Product overview
KL4494
9
Version: 2.0.0
Neither user nor manufacturer scaling is active
Y
a
= (B
a
+ X
ADC
) x A
a
(1.0)
Y
out
= Y
a
Manufacturer scaling active (default setting)
Y
1
= B
h
+ A
h
x Y
a
(1.1)
Y
out
= Y
1
User scaling active
Y
2
= B
w
+ A
w
x Y
a
(1.2)
Y
out
= Y
2
Manufacturer and user scaling active
Y
1
= B
h
+ A
h
x Y
a
(1.3)
Y
2
= B
w
+ A
w
x Y
1
(1.4)
Y
out
= Y
2
Key
X
adc
:
Output values of the A/D converter
Y
out
:
Process data to PLC
B
a
, A
a
:
Manufacturer gain and offset compensation
(
,
)
B
h
, A
h
:
Manufacturer scaling
(Not implemented)
B
w
, A
w
:
User scaling
(
,
)
The equations of the straight line are activated via register R32.
Analog output channels
The analog output channels of the KL4494 generate signals in the range from -10 V to +10 V with a
resolution of 12 bits (4095 steps). The outputs are single-ended outputs with a common ground potential.
Format of the output values
In the delivery state the process data are shown in two's complement form ( -1
integer
corresponds to 0xFFFF).
can be selected via the feature register R32 as an alternative.
Output value
Output voltage
hexadecimal
decimal
0x8000
-32768
-10 V
0xC001
-16383
-5 V
0x0000
0
0 V
0x3FFF
16383
+5 V
0x7FFF
32767
+10 V
Process data equations
The process data, which are transferred to the Bus Terminal, are calculated based on the following
equations:
Neither user nor manufacturer scaling is active
Y
dac
= X x A
a
+ B
a
(1.0)