LED Floodlight FMV Series
25L Industrial LED Floodlight
Installation & Maintenance Information
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
1711
ApplicAtion
FMV LED Floodlights construction is designed for use indoors and outdoors in
marine and wet locations, where moisture, dirt, corrosion, vibration and rough
usage may be present.
• UL1598 Luminaires, UL1598A Marine, UL8750, UL844 Hazardous
(Classified), CSA C22.2 No. 137
• cUL
• Class I, Division 2, Groups A,B,C,D
• Class II, Division 1, Groups E,F,G
• Class III
• Wet Locations, NEMA 4X
• IP66
FMV LED Floodlights are supplied for use with a choice of voltages:
• 100VAC – 277VAC, 50/60Hz and 127VDC – 250VDC
• 277VAC - 480VAC, 50/60Hz
Figure 2 - Wiring Diagram
to avoid the risk of fire, explosion, or electric shock,
this product
should be installed, inspected, and maintained by a qualified electrician
only, in accordance with all applicable electrical codes.
WARninG
to avoid electric shock:
Be certain electrical power is OFF before and during installation and
maintenance. Floodlight must be supplied by wiring system suitable for
Class I, Division 2 per NEC with an equipment grounding conductor.
to avoid burning hands:
Make sure lens and lamp are cool when performing maintenance.
WARninG
to avoid potentially unsafe operating conditions:
Make sure the supply voltage is within the floodlight voltage range
stated on the nameplate.
Do not operate in ambient temperatures above those indicated on the
floodlight nameplate.
Use only replacement parts from Crouse-Hinds.
Ensure supply cable and cable gland meet product ratings and conforms
with building and electrical codes.
Use proper supply wiring as specified on the floodlight nameplate.
All gasket seals must be clean.
Before opening, electrical power to the floodlight must be turned off.
Keep tightly closed when in operation.
Do not position the floodlight beyond the aiming range limits.
Do not exceed the maximum allowable current draw of 15 Amps when
daisy chaining floodlights.
WARninG
IF 1711 • 10/14
Copyright © 2014, Eaton’s Crouse-Hinds Business Page 1
instAllAtion
Mounting
Yoke Mount - post Mount Using Floodlight Yoke only
1. Select a durable, corrosion resistant mounting surface capable of
supporting the fixture’s 50 lb (22.7 kg) weight and cantilevered mass (as
applicable).
2. Using the floodlight yoke as a template, mark and drill desired location on
mounting surface.
3. Secure floodlight yoke to mounting surface by applying proper torque
to corrosion resistant 1/2 in bolts or lag screws accompanied by lock
washers.
4. Ensure that the safety chain is securely fastened between the yoke
bracket and back cover.
WiRinG
Wiring the Floodlight
1. Open back cover by loosening eight (8) 1/4 -20 x .625” stainless steel
cover screws. All components in the fixture are prewired so only line in,
neutral, and ground need to be connected in the fixture to the terminals
per the wiring diagrams using methods that comply with all applicable
codes. Terminate the equipment grounding conductor (green) first, the
common (white) next, and finally, the line voltage (black) last. Secure all
electrical connections. For DC voltage applications connect the positive
(+) lead to the white wire and negative (-) lead to the black wire.
DRIVER
INPUT
OUTPUT
LINE IN (BLK)
NEUTRAL (WHT)
V+ (RED)
V- (BLK)
+
-
DRIVER
INPUT
OUTPUT
LINE IN (BLK)
NEUTRAL (WHT)
V+ (RED)
V- (BLK)
LED CIRCUIT BOARD
+
-
NEUTRAL (WHT)
LINE IN (BLK)
GROUND (GREEN)
-
+
LED CIRCUIT BOARD
LED CIRCUIT BOARD
+
-
LED CIRCUIT BOARD
Figure 1
Entries shall be closed with
components that meet
enclosure ratings.