M-3520 Instruction Book
6–40
81 Frequency (#1, #2, #3, or #4)
VOLTAGE INPUTS:
Configuration V1
CURRENT INPUTS:
None
TEST SETTINGS:
Pickup
P
Hz
(50.00 to 67.00)
50 Hz Relay
(40.00 to 57.00)
Time Delay
D
Cycles
(2 to 65,500)
Programmed Outputs
Z
Output
(1 to 8)
Function 59, 81 (#1, #2, #3, #4)
Disable
1.
Disable functions as shown. Refer to Section 3.2, Configure Relay Data, for procedure.
2.
Confirm settings to be tested.
3.
Connect inputs in Configuration V1 designated previously. Refer to Section 6.4,
Input Configurations
for configuration.
4.
Pickup Test
:
Set the voltages to the Nominal Frequency. Hold the
TARGET RESET
button in and
slowly decrease the frequency on the input voltage(s) until the
FREQUENCY 81
LED illuminates or
the pickup indicator operates on the computer target screen. The level of operation will be equal to
P
Hz
&
0.02 Hz from 57 to 63 (47 to 53), otherwise the accuracy is
&
0.1 Hz. Return to nominal input
frequency and the
OUTPUT
LED’s will extinguish. Press
TARGET RESET
button to remove targets.
5.
Time Test
: With output contacts being connected to the timer, apply
P
&
0.5 Hz and start timing.
The operating time will be
D
cycles within –2 to +3 cycles or
&
1%.
6.
Complete the testing for the remaining 81 functions by repeating steps 4 and 5, above.
7.
If testing is complete, enable any functions disabled for this test. If further testing is desired, check
the proper functions to disable for the next test and continue from this point.
Summary of Contents for M-3520
Page 1: ...Instruction Book M 3520 Intertie Protection Relay ...
Page 83: ...2 50 M 3520 Instruction Book This Page Left Intentionally Blank ...
Page 95: ...M 3520 Instruction Book 3 12 This Page Intentionally Left Blank ...
Page 133: ...M 3520 Instruction Book 5 12 This Page Intentionally Left Blank ...
Page 195: ...A 20 M 3520 Instruction Book This Page Intentionally Left Blank ...
Page 213: ...D 12 M 3520 Instruction Book This Page Intentionally Left Blank ...