Access from the user program
KL4494
34
Version: 2.0.0
R32: Feature register
The feature register specifies the terminal's configuration. Default: 0x0404 (1028
dec
)
High-Byte: analog output configuration
Bit
R32.15
R32.14
R32.13
R32.12
R32.11
R32.10
R32.9
R32.8
Name
-
-
-
enUsrDefault
enSiemens
enWDT
enManScal
enUsrScal
Low-Byte: analog input configuration
Bit
R32.7
R32.6
R32.5
R32.4
R32.3
R32.2
R32.1
R32.0
Name
-
-
-
-
enSiemens
enWDT
enManScal
enUsrScal
Key
Bit
Name
Description
default
R32.15
-
reserved
0
bin
...
...
...
...
R32.13
-
reserved
0
bin
R32.12
enUsrDefault
1
bin
User default value specified via register
0
bin
R32.11
enSiemens
Analog Output
0
bin
Standard output format
0
bin
1
bin
Siemens output format
R32.10
enWDT
1
bin
Watchdog timer is active
1
bin
R32.9
enManScal
Analog Output
0
bin
Manufacturer scaling is active
0
bin
1
bin
Manufacturer scaling is not active
R32.8
enUsrScal
Analog Output
0
bin
User scaling is not active
0
bin
1
bin
User scaling is active
R32.7
-
reserved
0
bin
R32.6
-
reserved
0
bin
R32.5
-
reserved
0
bin
R32.4
-
reserved
0
bin
R32.3
enSiemens
Analog Input
0
bin
Standard output format
0
bin
1
bin
Siemens output format:
The three bits with the lowest value are used for displaying status in-
formation (see below).
R32.2
enWDT
1
bin
Watchdog timer is active
1
bin
R32.1
enManScal
Analog Input
0
bin
Manufacturer scaling is active
0
bin
1
bin
Manufacturer scaling is not active
R32.0
enUsrScal
Analog Input
0
bin
User scaling is not active
0
bin
1
bin
User scaling is active
Siemens output format
If the Siemens output format is selected, the lowest three bits are used for status evaluation. The process
data is represented in bits 15 to 3, with bit 15 representing the sign bit. Scaling of the measured value
according to the Siemens standard has to be done via user scaling (R33, R34).
Measured value
Bit 15 ... 3
Bit 2
X
Bit 1
Error
Bit 0
Overflow
Measured value < -10 V
0
0
1
-10 V < Measured value < 10 V
Process data
0
0
0
Measured value >+10 V
0
0
1
R33: User scaling for analog input - offset (B
w
)
This register contains the offset of the user scaling for the analog input (default: 0).
User scaling for the analog input can be activated in the feature register via bit
Summary of Contents for KL4494