Intended use
EJ19xx and EJ29xx
11
Version: 1.2.0
4
Intended use
WARNING
Caution - Risk of injury!
TwinSAFE EJ modules may only be used for the purposes described below!
The TwinSAFE EJ modules expand the application range of the Beckhoff EtherCAT system by functions that
enable it to be used in the field of machine safety as well. The TwinSAFE EJ modules are designed for
machine safety functions and directly associated to industrial automation tasks. It is therefore approved only
for applications with a defined fail-safe state. This safe state is the wattless state.
The TwinSAFE EJ modules are suitable for operation on an EJ distribution board.
WARNING
System limits
The TÜV-SÜD certificate applies to the TwinSAFE EJ modules, the function blocks avail-
able in it, the documentation and the engineering tool. Approved engineering tools are
TwinCAT 3.1
,
TwinSAFE Loader
and
CODESYS Safety for EtherCAT Safety Module
. Any
deviations from these procedures or tools, particularly externally generated xml files for
TwinSAFE import or externally generated automatic project creation procedures, are not
covered by the certificate.
WARNING
Power supply
An SELV/PELV power supply unit with a voltage limit of U
max
= 36 V
DC
on the output side
must be used to supply power for the TwinSAFE EJ modules with 24 V
DC
. Failure to ob-
serve this can result in a loss of safety.
WARNING
Commissioning test
Before the TwinSAFE EJ modules can be used for the safety task, the user must carry out
a commissioning test so that sensor and actuator wiring errors can be ruled out.
CAUTION
Note the Machinery Directive
The TwinSAFE EJ modules may only be used in machines according to the machinery di-
rective.
CAUTION
Ensure traceability
The buyer has to ensure the traceability of the device via the serial number.