![Bedford B503DSL Series Instruction Manual Download Page 25](http://html.mh-extra.com/html/bedford/b503dsl-series/b503dsl-series_instruction-manual_2719965025.webp)
21
Function
code
Name
Description
Factory
setting
F0.16
Reserve
F0.17
Restore
parameter
0: No action
1: Restore factory setting
2: Clear fault records
0
F0.18
Maximum
output
frequency
F0.02~600.00Hz
50.00Hz
F0.19
Third latest
fault type
0: No fault
1: IGBT Ph-U fault (OUT1)
2: IGBT Ph-V fault (OUT2)
3: IGBT Ph-W fault (OUT3)
4: Over-current (OC1~OC3)
5: Over-voltage (OV1~OV3)
6: DC bus under-voltage (P.OFF)
7: Motor overload (OL1~OL2)
8: Output phase failure (SPO)
9: Overheat (OH1~OH2)
10: Current detection fault (ITE)
11: EEPROM fault (EEP)
F0.20
Second latest
fault type
F0.21
Current fault
type
F0.22
Output
frequency at
current fault
0.0Hz
F0.23
Output current
an current
fault
0.0A
F0.24
DC bus
voltage at
current fault
0.0V
F0.25
Reserve
*Attention:
The S1, S2 and COM terminal should be short connect if you do not use S1-S4 terminals,
otherwise the VFD can not work.
6 INITIAL DEBUGGING
In order to ensure photovoltaic water supply system can work in efficiency, reliability and
steady, the parameters setting of controller and debugging for the first time were performed by
the professional electrical engineering technicist according to the following steps. (you’d
better choose a sunny day with strong sunlight to debugging.)