A–34
M-6200A Instruction Book
Figure A-9 Communication Screens (page 5 of 6)
Communication/HMI
Set LCD Contrast: E
Allows contrast to be adjusted from +10 (lightest) to –10
(darkest). Factory setting is 0, which provides a neutral contrast.
User Line 1 E
Beckwith Electric
Allows input of 20 ASCII characters to configure a unit locator or
description. If not configured, a row of 15 asterisks will appear
in top row of User Line #1 screen.
User Line 2 E
M-6200A
Allows input of 20 ASCII characters to configure a unit locator or
description. If not configured, a row of 15 asterisks will appear
in bottom row of User Line #2 screen.
Level 1 Access Code
Press ENT to change
Configures a six-digit alpha/numerical Access Code for Level 1.
Factory setting is 000000 (disabled).
Level 2 Access Code
Press ENT to change
Configures a six-digit alpha/numerical Access Code for Level 2.
Factory setting is 222222.
Clear Osc Records
Ready Press ENTER
Allows the user to clear Oscillograph records from the HMI.
Oscillograph Message
ENABLE
Feature enables or disables the OSC Triggered Message to be
scrolled on the unit display when an OSC record is available.
Radius Secret Code
Press ENT to change
Allows the user to change the Radius Configuration Secret
Code.
IEEE 1686 Standard
not used/Authen with Encryp
Allows the user to enable IEEE 1686 Standard Cyber Security.
This option MUST be enabled in the control to allow User
Name/Password Cyber Security to be implemented.
OITE:
Q
Once IEEE 1686 Standard Cyber Security is
enabled, the user must enter a valid User Name
and Password to access any menus other than the
"Utilities/About" menu. This selection cannot be
changed to "not used" without entering a valid User
Name and Password.
Communication/Bluetooth
Bluetooth Enable
ENABLE
Enables or disables the Bluetooth feature when installed on the
control.
Bluetooth Reset
Ready Press ENTER
Allows the user to reset the Bluetooth Module to "Beckwith"
factory default settings.