20
Function
code
Name
Description
Factory
setting
F0.03
Restart delay
time
Restart delay time after power on. Please refer to description
of F0.13 when using
10.0s
F0.04
Output
threshold
voltage after
start
Only DC bus voltage
is greater than the
value of F0.04 to give
rise output.
100~900V(OUTPUT 220V series)
200V
100~900V(OUTPUT 380Vseries)
400V
F0.05
Maximum
power point’ s
voltage
PV array voltage correspond to maximum power point
Depend on
PV array
F0.06
The maximum
power output
The maximum power output of PV array (0.1~900.0kW)
Depend on
PV array
F0.07
Motor-pump
rated power
0.1~900.0kW
Depend on
model
F0.08
Motor-pump
rated
frequency
10Hz~F0.01
Depend on
model
F0.09
Motor-pump
rated voltage
0~460V
Depend on
model
F0.10
Motor-pump
rated current
0.1~1000.0A
Depend on
model
F0.11
Reserve
F0.12
NO/NC input
statue
selection of
Water-level
detection
terminal
BIT0: Define the NC or NO of S1
BIT1: Define the NC or NO of S2
BIT2: Define the NC or NO of S3
BIT3: Define the NC or NO of S4
0: NC Action; 1: NO Action.
(
0~F
)
NC: Si connected to COM is valid,disconnected is invalid
NO: Si disconnected from COM is valid, connected is
invalid
E.g.: if NC is valid for S1 and S2 and NO is valid for S3 and
S4, this parameter F0.012 need to be set as follow:
The statues( S4~S1) can be represented as a binary
“1100” ( “C”in hex notation ), that is to say, F0.12
should be set as “C”
00
F0.13
Power on
restart
selection
0: invalid
1: valid
Pleased refer to the parameter F0.00 to select this function.
It is meaningful only to F0.00=0
1
F0.14
Carrier
frequency
1.0~15.0KHz
Depend on
mode
F0.15
Acceleration
time
0.1~3600.0s
Depend on
mode