Operation
EL2912
36
Version: 1.0.0
Under the
Connection
tab you can make further settings, e.g. the mapping of the info data or the behavior in
case of a module error.
Fig. 23: Connection tab of the alias device
The
Safety Parameters
tab contains the parameters of the EL2911 to be set. The output is parameterized via
parameter 0x8000. The inputs are configured via the objects 0x8010 and 0x8011.
Fig. 24: EL2912 parameters
Index
Name
Default value/
unit
Description
80x0:01 ModuloDiagTestPulse
0x00 / integer
Modulo value for the frequency of the generation of a
test pulse.
0 -> every time
1 -> every 2nd time
...
80x0:02 MultiplierDiagTestPulse
0x01 / integer
Length of the test pulse in multiples of 400 µs
80x0:03 Standard outputs active
FALSE / Boolean Activation of the logical AND operator of the safe and
standard outputs of the module
80x0:04 Diag TestPulse active
TRUE / Boolean
Activation of test pulses for the corresponding output
module
80x0:07 Module Fault Link active TRUE / Boolean
If a module error occurs in this module, a module
error is also set for all other modules of this
TwinSAFE component for which this parameter is set
to TRUE.