General operation / function
EJ19xx and EJ29xx
18
Version: 1.2.0
5.6
General technical data
Product property
EJx9xx
Supply voltage (SELV / PELV)
24 V
DC
(–15% / +20%)
Permissible ambient temperature (operation)
-25°C to +55°C
Permissible ambient temperature (transport/
storage)
-40°C to +70°C
Permissible air humidity
5% to 95%, non-condensing
Permissible air pressure (operation/storage/
transport)
750 hPa to 1100 hPa
(this corresponds to an altitude of approx. -690 m to
2450 m above sea level, assuming an international
standard atmosphere)
Minimum/maximum cycle time
approx. 500 µs / according to project size (if a user-
specific project is used)
Fault response time
≤ watchdog times
Watchdog time
min. 2 ms, max. 60,000 ms
Cable length between sensor/actuator and terminal unshielded max. 100 m (0.75 or 1 mm²)
shielded max. 100 m (0.75 or 1 mm²)
Input process image
dynamic in accordance with the configuration
Output process image
dynamic in accordance with the configuration
Reaction time (read input/write to E-bus)
typically: 4 ms,
maximally: see error reaction time
Output current of the clock outputs
typically 8 mA, max. 11 mA
Output current of the outputs
max. 500 mA
Actuators
• inductive
• resistive
• capacitive
When selecting actuators please ensure that the test
pulses do not lead to actuator switching
Actuator switching frequency (inductive load)
max. 2.5 mH at 100 Hz
max. 1 H at 1 Hz
These are example working points. The user must
evaluate the actuators used in relation to energy.
Reading back the outputs
(Diagnostic thresholds)
Signal voltage “1”: > 5.61 V
Signal voltage “0”: < 1.68 V
Signal voltage "0" inputs
-3 V ... 5 V (EN 61131-2, type 3) see chapter
Characteristic curve of the inputs [
Signal voltage "1" inputs
11 V ... 30 V (EN 61131-2, type 3) see chapter
Characteristic curve of the inputs [
Climate category according to EN 60721-3-3
3K3
(the deviation from 3K3 is possible only with optimal
environmental conditions and also applies only to the
technical data which are specified differently in this
documentation)
Permissible level of contamination according to
EN 60664-1
level of contamination 2