the bushing and tighten to complete the liquid tight
seal. Install the canopy mounting base (15) to the octagon box (11) (not supplied). Connect wires per diagram
provided. Caution! Failure to insulate unused wire may result in a shock hazard or unsafe condition as well as
equipment failure. The mounting base can be rotated for the desired mounting angle. Install the canopy (14) to the
mounting base (15) with the supplied screws.
3. Note: When installing the cover, be sure to align the light pipe (5) and LED indicator.
4. Apply power.
SELF-POWERED:
1. For models FTZ-SP, plug the battery into the circuit board per (wiring diagram) self-powered sign.
MAINTENANCE
1. Clean face(s) on a regular basis.
NOTE: The servicing of any parts should be performed by qualified service personnel only. The use of replacement
parts not furnished by Beghelli Canada Inc., may cause equipment failure and will void the warranty.
WIRING DIAGRAM
1. Remove torx screws (9) to release clear cover (1). There are 4 O-rings (10) inserted to the clear cover screw holes.
Release the stencil (2) from the clear face cover (1). Knockout to remove the chevron as necessary from the stencil.
Peel off backing paper from the tape on the back of the stencil (2) and carefully position and stick the colored fibre to
the stencil.
2. Remove the back plate (16) knockouts using applicable knockout holes. Install the liquid tight bushing into the large
center knockout with the lock nut (12). Feed the lead wires through the bushing, tighten to complete the liquid tight
seal and install the wall gasket (18) then secure the back plate and housing to the wall. Connect wire per wiring
diagram provided.
Caution! Failure to insulate unused wire may result in a shock hazard or unsafe condition as
well as equipment failure.
3. Replace faceplate, clear cover and torx screws.
Note: When installing the cover, be sure to align the light pipe (5) and
LED indicator.
4. Apply power.
926000318
02/10/14
BEGHELLI USA 3250 CORPORATE WAY - MIRAMAR, FL 33025 • P: 800.726.4316 • P: 954.442.6600 • F: 954.442.6677
I cahnged the contact info, the technical info seems pretty universal is there anything else you see that I need to change?