A–24
M-6200A Instruction Book
Figure A-8 Configuration Screens (page 3 of 8)
Configuration/Programmable Alarm
Prog Alarm Function
–<0001100011100110
Provides alarm for one or more of the following user-selected
conditions: Communication Block, Block Raise (TAP) Limit
exceeded, Block Lower (TAP) Limit exceeded, Block Raise
Voltage Limit exceeded, Block Lower Voltage Limit exceeded,
Voltage Reduction (any step) invoked, Reverse Power Flow
condition detected, Line Limit Current exceeded, LDC/LDZ,
Abnormal Tap Position, Backup Power Fail, Self Test, Max VAr
Bias Duration Lead, Max VAr Bias Duration Lag in effect, Run
Through Neutral Fail, Operation Count Signal Limit exceeded,
Leading VAr limit exceeded, Lagging VAr limit exceeded,
Leading Power Factor limit exceeded and Lagging Power
Factor limit exceeded. See
Figure 4-44
.
Pred. Maint. Alarm
0
When the resettable operations counter matches the Pred.
Maint. Alarm Setting, the control will display a message that the
Pred. Maint. Alarm Setting has been exceeded.
Clear Sealin Alarm
Ready Press ENTER
Allows the user to clear the Motor Seal-In Failure Block and
Alarm.
Clr Low Current Blk
Ready Press ENTER
Allows the user to clear the Low Current Block Alarm and Block.
Alarm and Block occurs when the control determines that load
current is less than 4 mA and Tap Delta Voltage is less than
0.4 VAC.
Clr Run T. Neu Alarm
Ready Press ENTER
Allows the user to clear the Run Through Neutral Alarm.
Clr Abnormal Tap Alarm
Ready Press ENTER
Allows the user to clear the Abnormal Tap Alarm.
Configuration/System Clock
Set Date and Time
03/26/07 15:41:29
Displays and allows resetting of the time and date. Press
EOT
to set date; change mode indicated by flashing C. Used in
conjunction with drag hands memories where the date/time
stamp will be recorded for each drag hand quantity.
Daylight Savings
disable
Allows automatic Daylight Savings time adjustment to be
enabled or disabled.
Configuration/Mtr Current Profile
Peak RMS % Change
xxx
Setting for Peak RMS current programmable from 10% to 200%
of the stored Peak RMS current to activate an alarm.
Average RMS % Change
xxx
Setting for Average RMS current programmable from 10% to
200% of the stored Average RMS current to activate an alarm.